Title | Size | Downloads |
---|---|---|
H3C HDM2 System Log Messages Reference-6W102-book(CHM&PDF&Excel).rar | 1.19 MB |
- Table of Contents
Title | Size | Download |
---|---|---|
book(CHM&PDF&Excel) | 1.19 MB |
System Log Messages Reference |
|
|
Copyright © 2024 New H3C Technologies Co., Ltd. All rights reserved.
No part of this manual may be reproduced or transmitted in any form or by any means without prior written consent of New H3C Technologies Co., Ltd.
Except for the trademarks of New H3C Technologies Co., Ltd., any trademarks that may be mentioned in this document are the property of their respective owners.
The information in this document is subject to change without notice.
Contents
Dropped below the lower minor threshold
Dropped below the lower major threshold
Dropped below the lower critical threshold
Exceeded the upper minor threshold
Exceeded the upper major threshold
Exceeded the upper critical threshold
Dropped below the lower minor threshold
Dropped below the lower major threshold
Dropped below the lower major threshold
Dropped below the lower critical threshold
Exceeded the upper minor threshold
Exceeded the upper major threshold
Exceeded the upper major threshold
Exceeded the upper critical threshold
Transition to Non-recoverable from less severe
Transition to Non-recoverable from less severe
Transition to Non-recoverable from less severe
Transition to Non-recoverable from less severe
Transition to Non-recoverable from less severe
Transition to Non-recoverable from less severe
Transition to Non-recoverable from less severe
Transition to Non-recoverable from less severe
Transition to Non-recoverable from less severe
Transition to Non-recoverable from less severe
Transition to Non-recoverable from less severe
Transition to Non-recoverable from less severe
Transition to Non-recoverable from less severe
Transition to Non-recoverable from less severe
Transition to Non-recoverable from less severe
Transition to Non-recoverable from less severe
Transition to Non-recoverable from less severe
Transition to Non-recoverable from less severe
Transition to Non-recoverable from less severe
Transition to Non-recoverable from less severe
Transition to Non-recoverable from less severe
Transition to Non-recoverable from less severe
Transition to Non-recoverable from less severe
Transition to Non-recoverable from less severe
Transition to Non-recoverable from less severe
Transition to Non-recoverable from less severe
Transition to Non-recoverable from less severe
Transition to Non-recoverable from less severe
Transition to Non-recoverable from less severe
Transition to Non-recoverable from less severe
Transition to Non-recoverable from less severe
Transition to Non-recoverable from less severe
Transition to Non-recoverable from less severe
Transition to Non-recoverable from less severe
Transition to Non-recoverable from less severe
Transition to Non-recoverable from less severe
Transition to Non-recoverable from less severe
Transition to Non-recoverable from less severe
Transition to Non-recoverable from less severe
Transition to Non-recoverable from less severe
Transition to Non-recoverable from less severe
Transition to Non-recoverable from less severe
Transition to Non-recoverable from less severe
Transition to Non-recoverable from less severe
Transition to Non-recoverable from less severe
Transition to Non-recoverable from less severe
Transition to Non-recoverable from less severe
Transition to Non-recoverable from less severe
Transition to Non-recoverable from less severe
Transition to Non-recoverable from less severe
Transition to Non-recoverable from less severe
Transition to Non-recoverable from less severe
Transition to Non-recoverable from less severe
Transition to Non-recoverable from less severe
Transition to Non-recoverable from less severe
Transition to Non-recoverable from less severe
Transition to Non-recoverable from less severe
Transition to Non-recoverable from less severe
Transition to Non-recoverable from less severe
Transition to Non-recoverable from less severe
Transition to Non-recoverable from less severe
Transition to Non-recoverable from less severe
Transition to Non-recoverable from less severe
Transition to Non-recoverable from less severe
Transition to Non-recoverable from less severe
Transition to Non-recoverable from less severe
Transition to Non-recoverable from less severe
Transition to Non-recoverable from less severe
Transition to Non-recoverable from less severe
Transition to Non-recoverable from less severe
Transition to Non-recoverable from less severe
Transition to Non-recoverable from less severe
Transition to Non-recoverable from less severe
Transition to Non-recoverable from less severe
Transition to Non-recoverable from less severe
Transition to Non-recoverable from less severe
Transition to Non-recoverable from less severe
Transition to Non-recoverable from less severe
Transition to Non-recoverable from less severe
Transition to Non-recoverable from less severe
Transition to Non-recoverable from less severe
Transition to Critical from less severe
Exceeded the upper minor threshold
Exceeded the upper major threshold
Exceeded the upper major threshold
Exceeded the upper critical threshold
Non-redundant:Sufficient Resources from Redundant
Non-redundant:Insufficient Resources
FRB3/Processor Startup/Initialization failure
Processor Automatically Throttled
Processor Automatically Throttled
Processor Automatically Throttled
Triggered a uncorrectable error
Correctable Machine Check Error
Correctable Machine Check Error
Correctable Machine Check Error
Power Supply Predictive Failure
Power Supply input lost (AC/DC)
Power Supply input lost or out-of-range
Power Supply input out-of-range - but present
Configuration error ---Vendor mismatch
Configuration error---Power Supply rating mismatch
Configuration error---Power supply rating mismatch
Power Supply Inactive/standby state
Power limit is exceeded over correction time limit
Transition to Non-recoverable---Liquid leakage occurred
Transition to Non-recoverable from less severe
Transition to Non-Critical from OK--- Liquid leakage detection cable is disconnected
Exceeded the upper minor threshold
Correctable ECC or other correctable memory error
Correctable ECC or other correctable memory error
Correctable ECC or other correctable memory error
CPU triggered a correctable error
Uncorrectable ECC or other uncorrectable memory error
Uncorrectable ECC or other uncorrectable memory error
Triggered an uncorrectable error
Uncorrectable ECC or other uncorrectable memory error
Parity---An uncorrectable error occurs during the memory test phase
Parity---The memory interleaving configuration cannot meet the requirements of the server
Parity---The memory interleaving configuration cannot meet the requirements of the server
Parity---The memory interleaving configuration cannot meet the requirements of the server
Parity---CMD eye width is too small
Parity---CmdPiGroup: No Eye width
Parity---The command is not in the FNv table
Parity---Memory read DqDqs training failed
Parity---Memory Receive Enable Training Error
Parity---Memory write DqDqs training failed
Parity---An error occurs during memory test, and the rank is disabled
Parity---LRDIMM RCVEN training failed
Parity---Read delay training failed
Parity---Write delay training failed
Parity---Mapped out because failed critical mask test at cold boot
Parity---The DCPMM memory modules of the unexpected model are installed
Parity---Failed to set the VDD voltage of the DIMM
Parity---Timing error occurred during signal line adjustment for memory write leveling training
Parity---CS is not consistent with clock in timing, and the channel is isolated
Parity---CA is not consistent with clock in timing, and the channel is isolated
Parity---LRDIMM external coarse training failed
Parity---LRDIMM external fine training failed
Parity---LRDIMM internal coarse training failed
Parity---LRDIMM internal fine training failed
Memory Device Disabled---The Rank is disabled
Memory Device Disabled---The DIMM is disabled
Correctable ECC or other memory error limit reached
Correctable ECC or other memory error limit reached
Memory patrol scrub CE occurred
Memory patrol scrub UCE occurred and degraded to CE
Configuration error---RDIMMs are installed on the server that supports only UDIMMs
Configuration error---UDIMMs are installed on the server that supports only RDIMMs
Configuration error---SODIMMs are installed on the server that supports only RDIMMs
Configuration error---The number of ranks per channel can be only 1, 2, or 4
Configuration error---The number of ranks in the channel exceeds 8
Configuration error---The CPU is not compatible with 3DS DIMMs
Configuration error---NVDIMMs with stepping lower than 0x10 are not supported
Configuration error---The CPU is not compatible with the DIMMs
Configuration error---The frequency of the DIMM is not supported on the server
Configuration error---24Gb or higher Capacity DRAMs not supported with this CPU
Configuration error---The CPU is not compatible with LRDIMMs
Configuration error--- DCPMM + HBM config is not supported. Disable DCPMM populated channel
Configuration error---Failed to enable the full mirror mode
Configuration error---Failed to enable patrol scrubbing
Configuration error---The DDR-T memory module is installed in the white slot
Configuration error---ODT configuration errorThe channel is isolated
Configuration error---REQ is not consistent with clock in timing
Configuration error---Failed to enable ADDDC
Configuration error---NVMCTRL_MEDIA_NOTREADY
Drive Fault---The disk is missing
The disk triggered an media error
The disk triggered an uncorrectable error
System Firmware Error (POST Error)---Run sense AMP HW FSM failed
System Firmware Error (POST Error)---No Dimm on socket$1
System Firmware Error (POST Error)---No memory found
System Firmware Error (POST Error)---No DIMM is available for memory-mapping operation
System Firmware Error (POST Error)---DIMM population error
System Firmware Error (POST Error)---CPU stepping mismatch detected
System Firmware Error (POST Error)---KTI Topology Change Logged
System Firmware Error (POST Error)---CPU matching failure---CPU stepping is detected
System Firmware Error (POST Error)---CPU matching failure---CPU frequency is detected
System Firmware Error (POST Error)---CPU matching failure---CPU Microcode is detected
System Firmware Error (POST Error)---CPU matching failure---UPI Topology is detected
System Firmware Error(POST Error)---Unrecoverable video controller failure
System software triggered an uncorrectable error
System software triggered a correctable error
System Firmware Progress---Video initialization---Detection unsuccessful
System Firmware Progress---Secondary processor(s) initialization---Detection unsuccessful
System Reconfigured---BIOS load default. CMOS cleared
Limit Exceeded---CPU usage exceeds the threshold
Limit Exceeded---Mem usage exceeds the threshold
Limit Exceeded---Network usage exceeds the threshold
Limit Exceeded---Hard disk usage exceeds the threshold
Timestamp clock synch---BMC Time SYNC succeed
$1 triggered an uncorrectable error
$1 triggered a correctable error
Power Button pressed---Physical button---Button pressed
Transition to Non-Critical from OK
Transition to Critical from less severe
Transition to Non- Recoverable from less severe
Transition to Non-Critical from OK---System is operating in KTI Link Slow Speed Mode
Transition to Non-Critical from OK---Requested Link Speed is not supported. Defaulting to 18GT
System board triggered an uncorrectable error
System board triggered a correctable error
Transition to Critical from less severe
Transition to Critical from less severe
Transition to Non-recoverable from less severe
Transition to Critical from less severe
Configuration Error - Incorrect cable connected / Incorrect interconnection
Configuration Error - Incorrect cable connected / Incorrect interconnection
Configuration Error - Incorrect cable connected / Incorrect interconnection
System Boot / Restart Initiated
Boot completed - boot device not specified
Device disabled: PCIe module information not obtained
Transition to Non-Critical from OK
S4 / S5 soft-off, particular S4 / S5 state cannot be determined
Watchdog overflowAction:Timer expired
Watchdog overflowAction:Hard Reset
Watchdog overflowAction:Power Down
Watchdog overflowAction:Power Cycle
Entity Present---License is about to expire
Entity Disabled---License has expired
Controller access degraded or unavailable
Controller access degraded or unavailable
Battery low (predictive failure)
Hardware incompatibility detected with associated Entity---Memory is not certified
Introduction
This document describes HDM2 log messages generated to notify the occurrence and removal of system exceptions detected by sensors in the server. You can use this document to obtain message details and recommended actions for server maintenance.
HDM2 is an upgraded version of HDM. For convenience purposes, the term "HDM" refers to HDM2 in this document.
