- Table of Contents
- Related Documents
-
Title | Size | Download |
---|---|---|
01-Text | 2.46 MB |
Examining the installation site
Installing the switch in a 19-inch rack
Rack-mounting procedure at a glance
Chassis dimensions and rack requirements
Attaching the mounting brackets, chassis rails, and grounding cable to the chassis
Attaching the slide rails to the rack
Mounting the switch in the rack
Grounding the switch by using a grounding strip
Installing and removing a fan tray
Installing and removing a power supply
Connecting the power cord for a PSR450-12A/PSR450-12A1 power supply
Connecting the power cord for a PSR450-12AHD power supply
Connecting the DC power cord for a PSR450-12D power supply
3 Accessing the switch for the first time
Setting up the configuration environment
Connecting the serial console cable
Connecting a mini USB console cable
Planning IRF fabric size and the installation site
Identifying the master switch and planning IRF member IDs
Planning IRF topology and connections
Identifying physical IRF ports on the member switches
Configuring basic IRF settings
Connecting the physical IRF ports
Accessing the IRF fabric to verify the configuration
5 Maintenance and troubleshooting
Configuration terminal display issues
No display on the configuration terminal
Garbled display on the configuration terminal
6 Appendix A Chassis views and technical specifications
7 Appendix B FRUs and compatibility matrixes
1/10GBASE-T autosensing Ethernet port
1/10GBASE-T autosensing Ethernet port LEDs
1
Preparing for installation
The S6805 switch series includes the following models:
Part No. |
Product code |
Product model |
0235A3EU |
LS-6805-54HF |
S6805-54HF |
0235A2EM |
LS-6805-54HT |
S6805-54HT |
Safety recommendations
To avoid any equipment damage or bodily injury caused by incorrect use, read the following safety recommendations before installation. Note that the recommendations do not cover every possible hazardous condition.
· Before cleaning the switch, remove all power cords from the switch. Do not clean the switch with wet cloth or liquid.
· Do not place the switch near water or in a damp environment. Prevent water or moisture from entering the switch chassis.
· Do not place the switch on an unstable case or desk. The switch might be severely damaged in case of a fall.
· Ensure good ventilation of the equipment room and keep the air inlet and outlet vents of the switch free of obstruction.
· Connect the yellow-green protection grounding cable before power-on.
· Make sure the operating voltage is in the required range.
· To avoid electrical shocks, do not open the chassis while the switch is operating or when the switch is just powered off.
· When replacing FRUs, including power supplies and fan trays, wear an ESD wrist strap to avoid damaging the units.
Examining the installation site
The switch must be used indoors. Mount your switch in a rack and verify the following items:
· Adequate clearance is reserved at the air inlet and outlet vents for ventilation.
· The rack has a good ventilation system.
· Identify the hot aisle and cold aisle at the installation site, and make sure ambient air flows into the switch from the cold aisle and exhausts to the hot aisle.
· Identify the airflow designs of neighboring devices, and prevent hot air flowing out of the bottom device from entering the top device.
· The rack is sturdy enough to support the switch and its accessories.
· The rack is reliably grounded.
To ensure correct operation and long service life of your switch, install it in an environment that meets the requirements described in the following subsections.
Temperature/humidity
Maintain appropriate temperature and humidity in the equipment room.
· Lasting high relative humidity can cause poor insulation, electricity leakage, mechanical property change of materials, and metal corrosion.
· Lasting low relative humidity can cause washer contraction and ESD and cause problems including loose screws and circuit failure.
· High temperature can accelerate the aging of insulation materials and significantly lower the reliability and lifespan of the switch.
For the temperature and humidity requirements of different switch models, see "Appendix A Chassis views and technical specifications."
Cleanliness
Dust buildup on the chassis might result in electrostatic adsorption, which causes poor contact of metal components and contact points, especially when indoor relative humidity is low. In the worst case, electrostatic adsorption can cause communication failure.
Table1-1 Dust concentration limit in the equipment room
Substance |
Particle diameter |
Concentration limit |
Dust particles |
≥ 5 µm |
≤ 3 x 104 particles/m3 (No visible dust on desk in three days) |
Dust (suspension) |
≤ 75 µm |
≤ 0.2 mg/m3 |
Dust (sedimentation) |
75 µm to 150 µm |
≤ 1.5 mg/(m2h) |
Sand |
≥ 150 µm |
≤ 30 mg/m3 |
The equipment room must also meet strict limits on salts, acids, and sulfides to eliminate corrosion and premature aging of components, as shown in Table1-2.
Table1-2 Harmful gas limits in the equipment room
Gas |
Maximum concentration (mg/m3) |
SO2 |
0.2 |
H2S |
0.006 |
NH3 |
0.05 |
Cl2 |
0.01 |
EMI
All electromagnetic interference (EMI) sources, from outside or inside of the switch and application system, adversely affect the switch in the following ways:
· A conduction pattern of capacitance coupling.
· Inductance coupling.
· Electromagnetic wave radiation.
· Common impedance (including the grounding system) coupling.
To prevent EMI, use the following guidelines:
· If AC power is used, use a single-phase three-wire power receptacle with protection earth (PE) to filter interference from the power grid.
· Keep the switch far away from radio transmitting stations, radar stations, and high-frequency devices.
· Use electromagnetic shielding, for example, shielded interface cables, when necessary.
· To prevent signal ports from getting damaged by overvoltage or overcurrent caused by lightning strikes, route interface cables only indoors.
Laser safety
|
WARNING! · The switch is a Class 1M laser device. · Disconnected optical fibers or transceiver modules might emit invisible laser light. Do not stare into beams or view directly with optical instruments when the switch is operating. |
Installation tools
No installation tools are provided with the switch. Prepare the following tools yourself:
· Phillips screwdriver.
· Flathead screwdriver.
· ESD wrist strap.
· Marker.
Installation accessories
Before installation, make sure you have all the required installation accessories. If any accessory is damaged or missing, use the part No. provided in this table to purchase a new one.
Table1-3 Installation accessories
Part No. |
Description |
Quantity |
Applicable device models |
0223A19T |
Mounting brackets |
1 pair, provided |
All S6805 models |
2150A050 |
1U rack mounting rail kit A (long slide rails) |
1 kit, provided |
All S6805 models |
2150A0CP |
1U rack mounting rail kit B (super-short slide rails) |
Optional |
S6805-54HF |
2150A05D |
1U rack mounting rail kit C |
Optional |
S6805-54HT |
N/A |
M6 screw and cage nut |
User supplied |
All S6805 models |
0404A0KM |
Grounding cable |
1, provided |
All S6805 models |
N/A |
Grounding screw |
2, provided |
All S6805 models |
2114A09C |
Power supply filler panel |
1, provided |
All S6805 models |
N/A |
Releasable cable tie |
User supplied |
All S6805 models |
04042967 |
Serial console cable |
1, provided |
All S6805 models |
14990101 |
SFP port plug |
Same number as the SFP/SFP+ ports |
All S6805 models |
1499A01G |
QSFP port plug |
Same number as the QSFP28 ports |
All S6805 models |
2 Installing the
switch
|
CAUTION: Keep the tamper-proof seal on a mounting screw on the chassis cover intact, and if you want to open the chassis, contact H3C for permission. Otherwise, H3C shall not be liable for any consequence caused thereby. |
|
CAUTION: Always wear an ESD wrist strap during the installation process. Make sure the wrist strap makes good skin contact and is reliably grounded. |
Figure2-1 Hardware installation flow
Installing the switch in a 19-inch rack
Installation accessories
Table2-2 Installation accessories
Switch model |
Mounting brackets |
Rack mounting rail kit |
S6805-54HF |
1U high, one pair (provided). See Figure2-2. |
· 1U rack mounting rail kit A, including one pair of chassis rails and one pair of long slide rails (provided). See Figure2-3. · 1U rack mounting rail kit B, including one pair of chassis rails and one pair of super-short slide rails (optional). See Figure2-4. |
S6805-54HT |
1U high, one pair (provided). See Figure2-2. |
· 1U rack mounting rail kit A, including one pair of chassis rails and one pair of long slide rails (provided). See Figure2-3. · 1U rack mounting rail kit C, including one pair of chassis rails and one pair of slide rails (optional). See Figure2-5. |
Figure2-3 1U rack mounting rail kit A (long slide rails)
(1) Chassis rail |
(2) Long slide rail |
Figure2-4 1U rack mounting rail kit B (super-short slide rails)
(1) Chassis rail |
(2) Super-short slide rail |
Figure2-5 1U rack mounting rail kit C
(1) Chassis rail |
(2) Slide rail |
Rack-mounting procedure at a glance
Figure2-6 Rack-mounting procedure
|
NOTE: If a rack shelf is available, you can put the switch on the rack shelf, slide the switch to an appropriate location, and attach the switch to the rack with the mounting brackets. |
Chassis dimensions and rack requirements
Figure2-7 S6805-54HF chassis dimensions with the mounting brackets installed at the port side
(1) Power supply handle |
(2) Mounting bracket |
Figure2-8 S6805-54HF chassis dimensions with the mounting brackets installed at the power supply side
(1) Power supply handle |
(2) Mounting bracket |
Figure2-9 S6805-54HT chassis dimensions with the mounting brackets installed at the port side
(1) Power supply handle |
(2) Mounting bracket |
Figure2-10 S6805-54HT chassis dimensions with the mounting brackets installed at the power supply side
(1) Power supply handle |
(2) Mounting bracket |
Follow these guidelines when you install the switch in a 19-inch rack:
· The distance between the front and rear posts of the rack must meet the requirements described in Table2-3.