Use cases
When the device experiences a failure or certain reasons lead to an abnormal working state of the system, the system is able to generate alarms based on the faults occurring in different modules, as well as generate event log information. After obtaining the log information, users can search for the corresponding log information in this document using the relevant fields in the log information. This will allow them to understand the detailed content of the log information and receive recommended solutions for handling, thus facilitating the maintenance of the server's normal operation.
Obtaining system log messages
You can obtain system log messages through the following methods:
· HDM Web interface—Access the HDM Web interface and click Remote O&M > Log > Log Download. On the Log Download tab, select to download the entire log or log entries for a period.
· Alert emails—Complete alert email settings to obtain log messages.
· Third-party platform—Complete SNMP, SMTP, and SYSLOG settings to connect HDM to a third-party management platform, and obtain log messages from the platform.
· Redfish event subscription—If a remote subscription server is configured, Redfish uploads received log messages to the remote subscription server.
· IPMI commands—Use IPMItool commands to access the IPMI interface for BMC and enter commands to obtain event log messages.
System log severity level
Table 1 System log message severity levels
Severity |
Description |
Critical |
The following conditions are present: severe decreases in the processing power of the system processing unit, significant reduction in available system resources, severe decreases in service processing capabilities, widespread interruptions in service modules, or unavailability of storage devices. This may lead to or cause server failure, system crashes, service data loss or other similar situations. Immediate action is required. |
Major |
Such events have had a significant impact on the system and there is a possibility of interrupting the normal operation of system or service modules (computing, storage, communication, and user data security), which may lead to service interruption. |
Minor |
Such events have not had a significant impact on the system, but there may be some risks and potential hazards. It is advisable to observe the relevant events and take necessary measures when needed to prevent further escalation of faults. |
Info |
Event logs generated during the normal operation of the server. Such events do not affect the normal operation of the server and do not require any action. |
Using this document
This document explains messages in tables. Table 2 describes information provided in these tables.
Table 2 Message explanation table contents
Item |
Description |
Example |
Event code |
A hexadecimal code that uniquely represents a log message. The parity of the last character in the event code represents the alarm type: · Even—An alarm was generated. · Odd—An alarm was removed. |
0x02900002 |
Message text |
Presents the message description. The same message description might be reported by different types of sensors. |
Exceeded the upper major threshold.---Current reading:$1---Threshold reading:$2 |
Variable fields |
Briefly describes the variable fields in the order that they appear in the message text. The variable fields are numbered in the "$Number" form to help you identify their location in the message text. |
· $1: Current reading of the voltage sensor. · $2: Major overvoltage threshold of the voltage sensor. |
Severity level |
Provides the severity level of the message. |
Major |
Example |
Log example. |
Exceeded the upper major threshold.---Current reading:2.58---Threshold reading:2.56 |
Impact |
Explains the impact of the alarm event on the system |
Performance degradation and unstable operation might occur on the device components if the voltage is too high. |
Cause |
Explains the reason for the log generation |
Abnormal board voltage. |
Recommended action |
Provides recommended actions. If the issue persists after the recommended actions have been taken, contact the technical support. |
1. Verify that the external power supply is operating correctly. 2. Access the HDM Web interface and verify that the power supply is operating correctly. 3. If the issue persists, contact Technical Support. |
Applicable products
This document is available for the following product models:
· H3C UniServer R4300 G6
· H3C UniServer R4700 G6
· H3C UniServer R4700LE G6
· H3C UniServer R4900 G6
· H3C UniServer R4900 G6 Ultra
· H3C UniServer R4900LE G6 Ultra
· H3C UniServer R4950 G6
· H3C UniServer R5300 G6
· H3C UniServer R5350 G6
· H3C UniServer R5500 G6
· H3C UniServer B5700 G6
· H3C UniServer R6700 G6
· H3C UniServer R6900 G6
Event log messages
Temperature
Dropped below the lower minor threshold
Event code |
0x01000002 |
Variable fields |
$1: Current reading of the temperature sensor $2: Threshold (in Celsius) for triggering a minor low-temperature notification. |
Severity level |
Minor |
Example |
Dropped below the lower minor threshold---Current reading:8--Threshold reading:10 |
Impact |
Performance degradation and unstable operation might occur on the device components if the temperature is too low. If the temperature does not rise and the alarm persists, it may result in further temperature reduction and produce alarms of the major level. Therefore, it is important to detect potential issues that may lead to low temperature alarms as early as possible to avoid escalation of the problem. |
Cause |
The temperature is too low. |
Recommended action |
1. Adjust the temperature of the equipment room. 2. If the issue persists, contact Technical Support. |
Dropped below the lower major threshold
Event code |
0x01200002 |
Message text |
Dropped below the lower major threshold---Current reading:$1---Threshold reading:$2 |
Variable fields |
$1: Current reading of the temperature sensor $2: Threshold (in Celsius) for triggering a major low-temperature notification. |
Severity level |
Major |
Example |
Dropped below the lower major threshold---Current reading:4--Threshold reading:5 |
Impact |
Performance degradation and unstable operation might occur on the device components if the temperature is too low. If the temperature does not rise and the alarm persists, it may result in further temperature reduction and generate alarms of the critical level. Therefore, it is important to detect potential issues that may lead to low temperature alarms as early as possible in order to avoid problem escalation. |
Cause |
The temperature is too low. |
Recommended action |
1. Adjust the temperature of the equipment room. 2. If the issue persists, contact Technical Support. |
Dropped below the lower critical threshold
Event code |
0x01400002 |
Message text |
Dropped below the lower critical threshold---Current reading:$1---Threshold reading:$2 |
Variable fields |
$1: Current reading of the temperature sensor $2: Threshold (in Celsius) for triggering a critical low-temperature notification. |
Severity level |
Critical |
Example |
Dropped below the lower critical threshold---Current reading:0--Threshold reading:1 |
Impact |
Operating devices in ultra-low temperature environments can reduce device performance, impact device lifespan, disrupt business operations, and lead to system downtime. |
Cause |
The temperature is too low. |
Recommended action |
1. Adjust the temperature of the equipment room. 2. If the issue persists, contact Technical Support. |
Exceeded the upper minor threshold
Event code |
0x01700002 |
Message text |
Exceeded the upper minor threshold---Current reading:$1---Threshold reading:$2 |
Variable fields |
$1: Current reading of the temperature sensor $2: Threshold (in Celsius) for triggering a minor high-temperature notification. |
Severity level |
Minor |
Example |
Exceeded the upper minor threshold---Current reading:85---Threshold reading:80 |
Impact |
Performance degradation and unstable operation might occur on the device components if the temperature is too high. If the temperature does not decrease and the alarm persists, it may result in further temperature rise and generate major-level alarms. Therefore, it is important to detect potential issues that may lead to high temperature alarms as early as possible in order to avoid problem escalation. |
Cause |
High ambient temperature, blockage of air intake or exhaust, and low fan speed. |
Recommended action |
1. Adjust the temperature of the equipment room. 2. Verify that the air inlet and outlet are not blocked. 3. Log in to HDM, and verify that the fans are running correctly. If abnormal fans exist, replace them. 4. Log in to HDM, access the fan management page, and verify that the fan speed is appropriate. 5. If the issue persists, contact Technical Support. |
Exceeded the upper major threshold
Event code |
0x01900002 |
Message text |
Exceeded the upper major threshold---Current reading:$1---Threshold reading:$2 |
Variable fields |
$1: Current reading of the temperature sensor $2: Threshold (in Celsius) for triggering a major high-temperature notification. |
Severity level |
Major |
Example |
Exceeded the upper major threshold---Current reading:90---Threshold reading:88 |
Impact |
Performance degradation and unstable operation might occur on the device components if the temperature is too high. If the temperature does not decrease and the alarm persists, it may result in further temperature rise and generate critical-level alarms. Therefore, it is important to detect potential issues that may lead to high temperature alarms as early as possible in order to avoid problem escalation. |
Cause |
High ambient temperature, clogged air intake or exhaust, and low fan speed. |
Recommended action |
1. Adjust the temperature of the equipment room. 2. Verify that the air inlet and outlet are not blocked. 3. Log in to HDM, and verify that the fans are running correctly. If abnormal fans exist, replace them. 4. Log in to HDM, access the fan management page, and verify that the fan speed is appropriate. 5. If the issue persists, contact Technical Support. |
Exceeded the upper critical threshold
Event code |
0x01b00002 |
Message text |
Exceeded the upper critical threshold---Current reading:$1---Threshold reading:$2 |
Variable fields |
$1: Current reading of the temperature sensor $2: Threshold (in Celsius) for triggering a critical high-temperature notification. |
Severity level |
Critical |
Example |
Exceeded the upper critical threshold---Current reading:95---Threshold reading:90 |
Impact |
Operating devices in high-temperature environments can reduce device performance, impact device lifespan, increase energy consumption, disrupt business operations, and cause system crashes. |
Cause |
High ambient temperature, clogged air intake or exhaust, and low fan speed. |
Recommended action |
1. Adjust the temperature of the equipment room. 2. Verify that the air inlet and outlet are not blocked. 3. Log in to HDM, and verify that the fans are running correctly. If abnormal fans exist, replace them. 4. Log in to HDM, access the fan management page, and verify that the fan speed is appropriate. 5. If the issue persists, contact Technical Support. |
Voltage
Dropped below the lower minor threshold
Event code |
0x02000002 |
Message text |
Dropped below the lower minor threshold---Current reading:$1---Threshold reading:$2 |
Variable fields |
$1: Current reading of the voltage sensor. $2: Threshold for triggering a minor low-voltage notification. |
Severity level |
Minor |
Example |
Dropped below the lower minor threshold---Current reading:8--Threshold reading:10 |
Impact |
Performance degradation and unstable operation might occur on the device components if the voltage is too low. |
Cause |
Abnormal board voltage. |
Recommended action |
1. Verify whether the log was generated during device power-on or power-off. If it was, no action is required. 2. If device was running correctly when the log was generated, replace the system board. 3. If the issue persists, contact Technical Support. |
Dropped below the lower major threshold
Event code |
0x02200002 |
Message text |
Dropped below the lower major threshold---Current reading:$1---Threshold reading:$2 |
Variable fields |
$1: Current reading of the voltage sensor. $2: Threshold for triggering a major low-voltage notification. |
Severity level |
Major |
Example |
Dropped below the lower major threshold---Current reading:4--Threshold reading:5 |
Impact |
Performance degradation and unstable operation might occur on the device components if the voltage is too low. |
Cause |
Abnormal board voltage. |
Recommended action |
1. Verify whether the log was generated during device power-on or power-off. If it was, no action is required. 2. If device was running correctly when the log was generated, replace the system board. 3. If the issue persists, contact Technical Support. |
Dropped below the lower major threshold
Event code |
0x02220002 |
Message text |
Dropped below the lower major threshold---Current reading:$1---Threshold reading:$2 |
Variable fields |
$1: Current reading of the voltage sensor. $2: Threshold for triggering a major low-voltage notification. |
Severity level |
Major |
Example |
Dropped below the lower major threshold---Current reading:10---Threshold reading:2 |
Impact |
Memory and system performance degradation might occur. |
Cause |
This alarm is generated when the PMIC voltage reading of the memory is lower than the low voltage major alarm threshold. |
Recommended action |
1. Verify whether the log was generated during device power-on or power-off. If it was, no action is required. 2. If device was running correctly when the log was generated, replace the DIMM. 3. If the issue persists, contact Technical Support. |
Dropped below the lower critical threshold
Event code |
0x02400002 |
Message text |
Dropped below the lower critical threshold---Current reading:$1---Threshold reading:$2 |
Variable fields |
$1: Current reading of the voltage sensor. $2: Threshold for triggering a critical low-voltage notification. |
Severity level |
Critical |
Example |
Dropped below the lower critical threshold---Current reading:0--Threshold reading:1 |
Impact |
The device is running in an ultra-low voltage environment, which affects the system's power supply, or causes one board to power off, leading to a system crash. |
Cause |
Abnormal board voltage. |
Recommended action |
1. Verify whether the log was generated during device power-on or power-off. If it was, no action is required. 2. If device was running correctly when the log was generated, replace the system board. 3. If the issue persists, contact Technical Support. |
Exceeded the upper minor threshold
Event code |
0x02700002 |
Message text |
Exceeded the upper minor threshold---Current reading:$1---Threshold reading:$2 |
Variable fields |
$1: Current reading of the voltage sensor. $2: Threshold for triggering a minor high-voltage notification. |
Severity level |
Minor |
Example |
Exceeded the upper minor threshold---Current reading:85---Threshold reading:80 |
Impact |
Performance degradation and unstable operation might occur on the device components if the voltage is too high. |
Cause |
Abnormal board voltage. |
Recommended action |
1. Verify whether the log was generated during device power-on or power-off. If it was, no action is required. 2. If device was running correctly when the log was generated, replace the system board. 3. If the issue persists, contact Technical Support. |
Exceeded the upper major threshold
Event code |
0x02900002 |
Message text |
Exceeded the upper major threshold---Current reading:$1---Threshold reading:$2 |
Variable fields |
$1: Current reading of the voltage sensor. $2: Threshold for triggering a major high-voltage notification. |
Severity level |
Major |
Example |
Exceeded the upper major threshold---Current reading:90---Threshold reading:88 |
Impact |
Performance degradation and unstable operation might occur on the device components if the voltage is too high. |
Cause |
Abnormal board voltage. |
Recommended action |
1. Verify whether the log was generated during device power-on or power-off. If it was, no action is required. 2. If device was running correctly when the log was generated, replace the system board. 3. If the issue persists, contact Technical Support. |
Exceeded the upper major threshold
Event code |
0x02920002 |
Message text |
Exceeded the upper major threshold---Current reading:$1---Threshold reading:$2 |
Variable fields |
$1: Current reading of the voltage sensor. $2: Threshold for triggering a major high-voltage notification. |
Severity level |
Major |
Example |
Exceeded the upper major threshold---Current reading:10---Threshold reading:1 |
Impact |
Memory and system performance degradation might occur. |
Cause |
This alarm is generated when the PMIC voltage of the memory is higher than the current major voltage alarm threshold. |
Recommended action |
1. Verify whether the log was generated during device power-on or power-off. If it was, no action is required. 2. If device was running correctly when the log was generated, replace the DIMM. 3. If the issue persists, contact Technical Support. |
Exceeded the upper critical threshold
Event code |
0x02b00002 |
Message text |
Exceeded the upper critical threshold---Current reading:$1---Threshold reading:$2 |
Variable fields |
$1: Current reading of the voltage sensor. $2: Threshold for triggering a critical high-voltage notification. |
Severity level |
Critical |
Example |
Exceeded the upper critical threshold---Current reading:95---Threshold reading:90 |
Impact |
The device is operating in an ultra-high voltage environment, which affects the system's power supply, or causes a board to power off, resulting in a system crash. |
Cause |
Abnormal board voltage. |
Recommended action |
1. Verify whether the log was generated during device power-on or power-off. If it was, no action is required. 2. If device was running correctly when the log was generated, replace the system board. 3. If the issue persists, contact Technical Support. |
Transition to Non-recoverable from less severe
Event code |
0x1530200e |
Message text |
Transition to Non-recoverable from less severe |
Variable fields |
N/A |
Severity level |
Critical |
Example |
Transition to Non-recoverable from less severe |
Impact |
HDD Bay does not operate correctly, which impacts the reliability of the system. |
Cause |
The HDD Bay voltage is abnormal. |
Recommended action |
1. Reconnect the HDD Bay node. Make sure the node is completely powered off from the AC power source before powering on the node. 2. If the issue persists, replace the HDD Bay component. 3. If the issue persists, contact Technical Support. |
Transition to Non-recoverable from less severe
Event code |
0x0230a00e |
Message text |
Transition to Non-recoverable from less severe---System detected a power supply failure ($1) |
Variable fields |
$1: AC lost |
Severity level |
Critical |
Example |
Transition to Non-recoverable from less severe---System detected a power supply failure (AC lost) |
Impact |
The AC power supply is removed from the device. |
Cause |
CPLD detected ACFAIL signal from all PSUs. |
Recommended action |
1. Examine whether any abnormalities exist in the power supply network of the device, such as power grid fluctuations, PDU abnormality, or poor contact of the national standard power cord. 2. Examine the PSUs for errors. If problems are detected, replace the PSUs. 3. If the issue persists, contact Technical Support. |
Transition to Non-recoverable from less severe
Event code |
0x0230d00e |
Message text |
Transition to Non-recoverable from less severe---System detected a power supply failure on $1 |
Variable fields |
$1: Mezz1, Mezz2, or Mezz3 |
Severity level |
Critical |
Example |
Transition to Non-recoverable from less severe---System detected a power supply failure on Mezz3 |
Impact |
The device immediately shuts down and enters power failure state. The LEDs on the chassis ear are rapidly flashing (the power LED flashes red, the UID LED flashes blue, the NIC LED flashes green, and the health LED flashes red), and the status is no longer controllable. The LED status recovers after the issue is resolved and the device is re-powered on. |
Cause |
CPLD detects PGD signal of MEZZ. |
Recommended action |
1. Reconnect the power cords. Verify that the server can be powered on correctly. If the server cannot be powered on, replace the corresponding MEZZ module. 2. If the issue persists, contact Technical Support. |
Transition to Non-recoverable from less severe
Event code |
0x0230200e |
Message text |
Transition to Non-recoverable from less severe---System detected a power supply failure on $1 |
Variable fields |
$1: CPU power supply failure type. Options include PVCCD_HV_CPU3, PVPP_HBM_CPU3, PVCCFA_EHV_CPU3, PVCCFA_EHV_FIVRA_CPU3, PVCCINFAON_CPU3, PVNN_MAIN_CPU3, PVCCIN_CPU3, PVCCD_HV_CPU4, PVPP_HBM_CPU4, PVCCFA_EHV_CPU4, PVCCFA_EHV_FIVRA_CPU4, PVCCINFAON_CPU4, PVNN_MAIN_CPU4, and PVCCIN_CPU4. |
Severity level |
Critical |
Example |
Transition to Non-recoverable from less severe---System detected a power supply failure (PVCCD_HV_CPU3) |
Impact |
The device is immediately shut down and enters power failure state. The LEDs on the chassis ear are rapidly flashing (the power LED flashes red, the UID LED flashes blue, the NIC LED flashes green, and the health LED flashes red), and the status is no longer controllable. The LED status recovers after the issue is resolved and the device is re-powered on. |
Cause |
The internal power supply of the CPU experiences faults such as overcurrent, overvoltage, or undervoltage in the VR chip on the processor mezzanine board that corresponds to the CPU power supply. |
Recommended action |
1. Identify whether the server is powered off. If the server is powered off, re-connect the power cord and identify whether the server can be powered on properly. 2. If the server is not powered off, replace the processor mezzanine board. 3. If the issue persists, replace the CPU. 4. If the issue persists, contact Technical Support. |
Transition to Non-recoverable from less severe
Event code |
0x0231d00e |
Message text |
Transition to Non-recoverable from less severe---System detected a power supply failure on $1 |
Variable fields |
$1: RAID card |
Severity level |
Critical |
Example |
Transition to Non-recoverable from less severe---System detected a power supply failure on RAID card |
Impact |
The device immediately shuts down and enters power failure state. The LEDs on the chassis ear are rapidly flashing (the power LED flashes red, the UID LED flashes blue, the NIC LED flashes green, and the health LED flashes red), and the status is no longer controllable. The LED status recovers after the issue is resolved and the device is re-powered on. |
Cause |
CPLD detects PGD signal of RAID controller. |
Recommended action |
1. Reconnect the power cords. Verify that the server can be powered on correctly. If the server cannot be powered on, replace the corresponding RAID controller. 2. If the issue persists, contact Technical Support. |
Transition to Non-recoverable from less severe
Event code |
0x0231190e |
Message text |
Transition to Non-recoverable from less severe---System detected a power supply failure($1) |
Variable fields |
$1: CPU1_DIMM_PMIC_ERROR_1-6, P1_DIMM_AF_PMIC_ERROR |
Severity level |
Critical |
Example |
Transition to Non-recoverable from less severe---System detected a power supply failure(CPU1_DIMM_PMIC_ERROR_1-6) |
Impact |
System power-off might occur. |
Cause |
The power supply is abnormal. |
Recommended action |
1. Re-install the memory modules in slots 1 through 6 under CPU1. 2. Examine whether the CPU is securely fastened. 3. Examine the CPU socket for bent pins or foreign objects. 4. If the issue persists, contact Technical Support. |
Transition to Non-recoverable from less severe
Event code |
0x02311a0e |
Message text |
Transition to Non-recoverable from less severe---System detected a power supply failure($1) |
Variable fields |
$1: CPU1_DIMM_PMIC_ERROR_7-12, P1_DIMM_GL_PMIC_ERROR |
Severity level |
Critical |
Example |
Transition to Non-recoverable from less severe---System detected a power supply failure(CPU1_DIMM_PMIC_ERROR_7-12) |
Impact |
System power-off might occur. |
Cause |
The power supply is abnormal. |
Recommended action |
1. Re-install the memory modules in slots 7 through 12 under CPU1. 2. Examine whether the CPU is securely fastened 3. Examine the CPU socket for bent pins or foreign objects. 4. If the issue persists, contact Technical Support. |
Transition to Non-recoverable from less severe
Event code |
0x02311b0e |
Message text |
Transition to Non-recoverable from less severe---System detected a power supply failure($1) |
Variable fields |
$1: CPU2_DIMM_PMIC_ERROR_1-6, P2_DIMM_AF_PMIC_ERROR |
Severity level |
Critical |
Example |
Transition to Non-recoverable from less severe---System detected a power supply failure(CPU2_DIMM_PMIC_ERROR_1-6) |
Impact |
System power-off might occur. |
Cause |
The power supply is abnormal. |
Recommended action |
1. Re-install the memory modules in slots 1 through 6 under CPU2. 2. Examine whether the CPU is securely fastened 3. Examine the CPU socket for bent pins or foreign objects. 4. If the issue persists, contact Technical Support. |
Transition to Non-recoverable from less severe
Event code |
0x02311c0e |
Message text |
Transition to Non-recoverable from less severe---System detected a power supply failure($1) |
Variable fields |
$1: CPU2_DIMM_PMIC_ERROR_7-12, P2_DIMM_GL_PMIC_ERROR |
Severity level |
Critical |
Example |
Transition to Non-recoverable from less severe---System detected a power supply failure(CPU2_DIMM_PMIC_ERROR_7-12) |
Impact |
System power-off might occur. |
Cause |
The power supply is abnormal. |
Recommended action |