· To secure the switch to the rack, you must install not only mounting brackets, but also chassis rails and slide rails.
Table2-3 Distance requirements between the front and rear rack posts
Switch model |
Installation method |
Distance between the front and rear rack posts |
S6805-54HF |
Using mounting brackets and rack mounting rail kit A (long slide rails) |
621 mm to 793 mm (24.45 in to 31.22 in) |
Using mounting brackets and rack mounting rail kit B (super-short slide rails, narrow-spacing installation) |
330 mm to 505 mm (12.99 in to 19.88 in) |
|
Using mounting brackets and rack mounting rail kit B (super-short slide rails, wide-spacing installation) |
438 mm to 632 mm (17.24 in to 24.88 in) |
|
S6805-54HT |
Using mounting brackets and rack mounting rail kit A (long slide rails) |
621 mm to 854 mm (24.45 in to 33.62 in) |
Using mounting brackets and rack mounting rail kit C |
401 mm to 634 mm (15.79 in to 24.96 in) |
Table2-4 Chassis dimensions and rack depth requirements
Device model |
Chassis dimensions |
Rack depth requirement |
S6805-54HF |
· Height—44 mm (1.73 in) (1 RU) · Width—440 mm (17.32 in). · Total depth—425 mm (16.73 in) ¡ 25 mm (0.98 in) for the power supply or fan tray handle ¡ 400 mm (15.75 in) for the chassis. |
To ensure that the rack door can be closed easily after cables are connected, make sure the rack meets the following requirements: · A minimum of 800 mm (31.50 in) in depth (recommended) · A minimum of 130 mm (5.12 in) from the front rack post to the front door · A minimum of 449 mm (17.68 in) from the front rack post to the rear door |
S6805-54HT |
· Height—44 mm (1.73 in) (1 RU) · Width—440 mm (17.32 in). · Total depth—485 mm (19.09 in) ¡ 25 mm (0.98 in) for the power supply or fan tray handle ¡ 460 mm (18.11 in) for the chassis. |
To ensure that the rack door can be closed easily after cables are connected, make sure the rack meets the following requirements: · A minimum of 800 mm (31.50 in) in depth (recommended) · A minimum of 130 mm (5.12 in) from the front rack post to the front door · A minimum of 509 mm (20.04 in) from the front rack post to the rear door |
Attaching
the mounting brackets, chassis rails, and grounding cable to the chassis
The switch has two mounting bracket installation positions on its two side panels: one near the network port side and one near the power supply side.
The switch provides a primary grounding point (with a grounding sign) and an auxiliary grounding point.
The S6805-54HF and S6805-54HT switches are identical in the mounting bracket installation positions and grounding point positions. Figure2-11 describes these positions on the S6805-54HF switch.
Figure2-11 Mounting bracket installation positions and grounding point positions on the S6805-54HF switch
(1) Mounting bracket installation position near the power supply side |
|
(2) Primary grounding point |
(3) Auxiliary grounding point |
(4) Mounting bracket installation position near the port side |
Attaching the mounting brackets and chassis rails to the chassis
|
IMPORTANT: M4 screws are used to secure the mounting brackets and chassis rails to the switch. As a best practice, use a torque of 12 kgf-cm (1.18 Nm) to fasten M4 screws. |
To attach the mounting brackets and chassis rails to the chassis:
1. Place the wide flange of a mounting bracket against a side panel of the chassis and align the round holes in the wide flange of the front mounting bracket with the screw holes in the side panel. Then use M4 screws (provided) to attach the mounting bracket to the chassis.
¡ To install the mounting brackets at the port side, see Figure2-12, Figure2-13, Figure2-14, and Figure2-18.
¡ To install the mounting brackets at the power supply side, see Figure2-15, Figure2-16, Figure2-17, and Figure2-19.
2. Determine the chassis rail installation position based on the mounting bracket installation position.
3. Place the chassis rail against the side panel of the chassis and align the installation holes in the chassis rail with rail mounting holes in the chassis. Then use M4 screws (provided) to attach the chassis rail to the chassis.
¡ For installation of chassis rails of rack mounting rail kit A (long slide rails) and rack mounting rail kit C, see Figure2-12, Figure2-15, Figure2-18, and Figure2-19.
¡ The chassis rails of rack mounting rail kit B (super-short slide rails) support narrow-spacing installation and wide-spacing installation. Select narrow-spacing (as shown in Figure2-13 and Figure2-16) or wide-spacing (as shown in Figure2-14 and Figure2-17) installation based on the distance between the front and rear rack posts.
4. Follow the same procedure to attach another mounting bracket and chassis rail to the opposite side.
Figure2-12 Attaching the mounting brackets and chassis rails to an S6805-54HF switch (mounting brackets installed near the port side, rack mounting rail kit A)
Figure2-13 Attaching the mounting brackets and chassis rails to an S6805-54HF switch (mounting brackets installed near the port side, rack mounting rail kit B, narrow-spacing installation)
Figure2-14 Attaching the mounting brackets and chassis rails to an S6805-54HF switch (mounting brackets installed near the port side, rack mounting rail kit B, wide-spacing installation)
Figure2-16 Attaching the mounting brackets and chassis rails to an S6805-54HF switch (mounting brackets installed near the power supply side, rack mounting rail kit B, narrow-spacing installation)
Figure2-17 Attaching the mounting brackets and chassis rails to an S6805-54HF (mounting brackets installed near the power supply side, rack mounting rail kit B, wide-spacing installation)
Connecting the grounding cable to the chassis
|
IMPORTANT: The primary and auxiliary grounding points are located on the left side panel of the chassis. The two grounding points might be not reachable after the switch is mounted in the rack. Connect the grounding cable to a grounding point before you mount the switch in the rack. |
Select the primary or auxiliary grounding point as required. The following procedure connects the grounding cable to the primary grounding point (near the power supply side) on an S6805-54HF switch.
To connect the grounding cable to a grounding point:
1. Unpack the grounding cable and grounding screws (applicable to both the primary and auxiliary grounding points).
2. Use the grounding screws to attach the two-hole grounding lug to the grounding point and then fasten the screws, as shown in Figure2-20.
As a best practice, use a torque of 20 kgf-cm (1.96 Nm) to fasten the grounding screws.
Figure2-20 Attaching the grounding cable to the primary grounding point on an S6805-54HF switch
Attaching the slide rails to the rack
|
IMPORTANT: M6 screws and cage nuts are used to attach the slide rails to the rack. Prepare M6 screws and cage nuts yourself. As a best practice, use a torque of 30 kgf-cm (2.94 Nm) to fasten the M6 screws. |
Before mounting the switch in the rack, you must attach slide rails to the rack.
The installation procedure is the same for different types of slide rails. The following procedure attaches 1U long slide rails to the rack.
To attach the slide rails to the rack:
1. Identify the slide rail installation position on the rack based on the switch installation position.
2. Install cage nuts (user-supplied) in the mounting holes in the rack posts.
3. Align the screw holes in one slide rail with the cage nuts in a rear rack post, and then use M6 screws (user-supplied) to attach the slide rail to the rack, as shown in Figure2-21.
4. Attach the other slide rail to the rear rack post on the opposite side.
Make sure the two slide rails are at the same height and can slide into the chassis rails smoothly.