1. Re-install the memory modules in slots 7 through 12 under CPU2. 2. Examine whether the CPU is securely fastened 3. Examine the CPU socket for bent pins or foreign objects. 4. If the issue persists, contact Technical Support. |
Transition to Non-recoverable from less severe
Event code |
0x0231500e |
Message text |
Transition to Non-recoverable from less severe---System detected a power supply failure($1) |
Variable fields |
$1: OCP1 network card, OCP2 network card, or OCP3 network card |
Severity level |
Critical |
Example |
Transition to Non-recoverable from less severe---System detected a power supply failure(OCP1 network card) |
Impact |
System power-off might occur. |
Cause |
The power supply of the OCP network adapter is abnormal. |
Recommended action |
1. Identify whether the server is powered off. If the server is powered off, re-connect the power cord and identify whether the server can be powered on properly. 2. If the server is not powered off, replace the OCP network adapter. 3. If the issue persists, replace the adapter. 4. If the issue persists, replace the system board. 5. If the issue persists, contact Technical Support. |
Transition to Non-recoverable from less severe
Event code |
0x0233000e |
Message text |
Transition to Non-recoverable from less severe---System detected a power supply failure($1) |
Variable fields |
$1: BMC_network_PHY_P1V0, BMC_network_PHY_P1V8 |
Severity level |
Critical |
Example |
Transition to Non-recoverable from less severe---System detected a power supply failure(BMC_network_PHY_P1V0) |
Impact |
System power-off might occur. |
Cause |
The power supply of the BMC card is abnormal. |
Recommended action |
1. Identify whether the server is powered off. If the server is powered off, re-connect the power cord and identify whether the server can be powered on properly. 2. If the server is not powered off, replace the BMC card. 3. If the issue persists, replace the system board. 4. If the issue persists, contact Technical Support. |
Transition to Non-recoverable from less severe
Event code |
0x0233a00e |
Message text |
Transition to Non-recoverable from less severe---System detected a power supply failure($1) |
Variable fields |
$1: DSD card |
Severity level |
Critical |
Example |
Transition to Non-recoverable from less severe---System detected a power supply failure(DSD card) |
Impact |
System power-off might occur. |
Cause |
Abnormal DSD card voltage. |
Recommended action |
1. Identify whether the server is powered off. If the server is powered off, re-connect the power cord and identify whether the server can be powered on properly. 2. If the server is not powered off, replace the DSD card. 3. If the issue persists, replace the system board. 4. If the issue persists, contact Technical Support. |
Transition to Non-recoverable from less severe
Event code |
0x0233d00e |
Message text |
Transition to Non-recoverable from less severe---System detected a power supply failure($1) |
Variable fields |
$1: P12V |
Severity level |
Critical |
Example |
Transition to Non-recoverable from less severe---System detected a power supply failure(P12V) |
Impact |
System power-off might occur. |
Cause |
Abnormal P12V voltage. |
Recommended action |
1. Identify whether the server is powered off. If the server is powered off, re-connect the power cord and identify whether the server can be powered on properly. 2. Sequentially check the PSU, fans, RISER, drive backplane, and system board. 3. Replace the faulty component. 4. If the issue persists, contact Technical Support. |
Transition to Non-recoverable from less severe
Event code |
0x0233e00e |
Message text |
Transition to Non-recoverable from less severe---System detected a power supply failure($1) |
Variable fields |
$1: P5V |
Severity level |
Critical |
Example |
Transition to Non-recoverable from less severe---System detected a power supply failure(P5V) |
Impact |
System power-off might occur. |
Cause |
Abnormal P5V voltage. |
Recommended action |
1. Identify whether the server is powered off. If the server is powered off, re-connect the power cord and identify whether the server can be powered on properly. 2. If the server is not powered off, replace the system board. 3. If the issue persists, replace the BMC card. 4. If the issue persists, replace the rear backplane. 5. If the issue persists, contact Technical Support. |
Transition to Non-recoverable from less severe
Event code |
0x0233f00e |
Message text |
Transition to Non-recoverable from less severe---System detected a power supply failure($1) |
Variable fields |
$1: P5V_STBY |
Severity level |
Critical |
Example |
Transition to Non-recoverable from less severe---System detected a power supply failure(P5V_STBY) |
Impact |
System power-off might occur. |
Cause |
Abnormal P5V voltage. |
Recommended action |
1. Identify whether the server is powered off. If the server is powered off, re-connect the power cord and identify whether the server can be powered on properly. 2. If the server is not powered off, replace the system board. 3. If the issue persists, contact Technical Support. |
Transition to Non-recoverable from less severe
Event code |
0x0234000e |
Message text |
Transition to Non-recoverable from less severe---System detected a power supply failure($1) |
Variable fields |
$1: P12V_STBY |
Severity level |
Critical |
Example |
Transition to Non-recoverable from less severe---System detected a power supply failure(P12V_STBY) |
Impact |
System power-off might occur. |
Cause |
Abnormal P12V voltage. |
Recommended action |
1. Identify whether the server is powered off. If the server is powered off, re-connect the power cord and identify whether the server can be powered on properly. 2. If the server is not powered off, replace the system board. 3. If the issue persists, replace the OCP3 module. 4. If the issue persists, replace the fan module. 5. If the issue persists, contact Technical Support. |
Transition to Non-recoverable from less severe
Event code |
0x0234100e |
Message text |
Transition to Non-recoverable from less severe---System detected a power supply failure($1) |
Variable fields |
$1: P12V Overcurrent |
Severity level |
Critical |
Example |
Transition to Non-recoverable from less severe---System detected a power supply failure(P12V Overcurrent) |
Impact |
System power-off might occur. |
Cause |
Abnormal P12V signal current. |
Recommended action |
1. Identify whether the server is powered off. If the server is powered off, re-connect the power cord and identify whether the server can be powered on properly. 2. If the server is not powered off, replace the system board. 3. If the issue persists, replace the fan module. 4. If the issue persists, replace the memory module. 5. If the issue persists, contact Technical Support. |
Transition to Non-recoverable from less severe
Event code |
0x0234200e |
Message text |
Transition to Non-recoverable from less severe---System detected a power supply failure($1) |
Variable fields |
$1: PVCCD_HV_CPU1 |
Severity level |
Critical |
Example |
Transition to Non-recoverable from less severe---System detected a power supply failure(PVCCD_HV_CPU1) |
Impact |
System power-off might occur. |
Cause |
Abnormal board voltage. |
Recommended action |
1. Identify whether the server is powered off. If the server is powered off, re-connect the power cord and identify whether the server can be powered on properly. 2. If the server is not powered off, replace the system board. 3. If the issue persists, replace the CPU. 4. If the issue persists, contact Technical Support. |
Transition to Non-recoverable from less severe
Event code |
0x0234300e |
Message text |
Transition to Non-recoverable from less severe---System detected a power supply failure($1) |
Variable fields |
$1: PVPP_HBM_CPU1 |
Severity level |
Critical |
Example |
Transition to Non-recoverable from less severe---System detected a power supply failure(PVPP_HBM_CPU1) |
Impact |
System power-off might occur. |
Cause |
Abnormal board voltage. |
Recommended action |
1. Identify whether the server is powered off. If the server is powered off, re-connect the power cord and identify whether the server can be powered on properly. 2. If the server is not powered off, replace the system board. 3. If the issue persists, replace the CPU. 4. If the issue persists, contact Technical Support. |
Transition to Non-recoverable from less severe
Event code |
0x0234400e |
Message text |
Transition to Non-recoverable from less severe---System detected a power supply failure($1) |
Variable fields |
$1: PVCCFA_EHV_CPU1 |
Severity level |
Critical |
Example |
Transition to Non-recoverable from less severe---System detected a power supply failure(PVCCFA_EHV_CPU1) |
Impact |
System power-off might occur. |
Cause |
Abnormal board voltage. |
Recommended action |
1. Identify whether the server is powered off. If the server is powered off, re-connect the power cord and identify whether the server can be powered on properly. 2. If the server is not powered off, replace the system board. 3. If the issue persists, replace the CPU. 4. If the issue persists, contact Technical Support. |
Transition to Non-recoverable from less severe
Event code |
0x0234500e |
Message text |
Transition to Non-recoverable from less severe---System detected a power supply failure($1) |
Variable fields |
$1: PVCCFA_EHV_FIVRA_CPU1 |
Severity level |
Critical |
Example |
Transition to Non-recoverable from less severe---System detected a power supply failure(PVCCFA_EHV_FIVRA_CPU1) |
Impact |
System power-off might occur. |
Cause |
Abnormal board voltage. |
Recommended action |
1. Identify whether the server is powered off. If the server is powered off, re-connect the power cord and identify whether the server can be powered on properly. 2. If the server is not powered off, replace the system board. 3. If the issue persists, replace the CPU. 4. If the issue persists, contact Technical Support. |
Transition to Non-recoverable from less severe
Event code |
0x0234600e |
Message text |
Transition to Non-recoverable from less severe---System detected a power supply failure($1) |
Variable fields |
$1: PVCCINFAON_CPU1 |
Severity level |
Critical |
Example |
Transition to Non-recoverable from less severe---System detected a power supply failure(PVCCINFAON_CPU1) |
Impact |
System power-off might occur. |
Cause |
Abnormal board voltage. |
Recommended action |
1. Identify whether the server is powered off. If the server is powered off, re-connect the power cord and identify whether the server can be powered on properly. 2. If the server is not powered off, replace the system board. 3. If the issue persists, replace the CPU. 4. If the issue persists, contact Technical Support. |
Transition to Non-recoverable from less severe
Event code |
0x0234700e |
Message text |
Transition to Non-recoverable from less severe---System detected a power supply failure($1) |
Variable fields |
$1: PVNN_MAIN_CPU1 |
Severity level |
Critical |
Example |
Transition to Non-recoverable from less severe---System detected a power supply failure(PVNN_MAIN_CPU1) |
Impact |
System power-off might occur. |
Cause |
Abnormal board voltage. |
Recommended action |
1. Identify whether the server is powered off. If the server is powered off, re-connect the power cord and identify whether the server can be powered on properly. 2. If the server is not powered off, replace the system board. 3. If the issue persists, replace the CPU. 4. If the issue persists, contact Technical Support. |
Transition to Non-recoverable from less severe
Event code |
0x0234800e |
Message text |
Transition to Non-recoverable from less severe---System detected a power supply failure($1) |
Variable fields |
$1: PVCCIN_CPU1 |
Severity level |
Critical |
Example |
Transition to Non-recoverable from less severe---System detected a power supply failure(PVCCIN_CPU1) |
Impact |
System power-off might occur. |
Cause |
Abnormal board voltage. |
Recommended action |
1. Identify whether the server is powered off. If the server is powered off, re-connect the power cord and identify whether the server can be powered on properly. 2. If the server is not powered off, replace the system board. 3. If the issue persists, replace the CPU. 4. If the issue persists, contact Technical Support. |
Transition to Non-recoverable from less severe
Event code |
0x0234900e |
Message text |
Transition to Non-recoverable from less severe---System detected a power supply failure($1) |
Variable fields |
$1: PVCCD_HV_CPU2 |
Severity level |
Critical |
Example |
Transition to Non-recoverable from less severe---System detected a power supply failure(PVCCD_HV_CPU2) |
Impact |
System power-off might occur. |
Cause |
Abnormal board voltage. |
Recommended action |
1. Identify whether the server is powered off. If the server is powered off, re-connect the power cord and identify whether the server can be powered on properly. 2. If the server is not powered off, replace the system board. 3. If the issue persists, replace the CPU. 4. If the issue persists, contact Technical Support. |
Transition to Non-recoverable from less severe
Event code |
0x0234a00e |
Message text |
Transition to Non-recoverable from less severe---System detected a power supply failure($1) |
Variable fields |
$1: PVPP_HBM_CPU2 |
Severity level |
Critical |
Example |
Transition to Non-recoverable from less severe---System detected a power supply failure(PVPP_HBM_CPU2) |
Impact |
System power-off might occur. |
Cause |
Abnormal board voltage. |
Recommended action |
1. Identify whether the server is powered off. If the server is powered off, re-connect the power cord and identify whether the server can be powered on properly. 2. If the server is not powered off, replace the system board. 3. If the issue persists, replace the CPU. 4. If the issue persists, contact Technical Support. |
Transition to Non-recoverable from less severe
Event code |
0x0234b00e |
Message text |
Transition to Non-recoverable from less severe---System detected a power supply failure($1) |
Variable fields |
$1: PVCCFA_EHV_CPU2 |
Severity level |
Critical |
Example |
Transition to Non-recoverable from less severe---System detected a power supply failure(PVCCFA_EHV_CPU2) |
Impact |
System power-off might occur. |
Cause |
Abnormal board voltage. |
Recommended action |
1. Identify whether the server is powered off. If the server is powered off, re-connect the power cord and identify whether the server can be powered on properly. 2. If the server is not powered off, replace the system board. 3. If the issue persists, replace the CPU. 4. If the issue persists, contact Technical Support. |
Transition to Non-recoverable from less severe
Event code |
0x0234c00e |
Message text |
Transition to Non-recoverable from less severe---System detected a power supply failure($1) |
Variable fields |
$1: PVCCFA_EHV_FIVRA_CPU2 |
Severity level |
Critical |
Example |
Transition to Non-recoverable from less severe---System detected a power supply failure(PVCCFA_EHV_FIVRA_CPU2) |
Impact |
System power-off might occur. |
Cause |
Abnormal board voltage. |
Recommended action |
1. Identify whether the server is powered off. If the server is powered off, re-connect the power cord and identify whether the server can be powered on properly. 2. If the server is not powered off, replace the system board. 3. If the issue persists, replace the CPU. 4. If the issue persists, contact Technical Support. |
Transition to Non-recoverable from less severe
Event code |
0x0234d00e |
Message text |
Transition to Non-recoverable from less severe---System detected a power supply failure($1) |
Variable fields |
$1: PVCCINFAON_CPU2 |
Severity level |
Critical |
Example |
Transition to Non-recoverable from less severe---System detected a power supply failure(PVCCINFAON_CPU2) |
Impact |
System power-off might occur. |
Cause |
Abnormal board voltage. |
Recommended action |
1. Identify whether the server is powered off. If the server is powered off, re-connect the power cord and identify whether the server can be powered on properly. 2. If the server is not powered off, replace the system board. 3. If the issue persists, replace the CPU. 4. If the issue persists, contact Technical Support. |
Transition to Non-recoverable from less severe
Event code |
0x0234e00e |
Message text |
Transition to Non-recoverable from less severe---System detected a power supply failure($1) |
Variable fields |
$1: PVNN_MAIN_CPU2 |
Severity level |
Critical |
Example |
Transition to Non-recoverable from less severe---System detected a power supply failure(PVNN_MAIN_CPU2) |
Impact |
System power-off might occur. |
Cause |
Abnormal board voltage. |
Recommended action |
1. Identify whether the server is powered off. If the server is powered off, re-connect the power cord and identify whether the server can be powered on properly. 2. If the server is not powered off, replace the system board. 3. If the issue persists, replace the CPU. 4. If the issue persists, contact Technical Support. |
Transition to Non-recoverable from less severe
Event code |
0x0234f00e |
Message text |
Transition to Non-recoverable from less severe---System detected a power supply failure($1) |
Variable fields |
$1: PVCCIN_CPU2 |
Severity level |
Critical |
Example |
Transition to Non-recoverable from less severe---System detected a power supply failure(PVCCIN_CPU2) |
Impact |
System power-off might occur. |
Cause |
Abnormal board voltage. |
Recommended action |
1. Identify whether the server is powered off. If the server is powered off, re-connect the power cord and identify whether the server can be powered on properly. 2. If the server is not powered off, replace the system board. 3. If the issue persists, replace the CPU. 4. If the issue persists, contact Technical Support. |
Transition to Non-recoverable from less severe
Event code |
0x0235000e |
Message text |
Transition to Non-recoverable from less severe---System detected a power supply failure($1) |
Variable fields |
$1: P3V3_STBY_A |
Severity level |
Critical |
Example |
Transition to Non-recoverable from less severe---System detected a power supply failure(P3V3_STBY_A) |
Impact |
System power-off might occur. |
Cause |
Abnormal board voltage. |
Recommended action |
1. Identify whether the server is powered off. If the server is powered off, re-connect the power cord and identify whether the server can be powered on properly. 2. If the server is not powered off, replace the system board. 3. If the issue persists, contact Technical Support. |
Transition to Non-recoverable from less severe
Event code |
0x0235100e |
|
Message text |
Transition to Non-recoverable from less severe---System detected a power supply failure($1) |
|
Variable fields |
$1: P5V_STBY |
|
Severity level |
Critical |
|
Example |
Transition to Non-recoverable from less severe---System detected a power supply failure(P5V_STBY) |
|
Impact |
System power-off might occur. |
|
Cause |
Abnormal board voltage. |
|
Recommended action |
1. Identify whether the server is powered off. If the server is powered off, re-connect the power cord and identify whether the server can be powered on properly. 2. If the server is not powered off, replace the system board. 3. If the issue persists, replace the BMC card. 4. If the issue persists, contact Technical Support. |
|
Transition to Non-recoverable from less severe
Event code |
0x0235200e |
Message text |
Transition to Non-recoverable from less severe---System detected a power supply failure($1) |
Variable fields |
$1: P12V_STBY |
Severity level |
Critical |
Example |
Transition to Non-recoverable from less severe---System detected a power supply failure(P12V_STBY) |
Impact |
System power-off might occur. |
Cause |
Abnormal board voltage. |
Recommended action |
1. Identify whether the server is powered off. If the server is powered off, re-connect the power cord and identify whether the server can be powered on properly. 2. If the server is not powered off, replace the PSUs. 3. If the issue persists, replace the system board. 4. If the issue persists, contact Technical Support. |
Transition to Non-recoverable from less severe
Event code |
0x0235300e |
Message text |
Transition to Non-recoverable from less severe---System detected a power supply failure($1) |
Variable fields |
$1: P12V |
Severity level |
Critical |
Example |
Transition to Non-recoverable from less severe---System detected a power supply failure(P12V) |
Impact |
System power-off might occur. |
Cause |
Abnormal board voltage. |
Recommended action |
1. Identify whether the server is powered off. If the server is powered off, re-connect the power cord and identify whether the server can be powered on properly. 2. If the server is not powered off, replace the PSUs. 3. If the issue persists, replace the system board. 4. If the issue persists, contact Technical Support. |
Transition to Non-recoverable from less severe
Event code |
0x0235400e |
Message text |
Transition to Non-recoverable from less severe---System detected a power supply failure($1) |
Variable fields |
$1: CPU1_1V8_STBY |
Severity level |
Critical |
Example |
Transition to Non-recoverable from less severe---System detected a power supply failure(CPU1_1V8_STBY) |
Impact |
System power-off might occur. |
Cause |
Abnormal board voltage. |
Recommended action |
1. Identify whether the server is powered off. If the server is powered off, re-connect the power cord and identify whether the server can be powered on properly. 2. If the server is not powered off, replace the system board. 3. If the issue persists, replace CPU1. 4. If the issue persists, contact Technical Support. |
Transition to Non-recoverable from less severe
Event code |
0x0235500e |
Message text |
Transition to Non-recoverable from less severe---System detected a power supply failure($1) |
Variable fields |
$1: CPU1_3V3_STBY |
Severity level |
Critical |
Example |
Transition to Non-recoverable from less severe---System detected a power supply failure(CPU1_3V3_STBY) |
Impact |
System power-off might occur. |
Cause |
Abnormal board voltage. |
Recommended action |
1. Identify whether the server is powered off. If the server is powered off, re-connect the power cord and identify whether the server can be powered on properly. 2. If the server is not powered off, replace the system board. 3. If the issue persists, replace CPU1. 4. If the issue persists, contact Technical Support. |
Transition to Non-recoverable from less severe
Event code |
0x0235600e |
Message text |
Transition to Non-recoverable from less severe---System detected a power supply failure($1) |
Variable fields |
$1: CPU2_1V8_STBY |
Severity level |
Critical |
Example |
Transition to Non-recoverable from less severe---System detected a power supply failure(CPU2_1V8_STBY) |
Impact |
System power-off might occur. |
Cause |
Abnormal board voltage. |
Recommended action |
1. Identify whether the server is powered off. If the server is powered off, re-connect the power cord and identify whether the server can be powered on properly. If the server is not powered off, replace the system board. 2. If the issue persists, replace CPU2. 3. If the issue persists, contact Technical Support. |
Transition to Non-recoverable from less severe
Event code |
0x0235700e |
Message text |
Transition to Non-recoverable from less severe---System detected a power supply failure($1) |
Variable fields |
$1: CPU2_3V3_STBY |
Severity level |
Critical |
Example |
Transition to Non-recoverable from less severe---System detected a power supply failure(CPU2_3V3_STBY) |
Impact |
System power-off might occur. |
Cause |
Abnormal board voltage. |
Recommended action |
1. Identify whether the server is powered off. If the server is powered off, re-connect the power cord and identify whether the server can be powered on properly. 2. If the server is not powered off, replace the system board. 3. If the issue persists, replace CPU2. 4. If the issue persists, contact Technical Support. |
Transition to Non-recoverable from less severe
Event code |
0x0235800e |
Message text |
Transition to Non-recoverable from less severe---System detected a power supply failure($1) |
Variable fields |
$1: CPU1_VDDCR1 |
Severity level |
Critical |
Example |
Transition to Non-recoverable from less severe---System detected a power supply failure(CPU1_VDDCR1) |
Impact |
System power-off might occur. |
Cause |
Abnormal board voltage. |
Recommended action |
1. Identify whether the server is powered off. If the server is powered off, re-connect the power cord and identify whether the server can be powered on properly. If the server is not powered off, replace the system board. 2. If the issue persists, replace CPU1. 3. If the issue persists, contact Technical Support. |
Transition to Non-recoverable from less severe
Event code |
0x0235900e |
Message text |
Transition to Non-recoverable from less severe---System detected a power supply failure($1) |
Variable fields |
$1: CPU1_VDDCR0 |
Severity level |
Critical |
Example |
Transition to Non-recoverable from less severe---System detected a power supply failure(CPU1_VDDCR0) |
Impact |
System power-off might occur. |
Cause |
Abnormal board voltage. |
Recommended action |
1. Identify whether the server is powered off. If the server is powered off, re-connect the power cord and identify whether the server can be powered on properly. 2. If the server is not powered off, replace the system board. 3. If the issue persists, replace CPU1. 4. If the issue persists, contact Technical Support. |
Transition to Non-recoverable from less severe
Event code |
0x0235a00e |
Message text |
Transition to Non-recoverable from less severe---System detected a power supply failure($1) |
Variable fields |
$1: CPU1_VDDCR_SOC |
Severity level |
Critical |
Example |
Transition to Non-recoverable from less severe---System detected a power supply failure(CPU1_VDDCR_SOC) |
Impact |
System power-off might occur. |
Cause |
Abnormal board voltage. |
Recommended action |