Figure2-21 Installing the 1U long slide rails
Mounting the switch in the rack
The rack-mounting procedure is similar for the switches. The following procedure mounts an S6805-54HF switch in a rack.
This task requires two people.
To mount the switch in the rack:
1. Wear an ESD wrist strap and make sure it makes good skin contact and is reliably grounded.
2. Verify that the mounting brackets and chassis rails have been securely attached to the switch chassis.
3. Verify that the slide rails have been correctly attached to the rear rack posts.
4. Attach cage nuts (user-supplied) to the front rack posts and make sure they are at the same level as the slide rails.
5. One person performs the following operations:
a. Supporting the bottom of the switch, aligns the chassis rails with the slide rails on the rack posts.
b. Pushes the switch slowly for the slide rails to slide into the chassis rails smoothly until the mounting brackets are flush against the front rack posts.
- For long slide rails of rack mounting rail kit A and slide rails of rack mounting rail kit C, make sure the front ends of the slide rails reach out of the chassis rails.
- For super-short slide rails of rack mounting rail kit B, make sure the slide rails slide a minimum length of 90 mm (3.54 in) into the chassis rails.
6. The other person uses screws (user-supplied, rust-proofed) to attach the mounting brackets to the rack.
Figure2-23 Mounting an S6805-54HF switch in the rack (mounting brackets installed near the port side)
Grounding the switch by using a
grounding strip
|
CAUTION: · Correctly connecting the grounding cable is crucial to lightning protection and EMI protection. · Do not connect the grounding cable to a fire main or lightning rod. · To guarantee the grounding effect and avoid switch damage, use the grounding cable provided with the switch to connect the switch to a grounding strip in the equipment room. · For information about lightning protection for the switch, see H3C Lightning Protection Guide. |
The power input end of the switch has a noise filter, whose central ground is directly connected to the chassis to form the chassis ground (commonly known as PGND). You must securely connect this chassis ground to the earth so the faradism and leakage electricity can be safely released to the earth to minimize EMI susceptibility of the switch.
To ground the switch by using a grounding strip:
1. Attach the two-hole grounding lug at one end of the grounding cable to a grounding point on the switch chassis. For more information, see "Connecting the grounding cable to the chassis."
2. Remove the hex nut of a grounding post on the grounding strip.
3. Attach the ring terminal at the other end of the grounding cable to the grounding post on the grounding strip, and secure the ring terminal to the grounding post with the hex nut.
Figure2-24 Connecting the grounding cable to a grounding strip
(1) Hex nut |
(2) Ring terminal |
(3) Grounding post |
(4) Grounding strip |
Installing and
removing a fan tray
|
CAUTION: · For adequate heat dissipation, you must install five fan trays of the same model for the switch. · Make sure all slots have a module installed when the switch is operating. · If more than one fan tray fails during switch operation, do not remove the failed fan trays simultaneously. Replace the fan trays one by one and finish replacing each fan tray within three minutes. |
Installing a fan tray
|
CAUTION: To prevent damage to the fan tray or the connectors on the backplane, insert the fan tray gently. If you encounter a hard resistance while inserting the fan tray, pull out the fan tray and insert it again. |
Select fan trays for the switch as needed. For the fan trays available for the switch and their specifications, see "Fan trays."
To install an LSPM1FANSA or LSPM1FANSB fan tray:
1. Wear an ESD wrist strap and make sure it makes good skin contact and is reliably grounded.
2. Unpack the fan tray and verify that the fan tray model is correct.
3. Orient the fan tray with the "TOP" mark facing upward. Grasp the handle of the fan tray with one hand and support the fan tray bottom with the other, and slide the fan tray along the guide rails into the slot until the fan tray is fully seated in the slot and has a firm contact with the backplane.
Figure2-25 Installing a fan tray (LSPM1FANSA)
Removing a fan tray
|
WARNING! · Ensure electricity safety and never touch the rotating fans when you hot-swap a fan tray. · To prevent an unbalanced fan from causing loud noise, do not touch the fans, even if they are not rotating. · Do not touch any bare wires and terminals on a fan tray. · Do not place a fan tray in a moist location or let liquid flow into it. · Contact H3C Support if the circuits or components on a fan tray are faulty. Do not remove any fan tray components. |
To remove an LSPM1FANSA or LSPM1FANSB fan tray:
1. Wear an ESD wrist strap and make sure it makes good skin contact and is reliably grounded.
2. Grasp the fan tray handle and pull out the fan tray slowly along the guide rails.
3. Place the removed fan tray in an antistatic bag.
Figure2-26 Removing a fan tray (LSPM1FANSA)
Installing and
removing a power supply
The switch comes with power supply slot PWR1 empty and power supply slot PWR2 installed with a filler panel. As a best practice, install two power supplies of the same model for the switch.
Select power supplies for the switch as required. For the power supplies available for the switch and their specifications, see "Power supplies."
Precautions
· Provide a separate circuit breaker for each power supply.
· Do not install power supplies of different model on the same switch.
· To avoid device damage and body injury, strictly follow procedures in Figure2-27 and Figure2-28 to install and remove a power supply, respectively.
Figure2-27 Installation procedure
· If a power supply slot is empty, install a filler panel in it to ensure adequate heat dissipation.
Installing a power supply
To install a power supply:
1. Wear an ESD wrist strap and make sure it makes good skin contact and is reliably grounded.
2. Unpack the power supply and verify that the power supply model is correct.
3. Correctly orient the power supply with the lettering on it upward. Grasp the handle of the power supply with one hand and support its bottom with the other, and slide the power supply slowly along the guide rails into the slot. Make sure the power supply has good contact with the backplane.
To prevent connector damages, insert the power supply gently. The power supply and power supply slot have disorientation rejection designs. If you encounter a hard resistance while inserting the power supply, pull out the power supply and insert it again.
Figure2-29 Installing a power supply
|
IMPORTANT: If the target power supply slot has a filler panel installed, first remove the filler panel from the slot (as shown Figure2-30). |
Figure2-30 Removing the filler panel from a power supply slot
Removing a power supply
|
CAUTION: When the switch has two power supplies in 1+1 redundancy mode, removing one power supply does not affect the operation of the switch. When the switch has only one power supply installed, removing the power supply powers off the switch. |
Removing
a PSR450-12A/PSR450-12A1 power supply
The removal procedure is the same for the PSR450-12A and PSR450-12A1 power supplies. The following procedure removes a PSR450-12A power supply from an S6805-54HF switch.
To remove a PSR450-12A power supply:
1. Wear an ESD wrist strap and make sure it makes good skin contact and is reliably grounded.
2. Remove the power cord.
3. Hold the handle on the power supply with one hand, pivot the latch on the power supply to the right with your thumb, and pull the power supply part way out of the slot, as shown in Figure2-31.
4. Supporting the power supply bottom with one hand, slowly pull the power supply out with the other hand.
5. Place the removed power supply in an antistatic bag for future use.
Figure2-31 Removing a PSR250-12A power supply
(1) Pivot the latch to the right with your thumb |
(2) Pull the power supply out |
Removing
a PSR450-12AHD power supply
The following procedure removes a PSR450-12AHD power supply from an S6805-54HF switch.
To remove a PSR450-12AHD power supply:
1. Wear an ESD wrist strap and make sure it makes good skin contact and is reliably grounded.
2. Remove the power cord from the power supply.
a. Release the locking tab on the cable clamp and then open the cable clamp (see Figure2-32).
b. Remove the power cord connector from the power supply (see Figure2-33).
Figure2-32 Opening the cable clamp
Figure2-33 Removing the power cord from the power supply
3. Hold the handle of the power supply with one hand, press the latch on the power supply to the right with your thumb, and simultaneously pull the power supply part way out of the slot. Supporting the power supply bottom with the other hand, slowly pull the power supply out of the slot along the guide rails.
4. Put the removed power supply in an antistatic bag for future use.
Removing
a PSR450-12D DC power supply
The following procedure removes a PSR450-12D power supply from an S6805-54HT switch.
To remove a PSR450-12D power supply:
1. Wear an ESD wrist strap and make sure it makes good skin contact and is reliably grounded.
2. Use a flat-head screwdriver to loosen the screws on the power cord connector, and then pull the connector out to remove the power cord. See Figure2-34.
3. Hold the handle on the power supply with one hand, pivot the latch on the power supply to the right with your thumb, and simultaneously pull the power supply part way out of the slot. Supporting the power supply bottom with the other, slowly pull the power supply out of the slot. See Figure2-31.