1. Identify whether the server is powered off. If the server is powered off, re-connect the power cord and identify whether the server can be powered on properly. 2. If the server is not powered off, replace the system board. 3. If the issue persists, replace CPU1. 4. If the issue persists, contact Technical Support. |
Transition to Non-recoverable from less severe
Event code |
0x0235b00e |
Message text |
Transition to Non-recoverable from less severe---System detected a power supply failure($1) |
Variable fields |
$1: CPU1_VDDIO |
Severity level |
Critical |
Example |
Transition to Non-recoverable from less severe---System detected a power supply failure(CPU1_VDDIO) |
Impact |
System power-off might occur. |
Cause |
Abnormal board voltage. |
Recommended action |
1. Identify whether the server is powered off. If the server is powered off, re-connect the power cord and identify whether the server can be powered on properly. 2. If the server is not powered off, replace the system board. 3. If the issue persists, replace CPU1. 4. If the issue persists, contact Technical Support. |
Transition to Non-recoverable from less severe
Event code |
0x0235c00e |
Message text |
Transition to Non-recoverable from less severe---System detected a power supply failure($1) |
Variable fields |
$1: CPU1_1V1 |
Severity level |
Critical |
Example |
Transition to Non-recoverable from less severe---System detected a power supply failure(CPU1_1V1) |
Impact |
System power-off might occur. |
Cause |
Abnormal board voltage. |
Recommended action |
1. Identify whether the server is powered off. If the server is powered off, re-connect the power cord and identify whether the server can be powered on properly. 2. If the server is not powered off, replace the system board. 3. If the issue persists, replace CPU1. 4. If the issue persists, contact Technical Support. |
Transition to Non-recoverable from less severe
Event code |
0x0235d00e |
Message text |
Transition to Non-recoverable from less severe---System detected a power supply failure($1) |
Variable fields |
$1: CPU2_VDDCR1 |
Severity level |
Critical |
Example |
Transition to Non-recoverable from less severe---System detected a power supply failure(CPU2_VDDCR1) |
Impact |
System power-off might occur. |
Cause |
Abnormal board voltage. |
Recommended action |
1. Identify whether the server is powered off. If the server is powered off, re-connect the power cord and identify whether the server can be powered on properly. 2. If the server is not powered off, replace the system board. 3. If the issue persists, replace CPU2. 4. If the issue persists, contact Technical Support. |
Transition to Non-recoverable from less severe
Event code |
0x0235e00e |
Message text |
Transition to Non-recoverable from less severe---System detected a power supply failure($1) |
Variable fields |
$1: CPU2_VDDCR0 |
Severity level |
Critical |
Example |
Transition to Non-recoverable from less severe---System detected a power supply failure(CPU2_VDDCR0) |
Impact |
System power-off might occur. |
Cause |
Abnormal board voltage. |
Recommended action |
1. Identify whether the server is powered off. If the server is powered off, re-connect the power cord and identify whether the server can be powered on properly. 2. If the server is not powered off, replace the system board. 3. If the issue persists, replace CPU2. 4. If the issue persists, contact Technical Support. |
Transition to Non-recoverable from less severe
Event code |
0x0235f00e |
Message text |
Transition to Non-recoverable from less severe---System detected a power supply failure($1) |
Variable fields |
$1: CPU2_VDDCR_SOC |
Severity level |
Critical |
Example |
Transition to Non-recoverable from less severe---System detected a power supply failure(CPU2_VDDCR_SOC) |
Impact |
System power-off might occur. |
Cause |
Abnormal board voltage. |
Recommended action |
1. Identify whether the server is powered off. If the server is powered off, re-connect the power cord and identify whether the server can be powered on properly. 2. If the server is not powered off, replace the system board. 3. If the issue persists, replace CPU2. 4. If the issue persists, contact Technical Support. |
Transition to Non-recoverable from less severe
Event code |
0x0236000e |
Message text |
Transition to Non-recoverable from less severe---System detected a power supply failure($1) |
Variable fields |
$1: CPU2_VDDIO |
Severity level |
Critical |
Example |
Transition to Non-recoverable from less severe---System detected a power supply failure(CPU2_VDDIO) |
Impact |
System power-off might occur. |
Cause |
Abnormal board voltage. |
Recommended action |
1. Identify whether the server is powered off. If the server is powered off, re-connect the power cord and identify whether the server can be powered on properly. 2. If the server is not powered off, replace the system board. 3. If the issue persists, replace CPU2. 4. If the issue persists, contact Technical Support. |
Transition to Non-recoverable from less severe
Event code |
0x0236100e |
Message text |
Transition to Non-recoverable from less severe---System detected a power supply failure($1) |
Variable fields |
$1: CPU2_1V1 |
Severity level |
Critical |
Example |
Transition to Non-recoverable from less severe---System detected a power supply failure(CPU2_1V1) |
Impact |
System power-off might occur. |
Cause |
Abnormal board voltage. |
Recommended action |
1. Identify whether the server is powered off. If the server is powered off, re-connect the power cord and identify whether the server can be powered on properly. 2. If the server is not powered off, replace the system board. 3. If the issue persists, replace CPU2. 4. If the issue persists, contact Technical Support. |
Transition to Non-recoverable from less severe
Event code |
0x0236200e |
Message text |
Transition to Non-recoverable from less severe---System detected a power supply failure($1) |
Variable fields |
$1: OCP1 network card |
Severity level |
Critical |
Example |
Transition to Non-recoverable from less severe---System detected a power supply failure(OCP1 network card) |
Impact |
System power-off might occur. |
Cause |
Abnormal board voltage. |
Recommended action |
1. Identify whether the server is powered off. If the server is powered off, re-connect the power cord and identify whether the server can be powered on properly. 2. If the server is not powered off, replace the OCP1 network adapter. 3. If the issue persists, contact Technical Support. |
Transition to Non-recoverable from less severe
Event code |
0x0236300e |
Message text |
Transition to Non-recoverable from less severe---System detected a power supply failure($1) |
Variable fields |
$1: OCP2 network card |
Severity level |
Critical |
Example |
Transition to Non-recoverable from less severe---System detected a power supply failure(OCP2 network card) |
Impact |
System power-off might occur. |
Cause |
Abnormal board voltage. |
Recommended action |
1. Identify whether the server is powered off. If the server is powered off, re-connect the power cord and identify whether the server can be powered on properly. 2. If the server is not powered off, replace the OCP2 network adapter. 3. If the issue persists, contact Technical Support. |
Transition to Non-recoverable from less severe
Event code |
0x0236400e |
Message text |
Transition to Non-recoverable from less severe---System detected a power supply failure($1) |
Variable fields |
$1: OCP3 network card |
Severity level |
Critical |
Example |
Transition to Non-recoverable from less severe---System detected a power supply failure(OCP3 network card) |
Impact |
System power-off might occur. |
Cause |
Abnormal board voltage. |
Recommended action |
1. Identify whether the server is powered off. If the server is powered off, re-connect the power cord and identify whether the server can be powered on properly. 2. If the server is not powered off, replace the OCP3 network adapter. 3. If the issue persists, contact Technical Support. |
Transition to Non-recoverable from less severe
Event code |
0x0236500e |
Message text |
Transition to Non-recoverable from less severe---System detected a power supply failure($1) |
Variable fields |
$1: AC lost |
Severity level |
Critical |
Example |
Transition to Non-recoverable from less severe---System detected a power supply failure(AC lost) |
Impact |
System power-off might occur. |
Cause |
Abnormal board voltage. |
Recommended action |
1. Identify whether the server is powered off. If the server is powered off, re-connect the power cord and identify whether the server can be powered on properly. 2. If the server is not powered off, replace the power supply. 3. If the issue persists, contact Technical Support. |
Transition to Non-recoverable from less severe
Event code |
0x0236600e |
Message text |
Transition to Non-recoverable from less severe---System detected a power supply failure($1) |
Variable fields |
$1: P12V_STBY |
Severity level |
Critical |
Example |
Transition to Non-recoverable from less severe---System detected a power supply failure(P12V_STBY) |
Impact |
System power-off might occur. |
Cause |
Abnormal board voltage. |
Recommended action |
1. Identify whether the server is powered off. If the server is powered off, re-connect the power cord and identify whether the server can be powered on properly. 2. If the server is not powered off, replace the system board. 3. If the issue persists, contact Technical Support. |
Transition to Non-recoverable from less severe
Event code |
0x0236700e |
Message text |
Transition to Non-recoverable from less severe---System detected a power supply failure($1) |
Variable fields |
$1: P12V |
Severity level |
Critical |
Example |
Transition to Non-recoverable from less severe---System detected a power supply failure(P12V) |
Impact |
System power-off might occur. |
Cause |
Abnormal board voltage. |
Recommended action |
1. Identify whether the server is powered off. If the server is powered off, re-connect the power cord and identify whether the server can be powered on properly. 2. If the server is not powered off, replace the system board. 3. If the issue persists, contact Technical Support. |
Transition to Non-recoverable from less severe
Event code |
0x0236900e |
Message text |
Transition to Non-recoverable from less severe---System detected a power supply failure($1) |
Variable fields |
$1: RISER_P12V_OCP |
Severity level |
Critical |
Example |
Transition to Non-recoverable from less severe---System detected a power supply failure(RISER_P12V_OCP) |
Impact |
System power-off might occur. |
Cause |
Abnormal board voltage. |
Recommended action |
1. Identify whether the server is powered off. If the server is powered off, re-connect the power cord and identify whether the server can be powered on properly. 2. If the server is not powered off, replace the riser card. 3. If the issue persists, replace the system board. 4. If the issue persists, contact Technical Support. |
Transition to Non-recoverable from less severe
Event code |
0x0236a00e |
Message text |
Transition to Non-recoverable from less severe---System detected a power supply failure($1) |
Variable fields |
$1: CPU_DIMM_P12V_OCP |
Severity level |
Critical |
Example |
Transition to Non-recoverable from less severe---System detected a power supply failure(CPU_DIMM_P12V_OCP) |
Impact |
System power-off might occur. |
Cause |
Abnormal board voltage. |
Recommended action |
1. Identify whether the server is powered off. If the server is powered off, re-connect the power cord and identify whether the server can be powered on properly. 2. If power supply is not removed from the server, verify if any DIMM, processor, or system board alarms are present. If a corresponding component is faulty, replace the component. 3. If no component alarms are present, replace the DIMM. 4. If the issue persists, replace the CPU. 5. If the issue persists, replace the system board. 6. If the issue persists, contact Technical Support. |
Transition to Non-recoverable from less severe
Event code |
0x0236b00e |
Message text |
Transition to Non-recoverable from less severe---System detected a power supply failure($1) |
Variable fields |
$1: P12V_BP_FRONT |
Severity level |
Critical |
Example |
Transition to Non-recoverable from less severe---System detected a power supply failure(P12V_BP_FRONT) |
Impact |
System power-off might occur. |
Cause |
Abnormal board voltage. |
Recommended action |
1. Identify whether the server is powered off. If the server is powered off, re-connect the power cord and identify whether the server can be powered on properly. 2. If the server is not powered off, replace the system board. 3. If the issue persists, replace the front backplane. 4. If the issue persists, contact Technical Support. |
Transition to Non-recoverable from less severe
Event code |
0x0236c00e |
Message text |
Transition to Non-recoverable from less severe---System detected a power supply failure($1) |
Variable fields |
$1: P12V_BP_REAR |
Severity level |
Critical |