4. Put the removed power supply in an antistatic bag.
Figure2-34 Removing a PSR450-12D power supply
(1) Use a flat-head screwdriver to loosen the screws on the power cord connector |
(2) Pull the power cord connector out |
Connecting the power cord
|
WARNING! Provide a circuit breaker for each power input. When you connect a power cord, make sure the circuit breaker is switched off. |
Connecting the power cord for a PSR450-12A/PSR450-12A1 power supply
1. Insert the female connector of the power cord supplied with the power supply into the power receptacle on the power supply.
2. Use a releasable cable tie to secure the power cord to the handle of the power supply, as shown in Figure2-35.
3. Connect the other end of the power cord to an AC or DC power source.
Figure2-35 Connecting the power cord (PSR450-12A power supply)
(1) Releasable cable tie |
(2) Fasten the cable tie to secure the power cord to the handle of the power supply |
Connecting
the power cord for a PSR450-12AHD power supply
1. Slide the cable clamp onto the tie mount on the power supply, as shown in Figure2-36.
2. Connect the female connector of the power cord to the power receptacle on the power supply, as shown in Figure2-37
3. Close the cable clamp and slide it forward until it is flush against the edge of the female connector, as shown in Figure2-38.
4. Connect the other end of the power cord to an AC or DC power source.
Figure2-36 Connecting the power cord for a PSR450-12AHD power supply (1)
Figure2-37 Connecting the power cord for a PSR450-12AHD power supply (2)
Figure2-38 Connecting the power cord for a PSR450-12AHD power supply (3)
Connecting the DC power cord for a PSR450-12D
power supply
1. Correctly orient the DC power cord connector and insert the connector into the power receptacle on the power supply.
If you orient the DC power cord connector upside down, you cannot insert the connector into the power receptacle.
2. Use a flat-head screwdriver to fasten the screws on the power cord connector, as shown in Figure2-39.
3. Connect the other end of the power cord to a DC power source.
Figure2-39 Connecting the DC power cord for a PSR450-12D power supply
Verifying the installation
After you complete the installation, verify the following items:
· There is enough space for heat dissipation around the switch, and the rack is stable.
· The grounding cable is securely connected.
· The power source is as required by the switch.
· The power cords are correctly connected.
· If part of the network cable for a port is routed outdoors, verify that a network port lightning protector is used for the port.
· If a power line is routed from outdoors, verify that a surge protected power strip is used for the switch.
3 Accessing the switch for the first time
Setting up the
configuration environment
You can access the switch from the serial console port or the mini USB console port. As a best practice, use the serial console port to access the switch (the switch is provided with a serial console cable). To access the switch from the mini USB console port, prepare a mini USB console cable yourself.
In the following figure, the switch is connected to a PC from the serial console port.
Figure3-1 Connecting the switch to a terminal from the serial console port
Connecting the
serial console cable
A serial console cable is an 8-core cable, with a crimped RJ-45 connector at one end for connecting to the serial console port of the switch, and a DB-9 female connector at the other end for connecting to the serial port on the console terminal.
Figure3-2 Serial console cable
Table3-1 Serial console cable pinout
RJ-45 |
Signal |
DB-9 |
Signal |
1 |
RTS |
8 |
CTS |
2 |
DTR |
6 |
DSR |
3 |
TXD |
2 |
RXD |
4 |
SG |
5 |
SG |
5 |
SG |
5 |
SG |
6 |
RXD |
3 |
TXD |
7 |
DSR |
4 |
DTR |
8 |
CTS |
7 |
RTS |
To connect the switch to a terminal (for example, a PC) by using the serial console cable:
1. Plug the DB-9 female connector of the serial console cable to the serial port of the PC.
2. Connect the RJ-45 connector to the serial console port of the switch.
|
NOTE: · Identify the mark on the console port and make sure you are connecting to the correct port. · The serial ports on PCs do not support hot swapping. To connect a PC to an operating switch, first connect the PC end. To disconnect a PC from an operating switch, first disconnect the switch end. |
Connecting a mini USB console cable
A USB mini console cable has a USB mini-Type B connector at one end to connect to the Mini USB console port of the switch, and a standard USB Type A connector at the other end to connect to the USB port on the configuration terminal.
To connect the switch to a configuration terminal by using a USB mini console cable:
1. Connect the standard USB Type A connector to the USB port on the configuration terminal.
2. Connect the USB mini Type B connector to the Mini USB console port on the switch.
3. Click http://www.h3c.com/en/home/USB_Console/, or copy it to the address bar on the browser to log in to download page of the USB console driver, and download the driver.
4. Select a driver program according to the operating system you use:
¡ XR21V1410_XR21B1411_Windows_Ver1840_x86_Installer.EXE—32-bit operating system.
¡ XR21V1410_XR21B1411_Windows_Ver1840_x64_Installer.EXE—64-bit operating system.
5. Click Next on the installation wizard.
Figure3-3 Device Driver Installation Wizard
6. Click Continue Anyway if the following dialog box appears.
Figure3-4 Software Installation
7. Click Finish.
Figure3-5 Completing the device driver installation wizard
Setting
terminal parameters
To configure and manage the switch through the serial console port or mini USB console port, you must run a terminal emulator program, TeraTermPro or PuTTY, on your configuration terminal. You can use the emulator program to connect a network device, a Telnet site, or an SSH site. For more information about the terminal emulator programs, see the user guides for these programs
Configure the terminal parameters as follows:
· Bits per second—9600.
· Data bits—8.
· Stop bits—1.
· Parity—None.
· Flow control—None.
Starting the switch
1. Before powering on the switch, verify that the following requirements are met:
¡ The power cords are correctly connected.
¡ The input power voltage meets the requirement of the switch.
¡ The console cable is correctly connected.
¡ The configuration terminal (a PC, for example) has started, and the parameters are set correctly.
2. Power on the switch.
During the startup process, you can access Boot ROM menus to perform tasks such as software upgrade and file management. The Boot ROM interface and menu options vary by software versions. For more information about Boot ROM menu options, see the software-matching release notes for the device.
3. After the startup completes, you can access the CLI to configure the switch.
For more information about the configuration commands and CLI, see H3C S6805&S6850&S9850 Switch Series Configuration Guides and H3C S6805&S6850&S9850 Switch Series Command References.
4 Setting up an IRF
fabric
You can use H3C IRF technology to connect and virtualize S6805 switches into a large virtual switch called an "IRF fabric" for flattened network topology, and high availability, scalability, and manageability.
The switch can set up an IRF fabric only with switches from the same switch series.
IRF
fabric setup flowchart
Figure4-1 IRF fabric setup flowchart
To set up an IRF fabric:
Step |
Description |
1. Plan IRF fabric setup. |
Plan the installation site and IRF fabric setup parameters: · Planning IRF fabric size and the installation site · Identifying the master switch and planning IRF member IDs · Planning IRF topology and connections |
2. Install IRF member switches. |
|
3. Connect ground wires and power cords. |
See "Grounding the switch by using a grounding strip" and "Connecting the power cord." |
4. Power on the switches. |
N/A |
5. Configure basic IRF settings. |
See IRF configuration in H3C S6805&S6850&S9850 Switch Series Virtual Technologies Configuration Guide. |
6. Connect the physical IRF ports. |
Connect the physical IRF ports on switches by using QSFP28 transceiver modules and fibers, QSFP28 fiber cables, QSFP 28 copper cables, QSFP+ transceiver modules and fibers, QSFP+ fiber cables, or QSFP+ copper cables. All switches except the master switch automatically reboot, and the IRF fabric is established. |
Planning
IRF
fabric setup
This section describes issues that an IRF fabric setup plan must cover.
Planning IRF
fabric size and the installation site
Choose switch models and identify the number of required IRF member switches, depending on the user density and upstream bandwidth requirements. The switching capacity of an IRF fabric equals the total switching capacities of all member switches.
Plan the installation site depending on your network solution as follows:
· Place all IRF member switches in one rack for centralized high-density access.
· Distribute the IRF member switches in different racks to implement the top-of-rack (ToR) access solution for a data center.
As your business grows, you can add member switches into the IRF fabric to increase the switching capacity without any topology change or replacement.