Example |
Transition to Non-recoverable from less severe---System detected a power supply failure(P12V_BP_REAR) |
Impact |
System power-off might occur. |
Cause |
Abnormal board voltage. |
Recommended action |
1. Identify whether the server is powered off. If the server is powered off, re-connect the power cord and identify whether the server can be powered on properly. 2. If the server is not powered off, replace the system board. 3. If the issue persists, replace the rear backplane. 4. If the issue persists, contact Technical Support. |
Transition to Non-recoverable from less severe
Event code |
0x0236d00e |
Message text |
Transition to Non-recoverable from less severe---System detected a power supply failure($1) |
Variable fields |
$1: P5V_BP |
Severity level |
Critical |
Example |
Transition to Non-recoverable from less severe---System detected a power supply failure(P5V_BP) |
Impact |
System power-off might occur. |
Cause |
Abnormal board voltage. |
Recommended action |
1. Identify whether the server is powered off. If the server is powered off, re-connect the power cord and identify whether the server can be powered on properly. 2. If the server is not powered off, replace the system board. 3. If the issue persists, replace the backplane. 4. If the issue persists, contact Technical Support. |
Transition to Non-recoverable from less severe
Event code |
0x0236e00e |
Message text |
Transition to Non-recoverable from less severe---System detected a power supply failure($1) |
Variable fields |
$1: P12V Overcurrent |
Severity level |
Critical |
Example |
Transition to Non-recoverable from less severe---System detected a power supply failure(P12V Overcurrent) |
Impact |
System power-off might occur. |
Cause |
Abnormal board voltage. |
Recommended action |
1. Identify whether the server is powered off. If the server is powered off, re-connect the power cord and identify whether the server can be powered on properly. 2. If the server is not powered off, replace the fan. 3. If the issue persists, replace the system board. 4. If the issue persists, contact Technical Support. |
Transition to Non-recoverable from less severe
Event code |
0x0237100e |
Message text |
Transition to Non-recoverable from less severe---System detected a power supply failure($1) |
Variable fields |
$1: P12V |
Severity level |
Critical |
Example |
Transition to Non-recoverable from less severe---System detected a power supply failure(P12V) |
Impact |
System power-off might occur. |
Cause |
Abnormal board voltage. |
Recommended action |
1. Identify whether the server is powered off. If the server is powered off, re-connect the power cord and identify whether the server can be powered on properly. 2. If the server is not powered off, replace the riser card. 3. If the issue persists, replace the backplane. 4. If the issue persists, replace the system board. 5. If the issue persists, contact Technical Support. |
Transition to Non-recoverable from less severe
Event code |
0x0237200e |
Message text |
Transition to Non-recoverable from less severe($1) |
Variable fields |
$1: CPU1_THERMTRIP, CPU2_THERMTRIP |
Severity level |
Critical |
Example |
Transition to Non-recoverable from less severe(CPU1_THERMTRIP) |
Impact |
The device gets stuck before this message is generated. Then, the device is powered off and enters the standby mode. |
Cause |
The CPU actively lower its frequency when its actual temperature exceeds the upper limit. If the CPU continues to overheat even after the frequency is lowered, the Thermtrip signal will be triggered and the CPU will stop running. |
Recommended action |
1. Identify whether the server is powered off. If the server is powered off, re-connect the power cord and identify whether the server can be powered on properly. 2. If the server is not powered off, replace the CPU and CPU heatsink. 3. If the issue persists, contact Technical Support. |
Transition to Non-recoverable from less severe
Event code |
0x0237300e |
Message text |
Transition to Non-recoverable from less severe---System detected a power supply failure($1) |
Variable fields |
$1: REAR_4SFF_EFUSE, P12V_BP_REAR |
Severity level |
Critical |
Example |
Transition to Non-recoverable from less severe---System detected a power supply failure(REAR_4SFF_EFUSE) |
Impact |
System power-off might occur. |
Cause |
Abnormal board voltage. |
Recommended action |
1. Identify whether the server is powered off. If the server is powered off, re-connect the power cord and identify whether the server can be powered on properly. 2. If the server is not powered off, replace the system board. 3. If the issue persists, replace the 4SFF backplane. 4. If the issue persists, contact Technical Support. |
Transition to Non-recoverable from less severe
Event code |
0x0237400e |
Message text |
Transition to Non-recoverable from less severe---System detected a power supply failure($1) |
Variable fields |
$1: RISER2_GPU_EFUSE, P12V_SLOT_2_3 |
Severity level |
Critical |
Example |
Transition to Non-recoverable from less severe---System detected a power supply failure(RISER2_GPU_EFUSE) |
Impact |
System power-off might occur. |
Cause |
Abnormal board voltage. |
Recommended action |
1. Identify whether the server is powered off. If the server is powered off, re-connect the power cord and identify whether the server can be powered on properly. 2. If the server is not powered off, replace the system board. 3. If the issue persists, replace the riser card 2. 4. If the issue persists, contact Technical Support. |
Transition to Non-recoverable from less severe
Event code |
0x0237500e |
Message text |
Transition to Non-recoverable from less severe---System detected a power supply failure($1) |
Variable fields |
$1: RISER1_GPU_EFUSE, P12V_SLOT_0_1 |
Severity level |
Critical |
Example |
Transition to Non-recoverable from less severe---System detected a power supply failure(RISER1_GPU_EFUSE) |
Impact |
System power-off might occur. |
Cause |
Abnormal board voltage. |
Recommended action |
1. Identify whether the server is powered off. If the server is powered off, re-connect the power cord and identify whether the server can be powered on properly. 2. If the server is not powered off, replace the system board. 3. If the issue persists, replace the riser card 1. 4. If the issue persists, contact Technical Support. |
Transition to Non-recoverable from less severe
Event code |
0x0237600e |
Message text |
Transition to Non-recoverable from less severe---System detected a power supply failure($1) ---SW CpldReg 0x30:$2, 0x31:$3 |
Variable fields |
$1: SW $2: Value of register 0x30 in SW. $3: Value of register 0x31 in SW. |
Severity level |
Critical |
Example |
Transition to Non-recoverable from less severe---System detected a power supply failure(SW) ---SW CpldReg 0x30:0x01, 0x31:0x40 |
Impact |
System power-off might occur. |
Cause |
Abnormal board voltage. |
Recommended action |
1. Identify whether the server is powered off. If the server is powered off, re-connect the power cord and identify whether the server can be powered on properly. 2. If the server is not powered off, replace the switch card. 3. If the issue persists, contact Technical Support. |
Transition to Non-recoverable from less severe
Event code |
0x0237900e |
Message text |
Transition to Non-recoverable from less severe---System detected a power supply failure($1) |
Variable fields |
$1: UART_ERROR |
Severity level |
Critical |
Example |
Transition to Non-recoverable from less severe---System detected a power supply failure(UART_ERROR) |
Impact |
System power-off might occur. |
Cause |
Abnormal board voltage. |
Recommended action |
1. Identify whether the server is powered off. If the server is powered off, re-connect the power cord and identify whether the server can be powered on properly. 2. If the server is not powered off, replace the system board. 3. If the issue persists, contact Technical Support. |
Transition to Non-recoverable from less severe
Event code |
0x0237c00e |
Message text |
Transition to Non-recoverable from less severe---System detected a power supply failure($1) |
Variable fields |
$1: SWCPLD_ERROR |
Severity level |
Critical |
Example |
Transition to Non-recoverable from less severe---System detected a power supply failure(SWCPLD_ERROR) |
Impact |
System power-off might occur. |
Cause |
Abnormal board voltage. |
Recommended action |
1. Identify whether the server is powered off. If the server is powered off, re-connect the power cord and identify whether the server can be powered on properly. 2. If the server is not powered off, replace the switch card. 3. If the issue persists, contact Technical Support. |
Transition to Non-recoverable from less severe
Event code |
0x0237d00e |
Message text |
Transition to Non-recoverable from less severe---System detected a power supply failure($1) |
Variable fields |
$1: P5V |
Severity level |
Critical |
Example |
Transition to Non-recoverable from less severe---System detected a power supply failure(P5V) |
Impact |
System power-off might occur. |
Cause |
Abnormal board voltage. |
Recommended action |
1. Identify whether the server is powered off. If the server is powered off, re-connect the power cord and identify whether the server can be powered on properly. 2. If the server is not powered off, replace the system board. 3. If the issue persists, replace the BMC card. 4. If the issue persists, replace the rear backplane. 5. If the issue persists, contact Technical Support. |
Transition to Non-recoverable from less severe
Event code |
0x0237a00e |
Message text |
Transition to Non-recoverable from less severe---System detected a power supply failure($1) |
Variable fields |
$1: P12V_STBY |
Severity level |
Critical |
Example |
Transition to Non-recoverable from less severe---System detected a power supply failure(P12V_STBY) |
Impact |
System power-off might occur. |
Cause |
Abnormal board voltage. |
Recommended action |
1. Identify whether the server is powered off. If the server is powered off, re-connect the power cord and identify whether the server can be powered on properly. 2. If the issue persists, replace the power supply. 3. If the issue persists, replace the system board. 4. If the issue persists, contact Technical Support. |
Transition to Non-recoverable from less severe
Event code |
0x0237b00e |
Message text |
Transition to Non-recoverable from less severe---System detected a power supply failure($1) |
Variable fields |
$1: BMCCPLD_ERROR |
Severity level |
Critical |
Example |
Transition to Non-recoverable from less severe---System detected a power supply failure(BMCCPLD_ERROR) |
Impact |
System power-off might occur. |
Cause |
Abnormal board voltage. |
Recommended action |
1. Identify whether the server is powered off. If the server is powered off, re-connect the power cord and identify whether the server can be powered on properly. 2. If the server is not powered off, replace the BMC card. 3. If the issue persists, contact Technical Support. |
Transition to Non-recoverable from less severe
Event code |
0x0237e00e |
Message text |
Transition to Non-recoverable from less severe---System detected a power supply failure($1) |
Variable fields |
$1: RISER_P12V_PWR |
Severity level |
Critical |
Example |
Transition to Non-recoverable from less severe---System detected a power supply failure(RISER_P12V_PWR) |
Impact |
System power-off might occur. |
Cause |
Abnormal board voltage. |
Recommended action |
1. Identify whether the server is powered off. If the server is powered off, re-connect the power cord and identify whether the server can be powered on properly. 2. If the server is not powered off, replace the system board. 3. If the issue persists, replace the riser card. 4. If the issue persists, contact Technical Support. |
Transition to Non-recoverable from less severe
Event code |
0x0237f00e |
Message text |
Transition to Non-recoverable from less severe---System detected a power supply failure($1) |
Variable fields |
$1: PVCCD_HV_CPU1, PVPP_HBM_CPU1, PVCCFA_EHV_CPU1, PVCCFA_EHV_FIVRA_CPU1, PVCCINFAON_CPU1, PVNN_MAIN_CPU1, PVCCIN_CPU1 |
Severity level |
Critical |
Example |
Transition to Non-recoverable from less severe---System detected a power supply failure(PVCCD_HV_CPU1) |
Impact |
System power-off might occur. |
Cause |
Abnormal board voltage. |
Recommended action |
1. Identify whether the server is powered off. If the server is powered off, re-connect the power cord and identify whether the server can be powered on properly. 2. If the server is not powered off, replace the system board. 3. If the issue persists, replace the CPU1. 4. If the issue persists, contact Technical Support. |
Transition to Non-recoverable from less severe
Event code |
0x0238000e |
Message text |
Transition to Non-recoverable from less severe---System detected a power supply failure($1) |
Variable fields |
$1: PVCCD_HV_CPU2,PVPP_HBM_CPU2,PVCCFA_EHV_CPU2,PVCCFA_EHV_FIVRA_CPU2,PVCCINFAON_CPU2,PVNN_MAIN_CPU2,PVCCIN_CPU2 |