Identifying the
master switch and planning IRF member IDs
Determine which switch you want to use as the master for managing all member switches in the IRF fabric. An IRF fabric has only one master switch. You configure and manage all member switches in the IRF fabric at the command line interface of the master switch.
|
NOTE: IRF member switches will automatically elect a master. You can affect the election result by assigning a high member priority to the intended master switch. For more information about master election, see IRF configuration in H3C S6805&S6850&S9850 Switch Series Virtual Technologies Configuration Guide. |
Prepare an IRF member ID assignment scheme. An IRF fabric uses member IDs to uniquely identify and manage its members, and you must assign each IRF member switch a unique member ID.
Planning IRF
topology and connections
You can create an IRF fabric in daisy chain topology, or more reliably, ring topology. In ring topology, the failure of one IRF link does not cause the IRF fabric to split as in daisy chain topology. Rather, the IRF fabric changes to a daisy chain topology without interrupting network services.
You connect the IRF member switches through IRF ports, the logical interfaces for the connections between IRF member switches. Each IRF member switch has two IRF ports: IRF-port 1 and IRF-port 2. To use an IRF port, you must bind at least one physical port to it.
When connecting two neighboring IRF member switches, you must connect the physical ports of IRF-port 1 on one switch to the physical ports of IRF-port 2 on the other switch.
The IRF port connections in the two figures are for illustration only, and more connection methods are available.
Figure4-2 IRF fabric in daisy chain topology
Figure4-3 IRF fabric in ring topology
You can set up 100/40-GE IRF physical connections by connecting only QSFP28 ports between S6805 switches.
You can bind several ports to an IRF port for increased bandwidth and availability.
Identifying
physical IRF ports on the member switches
Identify the QSFP28 ports for IRF connections on the member switches according to your topology and connection scheme.
All the QSFP28 ports on the switch can be used for IRF connections.
Planning the
cabling scheme
You can use only QSFP28 transceiver modules and optical fibers, QSFP28 fiber cables, QSFP28 copper cables, QSFP transceiver modules and optical fibers, QSFP fiber cables, or QSFP copper cables to connect the switches for IRF connections.
If the IRF member switches are far away from one another, choose QSFP+/QSFP28 transceiver modules and optical fibers. If the IRF member switches are all in one equipment room, use QSFP/QSFP28 copper or fiber cables. For more information about transceiver modules and cables available for the switch, see "Appendix C Ports and LEDs."
The following subsections describe several H3C recommended IRF connection schemes by using QSFP28 transceiver modules and optical fibers, QSFP28 copper cables, and QSFP28 fiber cables. All these schemes use a ring topology.
Connecting
the IRF member switches in one rack
Figure4-4 shows an example for connecting four IRF member switches in a rack. The switches in the ring topology (see Figure4-5) are in the same order as connected in the rack.
Figure4-4 Connecting the switches in one rack
Connecting
the IRF member switches in a ToR solution
You can install IRF member switches in different racks side by side to deploy a top of rack (ToR) solution.
Figure4-6 shows an example for connecting four top of rack IRF member switches by using QSFP28 cables and QSFP28 transceiver modules and optical fibers. The topology is the same as Figure4-5.
Figure4-6 ToR cabling
Configuring basic
IRF settings
After you install the IRF member switches, power on the switches and then log in to each IRF member switch to configure basic IRF settings, including their member IDs, member priorities, and IRF port bindings.
For the approaches to accessing the switch, see login management in H3C S6805&S6850&S9850 Switch Series Fundamentals Configuration Guide.
For information about configuring IRF settings, see IRF configuration in H3C S6805&S6850&S9850 Switch Series Virtual Technologies Configuration Guide,.
Connecting the
physical IRF ports
|
CAUTION: Wear an ESD wrist strap when you connect fiber or copper cables or transceiver modules and optical fibers. For more information, see the installation guide for the transceiver modules and cables. |
Use fiber or copper cables or transceiver modules and optical fibers to connect the IRF member switches as planned.
Accessing the IRF
fabric to verify the configuration
To verify the basic functionality of the IRF fabric:
1. Log in to the IRF fabric through the console port of any member switch.
2. Create a Layer 3 interface, assign it an IP address, and make sure the IRF fabric and the remote network management station can reach each other.
3. Use Telnet or SNMP to access the IRF fabric from the network management station. For more information about the accessing method, see login management in H3C S6805&S6850&S9850 Switch Series Fundamentals Configuration Guide.
4. Display the running status of the IRF fabric by using the commands in Table4-1.
Table4-1 Displaying and maintaining IRF configuration and running status
Task |
Command |
Display information about the IRF fabric. |
display irf |
Display all members' IRF configurations. |
display irf configuration |
Display IRF fabric topology information. |
display irf topology |
|
NOTE: To avoid IP address collision and network issues, configure at least one multi-active detection (MAD) mechanism to detect the presence of multiple identical IRF fabrics and handle collisions. For more information about MAD detection, see H3C S6805&S6850&S9850 Switch Series Virtual Technologies Configuration Guide. |
5
Maintenance and
troubleshooting
Power supply
failure
Symptom
The status LED on a power supply is not steady green (active state) or flashing green (standby state).
You can use the status LED on a power supply to identify a power supply failure. For more information about the status LED on a power supply, see H3C PSR450 Power Module Series User Manual.
Solution
To resolve the issue:
1. Verify that the power cord is correctly connected.
2. Verify that the power source is as required by the power supply.
3. Verify that the operating temperature of the switch is in an acceptable range and good ventilation is provided for the power supply.
4. If the issue persists, contact the H3C Support
To replace a power supply, see "Installing and removing a power supply."
Fan tray failure
|
CAUTION: If more than one fan tray fails during the switch operation, do not remove the failed fan trays simultaneously. Replace the fan trays one by one and finish replacing each fan tray within 3 minutes. |
Symptom
The status LED on a fan tray is flashing and the system outputs a message that indicates a fan tray failure.
Solution
See "Installing and removing a fan tray" to replace the failed fan tray.
Configuration
terminal display issues
No
display on the configuration terminal
Symptom
The configuration terminal does not have display when the switch is powered on.
Solution
To resolve the issue:
1. Verify that the power system is operating correctly.
2. Verify that the console cable has been connected correctly and the console cable is in good condition.
3. Verify that terminal parameter settings are correct:
¡ Baud rate—9600.
¡ Data bits—8.
¡ Stop bits—1.
¡ Parity—None.
¡ Flow control—None.
4. If the issue persists, contact H3C Support.
Garbled
display
on the configuration terminal
Symptom
The configuration terminal displays garbled text when the switch is powered on.
Solution
To resolve the issue:
1. Verify that the terminal parameter settings are correct:
¡ Baud rate—9600.
¡ Data bits—8.
¡ Stop bits—1.
¡ Parity—None.
¡ Flow control—None.
2. If the issue persists, contact H3C Support.
6 Appendix A Chassis views and technical specifications
Chassis views
S6805-54HF
Figure6-1 Front panel
(1) SFP+ port |
(2) SFP+ port LED |
(3) QSFP28 port |
(4) QSFP28 port LED |
(1) Fiber management Ethernet port |
(2) Console port |
(3) Mini USB console port |
(4) USB port |
(5) Fan tray 1 |
(6) Fan tray 2 |
(7) Fan tray 3 |
(8) Fan tray 4 |
(9) Fan tray 5 |
(10) Power supply 1 |
(11) Power supply 2 |
(12) System status LED (SYS) |
(13) Serial label pull tab |
(14) Copper management Ethernet port LED (LINK/ACT) |
(15) Copper management Ethernet port |
(16) Fiber management Ethernet port LED (LINK/ACT) |
The S6805-54HF switch has a serial label pull tab on the rear panel. It provides the ESN and MAC address of the switch.
The switch comes with power supply slot PWR1 empty and power supply slot PWR2 installed with a filler panel. In Figure6-2, two PSR450-12A power supplies are installed on the switch. For more information about installing and removing a power supply, see "Installing and removing a power supply."
The switch comes with the five fan tray slots empty. You must install five fan trays of the same model for the switch. In Figure6-2, five LSPM1FANSA fan trays are installed on the switch. For more information about installing and removing a fan tray, see "Installing and removing a fan tray."
(1) Primary grounding point |
(2) Auxiliary grounding point |
S6805-54HT
Figure6-4 Front panel
(1) 1/10GBASE-T autosensing Ethernet port |
(2) 1/10GBASE-T autosensing Ethernet port LED |
(3) QSFP28 port |
(4) QSFP28 port LED |
(1) Fiber management Ethernet port |
(2) Console port |
(3) Mini USB console port |
(4) USB port |
(5) Fan tray 1 |
(6) Fan tray 2 |
(7) Fan tray 3 |
(8) Fan tray 4 |
(9) Fan tray 5 |
(10) Power supply 1 |
(11) Power supply 2 |
(12) System status LED (SYS) |
(13) Serial label pull tab |
(14) Copper management Ethernet port LED (LINK/ACT) |
(15) Copper management Ethernet port |
(16) Fiber management Ethernet port LED (LINK/ACT) |
The S6805-54HT switch has a serial label pull tab on the rear panel. It provides the ESN and MAC address of the switch.
The switch comes with power supply slot PWR1 empty and power supply slot PWR2 installed with a filler panel. In Figure6-5, two PSR450-12A power supplies are installed on the switch. For more information about installing and removing a power supply, see "Installing and removing a power supply."
The switch comes with the five fan tray slots empty. You must install five fan trays of the same model for the switch. In Figure6-5, five LSPM1FANSA fan trays are installed in the fan tray slots. For more information about installing and removing a fan tray, see "Installing and removing a fan tray."
Figure6-6 Left side panel
(1) Primary grounding point |
(2) Auxiliary grounding point |
Technical specifications
Table6-1 Technical specifications
Item |
S6805-54HF |
S6805-54HT |
|
Dimensions (H × W × D) |
44 × 440 × 400 mm (1.73 × 17.32 × 15.75 in) |
44 × 440 × 460 mm (1.73 × 17.32 × 18.11 in) |
|
Weight |
≤ 10 kg (22.05 lb) |
≤ 10 kg (22.05 lb) |
|
Console port |
· 1 × mini USB console port · 1 × serial console port |
· 1 × mini USB console port · 1 × serial console port |
|
Management Ethernet port |
· 1 × 10M/100M/1000MBASE-T copper port · 1 × SFP port |
· 1 × 10M/100M/1000MBASE-T copper port · 1 × SFP port |
|
USB port |
1 |
1 |
|
1/10GBASE-T autosensing Ethernet port |
N/A |
48 |
|
SFP+ port |
48 |
N/A |
|
QSFP28 port |
6 |
6 |
|
Fan tray slot |
5 |
5 |
|
Power supply slot |
2 |
2 |
|
Input voltage |
PSR450-12A/PSR450-12A1: · AC input ¡ Rated voltage range: 100 to 240 VAC @ 50/60 Hz ¡ Max voltage range: 90 to 290 VAC @ 47 to 63 Hz · High-voltage DC input ¡ Rated voltage range: 240 VDC ¡ Max voltage range: 180 to 320 VDC PSR450-12AHD: · AC input ¡ Rated voltage range: 100 to 240 VAC @ 50/60 Hz ¡ Max voltage range: 90 to 290 VAC @ 47 to 63 Hz · High-voltage DC input ¡ Rated voltage range e: 240 to 380 VDC ¡ Max voltage range: 180 to 400 VDC PSR450-12D: · Rated voltage range: –48 to –60 VDC · Max voltage range: –36 to –72 VDC |
||
Minimum power consumption |
PSR450-12A/PSR450-12A1: · Single AC input: 82 W · Dual AC inputs: 90 W PSR450-12AHD: · Single DC input: 89 W · Dual DC inputs: 96 W PSR450-12D: · Single DC input: 91 W · Dual DC inputs: 95 W |
PSR450-12A/PSR450-12A1: · Single AC input: 93 W · Dual AC inputs: 100 W PSR450-12AHD: · Single DC input: 91 W · Dual DC inputs: 102 W PSR450-12D: · Single DC input: 94 W · Dual DC inputs: 101 W |
|
Maximum power consumption |
PSR450-12A/PSR450-12A1: · Single AC input: 208 W · Dual AC inputs: 213 W PSR450-12AHD: · Single DC input: 202 W · Dual DC inputs: 214 W PSR450-12D: · Single DC input: 207 W · Dual DC inputs: 217 W |
PSR450-12A/PSR450-12A1: · Single AC input: 222 W · Dual AC inputs: 229 W PSR450-12AHD: · Single DC input: 225 W · Dual DC inputs: 233 W PSR450-12D: · Single DC input: 230 W · Dual DC inputs: 236 W |
|
Chassis leakage current compliance |
UL60950-1/EN60950-1/IEC60950-1/GB4943 |
||
Melting current of power supply fuse |
PSR450-12A/PSR450-12A1: · 10 A @ 250 VAC · 10 A @ 310 VDC PSR450-12D: 20 A @ 125 V PSR450-12AHD: 10 A @ 420 V |
||
Operating temperature |
0°C to 45°C (32°F to 113°F) |
||
Operating humidity |
5% RH to 95% RH, noncondensing |
||
Fire resistance compliance |
UL60950-1/EN60950-1/IEC60950-1/GB4943 |
||
7 Appendix B FRUs
and compatibility matrixes
|
CAUTION: · Select fan trays and power supplies with airflow directions that meet the ventilation requirements at the installation site. As a best practice, make sure the power supplies and fan trays have the same airflow direction. · Do not install fan trays of different models on the same switch. To guarantee adequate heat dissipation, install five fan trays of the same model on the switch. · Do not install power supplies of different models on the same switch. As a best practice, install two power supplies of the same model on the switch for 1+1 power supply redundancy. |
Table7-1 Compatibility matrix between the FRUs and S6805 switches
FRUs |
Part No. |
S6805-54HF |
S6805-54HT |
Power supplies |
|||
PSR450-12A |
0231A6N9 |
Yes |
Yes |
PSR450-12A1 |
0231A6NC |
Yes |
Yes |
PSR450-12AHD |
0231A6NA |
Yes |
Yes |
PSR450-12D |
0231A6NB |
Yes |
Yes |
Fan trays |
|||
LSPM1FANSA |
0231ACJM |
Yes |
Yes |
LSPM1FANSB |
0231ACJL |
Yes |
Yes |
Power supplies
|
CAUTION: When the switch has two power supplies in 1+1 redundancy, you can replace one of them without powering off the switch. To avoid device damage and body injury, make sure the power supply to be replaced is powered off before you replace it. |
Table7-2 Power supply specifications
Power supply |
Specifications |
Remarks |
PSR450-12A (with an airflow direction from the power supply side to the port side) PSR450-12A1 (with an airflow direction from the port side to the power supply side) |
· AC input: ¡ Rated input voltage range: 100 to 240 VAC @ 50/60 Hz ¡ Max input voltage range: 90 to 290 VAC @ 47 to 63 Hz ¡ Max output power: 450 W · DC input: ¡ Rated input voltage range: 240 VDC ¡ Max input voltage range: 180 to 320 VDC ¡ Max output power: 450 W |
For more information about the power supplies, see H3C PSR450 Power Module Series User Manual. |
PSR450-12AHD (with an airflow direction from the port side to the power supply side) |
· AC input ¡ Rated input voltage range: 100 to 240 VAC @ 50/60 Hz ¡ Max input voltage range: 90 to 290 VAC @ 47 to 63 Hz ¡ Max output power: 450 W · High-voltage DC input ¡ Rated input voltage range: 240 to 380 VDC ¡ Max input voltage range: 180 to 400 VDC ¡ Max output power: 450 W |
|
PSR450-12D (with an airflow direction from the port side to the power supply side) |
· Rated input voltage range: –48 to –60 VDC · Max input voltage range: –36 to –72 VDC · Max output power: 450 W |
Fan
trays
Table7-3 Fan tray specifications
Item |
Specifications |
LSPM1FANSA |
|
Dimensions |
41 × 40 × 105 mm (1.61 × 1.57 × 4.13 in), including the handle |
Fan number |
1 |
Fan speed |
20000 R.P.M |
Max airflow |
20 CFM |
Airflow direction |
From the power supply side to the port side |
Input voltage |
12 V |
Maximum power consumption |
9.8 W |
Documentation reference |
H3C LSPM1FANSA & LSPM1FANSB Fan Trays User Guide |
LSPM1FANSB |
|
Dimensions |
41 × 40 × 105 mm (1.61 × 1.57 × 4.13 in), including the handle |
Fan number |
1 |
Fan speed |
20000 R.P.M |
Max airflow |
20 CFM |
Airflow direction |
From the port side to the power supply side |
Input voltage |
12 V |
Maximum power consumption |
9.8 W |
Documentation reference |
H3C LSPM1FANSA & LSPM1FANSB Fan Trays User Guide |
8 Appendix C Ports
and LEDs
Ports
|
IMPORTANT: · As a best practice, use H3C transceiver modules and cables for the switch. · The H3C transceiver modules and cables are subject to change over time. For the most up-to-date list of H3C transceiver modules and cables, contact H3C Support or marketing staff. · For more information about H3C transceiver modules and cables, see H3C Transceiver Modules User Guide. |
Console
port
The switch has two console ports: serial console port and Mini USB console port.
Table8-1 Console port specifications
Item |
Console port |
Mini USB console port |
Connector type |
RJ-45 |
USB mini-Type B |
Compliant standard |
EIA/TIA-232 |
USB 2.0 |
Transmission baud rate |
9600 bps (default) to 115200 bps |
|
Services |
· Provides connection to an ASCII terminal. · Provides connection to the serial port of a local or remote (through a pair of modems) PC running terminal emulation program. |
· Provides connection to an ASCII terminal. · Provides connection to the USB port of a local PC running terminal emulation program. |
Management
Ethernet port
The switch provides a copper and a fiber management Ethernet port.
You can connect this port to a PC or management station for loading and debugging software or remote management.
Table8-2 Copper management Ethernet port specifications
Item |
Specification |
Connector type |
RJ-45 |
Connector quantity |
1 |
Port transmission rate and duplex mode |
10/100/1000 Mbps, half/full duplex |
Transmission medium and max transmission distance |
100 m (328.08 ft) over category-5 twisted pair cable |
Functions and services |
Software and Boot ROM upgrade and network management |
Table8-3 Fiber management Ethernet port specifications
Item |
Specification |
Connector type |
LC |
Connector quantity |
1 |
Port transmission rate |
100/1000 Mbps, full duplex |
Transmission medium and max transmission distance |
|
Functions and services |
Software upgrade and network management |
Table8-4 FE SFP transceiver modules
FE SFP transceiver module |
Central wavelength (nm) |
Connector |
Fiber type and diameter (µm) |
Max transmission distance |
SFP-FE-SX-MM1310-A |
1310 |
LC |
Multi-mode, 50/125 |
2 km (1.24 miles) |
Multi-mode, 62.5/125 |
||||
SFP-FE-LX-SM1310-A |
1310 |
LC |
Single-mode, 9/125 |
15 km (9.32 miles) |
SFP-FE-LH40-SM1310 |
1310 |
LC |
Single-mode, 9/125 |
40 km (24.86 miles) |
USB port
The switch has one OHC-compliant USB2.0 port that can upload and download data at a rate up to 480 Mbps. You can use this USB port to access the file system on the flash file system of the switch, for example, to upload or download application and configuration files.
|
IMPORTANT: · USB devices from different vendors vary in compatibility and driver. H3C does not guarantee correct operation of all USB devices on the switch. If a USB device fails to operate on the switch, replace it with one from another vendor. · The USB port on the switch is designed to output current in strict accordance with the USB 2.0 standard. For a USB storage device to be identified by the USB port, make sure the USB device fully complies with USB 2.0. |
SFP+ port
An S6805-54HF switch provides 48 SFP+ ports. The SFP+ ports support the following transceiver modules and cables:
· Gigabit SFP transceiver modules in Table8-5.
· 10-Gigabit SFP+ transceiver modules in Table8-6.
· 10-Gigabit SFP+ copper cables in Table8-7.
· 10-Gigabit SFP+ fiber cables in Table8-8.
Table8-5 Gigabit SFP transceiver modules available for the SFP+ ports
Gigabit SFP transceiver module |
Central wavelength (nm) |
Connector |
Cable/Fiber type and diameter (µm) |
Modal bandwidth (MHz × km) |
Max transmission distance |
SFP-GE-T |
N/A |
RJ-45 |
Twisted pair cable |
N/A |
100 m (328.08 ft) |
SFP-GE-SX-MM850-A |
850 |
LC |
Multi-mode, 50/125 |
500 |
550 m (1804.46 ft) |
400 |
500 m (1640.42 ft) |
||||
Multi-mode, 62.5/125 |
200 |
275 m (902.23 ft) |
|||
160 |
200 m (656.17 ft) |
||||
SFP-GE-LX-SM1310-A |
1310 |
LC |
Single-mode, 9/125 |
N/A |
10 km (6.21 miles) |
Multi-mode, 50/125 |
500 or 400 |
550 m (1804.46 ft) |
|||
Multi-mode, 62.5/125 |
500 |
550 m (1804.46 ft) |
|||
SFP-GE-LH40-SM1310 |
1310 |
LC |
Single-mode, 9/125 |
N/A |
40 km (24.86 miles) |
SFP-GE-LH40-SM1550 |
1550 |
LC |
Single-mode, 9/125 |
N/A |
40 km (24.86 miles) |
SFP-GE-LH80-SM1550 |
1550 |
LC |
Single-mode, 9/125 |
N/A |
80 km (49.71 miles) |
Table8-6 10-Gigabit SFP+ transceiver modules available for the SFP+ ports
10-Gigabit SFP+ transceiver module |
Central wavelength (nm) |
Connector |
Fiber type and diameter (µm) |
Modal bandwidth (MHz × km) |
Max transmission distance |
SFP-XG-SX-MM850-A |
850 |
LC |
Multi-mode, 50/125 |
2000 |
300 m (984.25 ft) |
500 |
82 m (269.03 ft) |
||||
400 |
66 m (216.54 ft) |
||||
Multi-mode, 62.5/125 |
200 |
33 m (108.27 ft) |
|||
160 |
26 m (85.30 ft) |
||||
SFP-XG-LX-SM1310 |
1310 |
LC |
Single-mode, 9/125 |
N/A |
10 km (6.21 miles) |
Table8-7 SFP+ copper cables available for the SFP+ ports
SFP+ copper cable |
Max transmission distance |
LSWM1STK |
0.65 m (2.13 ft) |
LSWM2STK |
1.2 m (3.94 ft) |
LSWM3STK |
3 m (9.84 ft) |
LSTM1STK |
5 m (16.40 ft) |
Table8-8 SFP+ fiber cables available for the SFP+ ports
SFP+ fiber cable |
Max transmission distance |
Data rate |
SFP-XG-D-AOC-7M |
7 m (22.97 ft) |
10.31 Gbps |
SFP-XG-D-AOC-10M |
10 m (32.81 ft) |
|
SFP-XG-D-AOC-20M |
20 m (65.62 ft) |
QSFP28 port
The QSFP28 ports on the switch do not support breakout. They support the following transceiver modules and cables:
· QSFP28 transceiver modules in Table8-9.
· QSFP28 copper cables in Table8-10.
· QSFP28 fiber cables in Table8-11.
· QSFP+ transceiver modules in Table8-12.
· QSFP+ copper cables in Table8-13.
· QSFP+ fiber cables in Table8-14.
Table8-9 QSFP28 transceiver modules available for the QSFP28 ports
Model |
Central wavelength (nm) |
Connector |
Cable/Fiber type and diameter (µm) |
Modal bandwidth (MHz × km) |
Max transmission distance |
QSFP-100G-SR4-MM850 |
850 |
MPO (PC polished, 12-fiber) |
Multi-mode, 50/125 |
2000 |
70 m (229.66 ft) |
4700 |
100 m (328.08 ft) |
||||
QSFP-100G-SWDM4-MM850 |
Four lanes: · 850 · 880 · 910 · 940 |
LC |
Multi-mode, 50/125 |
2000 |
75 m (246.06 ft) |
4700 |
100 m (328.08 ft) |
||||
QSFP-100G-PSM4-SM1310 |
1295 to 1325 |
MPO (APC polished, 12-fiber) |
Single-mode, 9/125 |
N/A |
0.5 km (0.31 miles) |
QSFP-100G-LR4-WDM1300 |
Four lanes: · 1295 · 1300 · 1304 · 1309 |
LC |
Single-mode, 9/125 |
N/A |
10 km (6.21 miles) |
QSFP-100G-LR4L-WDM1300 |
Four lanes: · 1271 · 1291 · 1311 · 1331 |
LC |
Single-mode, 9/125 |
N/A |
2 km (1.24 miles) |
Table8-10 QSFP28 copper cables available for the QSFP28 ports
Model |
Max transmission distance |
QSFP-100G-D-CAB-1M |
1 m (3.28 ft) |
QSFP-100G-D-CAB-3M |
3 m (9.84 ft) |
QSFP-100G-D-CAB-5M |
5 m (16.40 ft) |
Table8-11 QSFP28 fiber cables available for the QSFP28 ports
QSFP28 fiber cable |
Max transmission distance |
Data rate |
QSFP-100G-D-AOC-7M |
7 m (22.97 ft) |
100 Gbps |
QSFP-100G-D-AOC-10M |
10 m (32.81 ft) |
|
QSFP-100G-D-AOC-20M |
20 m (65.62 ft) |
Table8-12 40GE QSFP+ transceiver modules available for the QSFP28 ports
QSFP+ transceiver module |
Central wavelength (nm) |
Connector |
Fiber type and diameter (µm) |
Modal bandwidth (MHz × km) |
Max transmission distance |
QSFP-40G-SR4-MM850 |
850 |
MPO (PC polished, 12-fiber) |
Multi-mode, 50/125 |
2000 |
100 m (328.08 ft) |
4700 |
150 m (492.12 ft) |
||||
QSFP-40G-CSR4-MM850 |
850 |
MPO (PC polished, 12-fiber) |
Multi-mode, 50/125 |
2000 |
300 m (984.25 ft) |
4700 |
400 m (1312.33 ft) |
||||
QSFP-40G-LR4-PSM1310 |
1310 |
MPO (PC polished, 12-fiber) |
Single-mode, 9/125 |
N/A |
10 km (6.21 miles) |
QSFP-40G-BIDI-SR-MM850 |
850 |
LC |
Multi-mode, 50/125 |
2000 |
100 m (328.08 ft) |
4700 |
150 m (492.12 ft) |
||||
QSFP-40G-LR4-WDM1300 |
Four lanes: · 1271 · 1291 · 1311 · 1331 |
LC |
Single-mode, 9/125 |
N/A |
10 km (6.21 miles) |
QSFP-40G-LR4L-WDM1300 |
Four lanes: · 1271 · 1291 · 1311 · 1331 |
LC |
Single-mode, 9/125 |
N/A |
2 km (1.24 miles) |
Table8-13 QSFP+ copper cables available for the QSFP28 ports
QSFP+ copper cable |
Max transmission distance |
LSWM1QSTK0 |
1 m (3.28 ft) |
LSWM1QSTK1 |
3 m (9.84 ft) |
LSWM1QSTK2 |
5 m (16.40 ft) |
Table8-14 QSFP+ fiber cables available for the QSFP28 ports
QSFP+ fiber cable |
Max transmission distance |
Data rate |
QSFP-40G-D-AOC-7M |
7 m (22.97 ft) |
40 Gbps |
QSFP-40G-D-AOC-10M |
10 m (32.81 ft) |
|
QSFP-40G-D-AOC-20M |
20 m (65.62 ft) |
1/10GBASE-T autosensing Ethernet port
An S6805-54HT switch provides forty-eight 1/10GBASE-T autosensing Ethernet ports.
Table8-15 1/10GBASE-T autosensing Ethernet port specifications
Item |
Specification |
Connector type |
RJ-45 |
Port transmission rate, duplex mode, and auto-MDIX |
1/10 Gbps, full duplex, MDI/MDIX autosensing |
Transmission medium and max transmission distance |
· 55 m (180.45 ft) over category-6 unshielded twisted pair cable · 100 m (328.08 ft) over category-6 shielded twisted pair cable · 100 m (328.08 ft) over category-6A or above twisted pair cable |
Compatible standards |
· IEEE 802.3ab · IEEE 802.3an |
To avoid interference between cables, layer cables as follows:
· Use category-6A or above cables and connectors.
· Do not bundle cables in their first 20 m (65.62 ft).
· Separate power cords and twisted pair cables at and around the distribution frame.
· For ports adjacent to one another on the device, the peer ports on the distribution frame are preferably not adjacent, for example:
¡ If the device connects to one distribution frame, connect port 1 on the device to port 1 on the distribution frame, port 2 on the device to port 3 on the distribution frame, and port 3 on the device to port 5 on the distribution frame.
¡ If the device connects to two distribution frames, connect port 1 on the device to port 1 on distribution frame 1, port 2 on the device to port 1 on distribution frame 2, and port 3 on the device to port 2 on distribution frame 1.
LEDs
System status LED
The system status LED shows the operating status of the switch.
Table8-16 System status LED description
LED mark |
Status |
Description |
SYS |
Steady green |
The switch is operating correctly. |
Flashing green |
The switch is performing power-on self test (POST). |
|
Steady red |
The system has failed POST, or a fault has occurred. |
|
Flashing red |
Some ports have failed POST. |
|
Flashing blue (3 Hz) |
Helps you to locate the device. To locate the device, execute the locator blink command on the device. Then the SYS LED will be in this state. |
|
Off |
The switch is powered off or has failed to start up. |
SFP+ port LED
Each SFP+ port has a status LED to show its operating status and activities.
Table8-17 SFP+ port LED description
LED status |
Description |
Steady green |
A transceiver module or cable has been correctly installed. The port has a link and is operating at 10 Gbps. |
Flashing green |
The port is sending or receiving data at 10 Gbps. |
Steady yellow |
A transceiver module or cable has been correctly installed. The port has a link and is operating at 1 Gbps. |
Flashing yellow (3 Hz) |
The port is sending or receiving data at 1 Gbps. |
Off |
No transceiver module or cable has been installed or no link is present on the port. |
QSFP28 port LED
Each QSFP28 port has a status LED to show its operating status and activities.
Table8-18 QSFP28 port LED description
LED status |
Description |
Steady green |
A transceiver module or cable has been correctly installed. The port has a link and is operating at 100 Gbps. |
Flashing green |
The port is sending or receiving data at 100 Gbps. |
Steady yellow |
A transceiver module or cable has been correctly installed. The port has a link and is operating at 40 Gbps. |
Flashing yellow (3 Hz) |
The port is sending or receiving data at 40 Gbps. |
Off |
No transceiver module or cable has been installed or no link is present on the port. |
1/10GBASE-T autosensing Ethernet port LEDs
Table8-19 1/10GBASE-T autosensing Ethernet port LED description
Status |
Description |
Steady green |
The port has a link and is operating at 10 Gbps. |
Flashing green |
The port is sending or receiving data at 10 Gbps. |
Steady yellow |
The port has a link and is operating at 1 Gbps. |
Flashing yellow |
The port is sending or receiving data at 1 Gbps. |
Off |
No link is present on the port. |
Management Ethernet port LEDs
The switch provides a LINK/ACT LED for each management Ethernet port. To view the description for the copper management Ethernet port LED, see Table8-20. To view the description for the fiber management Ethernet port LED, see Table8-21.
Table8-20 Copper management Ethernet port LED description
LED mark |
Status |
Description |
LINK/ACT |
Steady green |
The port is operating at 10/100/1000 Mbps and a link is present. |
Flashing green |
The port is receiving or sending data. |
|
Off |
No link is present. |
Table8-21 Fiber management Ethernet port LED description
LED mark |
Status |
Description |
LINK/ACT |
Off |
No link is present. |
Steady green |
The port is operating at 1000 Mbps and a link is present. |
|
Flashing green |
The port is receiving or sending data at 1000 Mbps. |
|
Steady yellow |
The port is operating at 100 Mbps and a link is present. |
|
Flashing yellow |
The port is receiving or sending data at 100 Mbps. |
Fan tray alarm LEDs
The LSPM1FANSA and LSPM1FANSB fan trays each provide an alarm LED.
Table8-22 Fan tray alarm LED description
Status |
Description |
On |
The fan tray is faulty. |
Off |
The fan tray is operating correctly. |
9
Appendix D Cooling system
|
CAUTION: To guarantee heat dissipation, you must install fan trays of the same model for the switch. |
To dissipate heat timely and ensure system stability, the switch uses the front-rear air aisle cooling system. Consider the site ventilation design when you plan the installation site for the switch.
Table9-1 Cooling system for the switch
Available fan trays |
Airflow direction |
LSPM1FANSA |
From the power supply side to the port side |
LSPM1FANSB |
From the port side to the power supply side |
Figure9-1 Airflow from the power supply side to the port side through the S6805-54HF chassis (with LSPM1FANSA fan trays)
Figure9-2 Airflow from the port side to the power supply side through the S6805-54HF chassis (with LSPM1FANSB fan trays)