Severity level |
Critical |
Example |
Transition to Non-recoverable from less severe---System detected a power supply failure(PVCCD_HV_CPU2) |
Impact |
System power-off might occur. |
Cause |
Abnormal board voltage. |
Recommended action |
1. Identify whether the server is powered off. If the server is powered off, re-connect the power cord and identify whether the server can be powered on properly. 2. If the server is not powered off, replace the system board. 3. If the issue persists, replace the CPU2. 4. If the issue persists, contact Technical Support. |
Transition to Non-recoverable from less severe
Event code |
0x0238100e |
Message text |
Transition to Non-recoverable from less severe---System detected a power supply failure($1) |
Variable fields |
$1: P12V |
Severity level |
Critical |
Example |
Transition to Non-recoverable from less severe---System detected a power supply failure(P12V) |
Impact |
System power-off might occur. |
Cause |
Abnormal board voltage. |
Recommended action |
1. Identify whether the server is powered off. If the server is powered off, re-connect the power cord and identify whether the server can be powered on properly. 2. If the server is not powered off, replace the system board. 3. If the issue persists, contact Technical Support. |
Transition to Non-recoverable from less severe
Event code |
0x0238400e |
Message text |
Transition to Non-recoverable from less severe---System detected a power supply failure($1) |
Variable fields |
$1: FAN_P12V |
Severity level |
Critical |
Example |
Transition to Non-recoverable from less severe---System detected a power supply failure(FAN_P12V) |
Impact |
System power-off might occur. |
Cause |
Abnormal board voltage. |
Recommended action |
1. Identify whether the server is powered off. If the server is powered off, re-connect the power cord and identify whether the server can be powered on properly. 2. If the server is not powered off, replace the fan board. 3. If the issue persists, replace the power board. 4. If the issue persists, replace the fan. 5. If the issue persists, contact Technical Support. |
Transition to Non-recoverable from less severe
Event code |
0x0238500e |
Message text |
Transition to Non-recoverable from less severe---System detected a power supply failure($1) |
Variable fields |
$1: USB_HUB_P1V2_STBY |
Severity level |
Critical |
Example |
Transition to Non-recoverable from less severe---System detected a power supply failure(USB_HUB_P1V2_STBY) |
Impact |
System power-off might occur. |
Cause |
Abnormal board voltage. |
Recommended action |
1. Identify whether the server is powered off. If the server is powered off, re-connect the power cord and identify whether the server can be powered on properly. 2. If the server is not powered off, replace the upper and lower USB ports of the BMC card. 3. If the issue persists, replace the iFIST module. 4. If the issue persists, replace the system board. 5. If the issue persists, replace the internal USB. 6. If the issue persists, contact Technical Support. |
Transition to Non-recoverable from less severe
Event code |
0x0238600e |
Message text |
Transition to Non-recoverable from less severe---System detected a power supply failure($1) |
Variable fields |
$1: DIMM_P12V |
Severity level |
Critical |
Example |
Transition to Non-recoverable from less severe---System detected a power supply failure(DIMM_P12V) |
Impact |
System power-off might occur. |
Cause |
Abnormal board voltage. |
Recommended action |
1. Identify whether the server is powered off. If the server is powered off, re-connect the power cord and identify whether the server can be powered on properly. 2. If the server is not powered off, replace the DIMM. 3. If the issue persists, replace the system board. 4. If the issue persists, contact Technical Support. |
Transition to Non-recoverable from less severe
Event code |
0x0238700e |
Message text |
Transition to Non-recoverable from less severe---System detected a power supply failure($1) |
Variable fields |
$1: CPU_P12V |
Severity level |
Critical |
Example |
Transition to Non-recoverable from less severe---System detected a power supply failure(CPU_P12V) |
Impact |
System power-off might occur. |
Cause |
Abnormal board voltage. |
Recommended action |
1. Identify whether the server is powered off. If the server is powered off, re-connect the power cord and identify whether the server can be powered on properly. 2. If the issue persists, replace the CPU. 3. If the issue persists, replace the system board. 4. If the issue persists, contact Technical Support. |
Transition to Non-recoverable from less severe
Event code |
0x0238800e |
Message text |
Transition to Non-recoverable from less severe---System detected a power supply failure($1) |
Variable fields |
$1: P12V_BP_REAR_GPU |
Severity level |
Critical |
Example |
Transition to Non-recoverable from less severe---System detected a power supply failure(P12V_BP_REAR_GPU) |
Impact |
System power-off might occur. |
Cause |
Abnormal board voltage. |
Recommended action |
1. Identify whether the server is powered off. If the server is powered off, re-connect the power cord and identify whether the server can be powered on properly. 2. If the server is not powered off, replace the power board. 3. If the issue persists, replace the rear GPU. 4. If the issue persists, contact Technical Support. |
Current
Transition to Critical from less severe
Event code |
0x0320000e |
Message text |
Transition to Critical from less severe |
Variable fields |
N/A |
Severity level |
Major |
Example |
Transition to Critical from less severe |
Impact |
Powering off a module affects system operations. |
Cause |
The current of the corresponding component is abnormal. |
Recommended action |
1. Check for any abnormal alarms on the power supply and the system board through the HDM Web alarm page. 2. Make sure the power supply system is functioning properly and the voltage is stable. 3. If the issue persists, contact Technical Support. |
Exceeded the upper minor threshold
Event code |
0x03700002 |
Message text |
Exceeded the upper minor threshold---Current reading:$1---Threshold reading:$2 |
Variable fields |
$1: Current reading of the current sensor. $2: Threshold for triggering a minor current notification. |
Severity level |
Minor |
Example |
Exceeded the upper minor threshold---Current reading:85---Threshold reading:80 |
Impact |
Performance degradation and unstable operation might occur on the device components if the current is too high. |
Cause |
The current of the corresponding component is abnormal. |
Recommended action |
1. Replace the component. 2. If the issue persists, contact Technical Support. |
Exceeded the upper major threshold
Event code |
0x03900002 |
Message text |
Exceeded the upper major threshold---Current reading:$1---Threshold reading:$2 |
Variable fields |
$1: Current reading of the current sensor. $2: Threshold for triggering a major current notification. |
Severity level |
Major |
Example |
Exceeded the upper major threshold---Current reading:90---Threshold reading:88 |
Impact |
Performance degradation and unstable operation might occur on the device components if the current is too high. |
Cause |
Abnormal board current. |
Recommended action |
1. Replace the component. 2. If the issue persists, contact Technical Support. |
Exceeded the upper major threshold
Event code |
0x03920002 |
Message text |
Exceeded the upper major threshold---Current reading:$1---Threshold reading:$2 |
Variable fields |
$1: Current reading of the current sensor. $2: Threshold for triggering a major current notification. |
Severity level |
Major |
Example |
Exceeded the upper major threshold---Current reading:0.50---Threshold reading:0.20 |
Impact |
Memory and system performance degradation might occur. |
Cause |
This alarm is triggered when the current reading of the PMIC for the memory exceeds the major alarm threshold. |
Recommended action |
1. Replace the DIMM. 2. If the issue persists, contact Technical Support. |
Exceeded the upper critical threshold
Event code |
0x03b00002 |
Message text |
Exceeded the upper critical threshold---Current reading:$1---Threshold reading:$2 |
Variable fields |
$1: Current reading of the current sensor. $2: Threshold for triggering a critical current notification. |
Severity level |
Critical |
Example |
Exceeded the upper critical threshold---Current reading:95---Threshold reading:90 |
Impact |
This could potentially cause component damage, leading to a system crash. |
Cause |
Abnormal board current. |
Recommended action |
1. Replace the component. 2. If the issue persists, contact Technical Support. |
Fan
Predictive Failure deasserted
Event code |
0x04000008 |
Message text |
Predictive Failure deasserted |
Variable fields |
N/A |
Severity level |
Info |
Example |
Predictive Failure deasserted |
Impact |
No negative impact. |
Cause |
The status of the power fan has returned to normal. |
Recommended action |
No action is required. |
Predictive Failure asserted
Event code |
0x04000008 |
Message text |
Predictive Failure asserted |
Variable fields |
N/A |
Severity level |
Minor |
Example |
Predictive Failure asserted |
Impact |
Predictive failure. |
Cause |
The state of the power supply fan is abnormal. |
Recommended action |
1. If the power supply fan stops due to foreign objects in the power supply, remove the foreign objects. 2. If the issue persists, Re-install the power supplies, 3. If the issue persists, replace the faulty power supply. 4. If the issue persists, contact Technical Support. |
Transition to Running
Event code |
0x04000014 |
Message text |
Transition to Running |
Variable fields |
N/A |
Severity level |
Info |
Example |
Transition to Running |
Impact |
No negative impact. |
Cause |
The fan is operating correctly. |
Recommended action |
No action is required. |
Transition to Off Line
Event code |
0x04400014 |
Message text |
Transition to Off Line |
Variable fields |
N/A |
Severity level |
Info |
Example |
Transition to Off Line |
Impact |
This affects system heat dissipation and reduces the performance of the system board components. |
Cause |
The fan module has been unplugged or the fan module and the system board have poor contact. |
Recommended action |
1. If the fan has been removed, reinstall the fan as a best practice. 2. Check if the pins of the fan and system board connector are normal. If an abnormality is present, replace the component. Otherwise, reinsert or reattach the fan to ensure proper contact. 3. Replace the fan. 4. If the issue persists, contact Technical Support. |
Transition to Degraded
Event code |
0x04600014 |
Message text |
Transition to Degraded |
Variable fields |
N/A |
Severity level |
Major |
Example |
Transition to Degraded |
Impact |
This affects system heat dissipation and reduces the performance of the system board components. |
Cause |
The fan speed is abnormal. |
Recommended action |
1. Use the HDM Web page to check the fan speed and confirm the cause of the fan failure. If the speed is too low, it may be due to fan aging. If the speed is close to zero, it may be due to the fan being blocked by foreign objects or a fan failure. 2. Verify that the fan is not blocked. 3. Replace the fan. 4. If the issue persists, contact Technical Support. |
Fully Redundant
Event code |
0x04000016 |
Message text |
Fully Redundant |
Variable fields |
N/A |
Severity level |
Info |
Example |
Fully Redundant |
Impact |
No negative impact. |
Cause |
All fan slots are equipped with fans. |
Recommended action |
No action is required. |
Non-redundant:Sufficient Resources from Redundant
Event code |
0x04300016 |
Message text |
Non-redundant:Sufficient Resources from Redundant |
Variable fields |
N/A |
Severity level |
Major |
Example |
Non-redundant:Sufficient Resources from Redundant |
Impact |
This issue does not affect system heat dissipation. |
Cause |
The fan is invalid or is absent. |
Recommended action |
1. If the fan has been removed, reinstall the fan as a best practice. 2. Reinsert or reattach the fan to ensure proper contact. 3. If the fan status sensor reports a malfunction, it means that the fan has failed. Replace the fan. 4. If the issue persists, contact Technical Support. |
Non-redundant:Insufficient Resources
Event code |
0x04500016 |
Message text |
Non-redundant:Insufficient Resources |
Variable fields |
N/A |
Severity level |
Critical |
Example |
Non-redundant:Insufficient Resources |
Impact |
This affects system heat dissipation, causing the system to overheat and automatically shut down. |
Cause |
The fan is invalid or is absent. |
Recommended action |
1. If the fan has been removed, reinstall the fan as a best practice. 2. Reinsert or reattach the fan to ensure proper contact. 3. If the fan status sensor reports a malfunction, it means that the fan has failed. Replace the fan. 4. If the issue persists, contact Technical Support. |
Physical Security
General Chassis Intrusion
Event code |
0x050000de |
Message text |
General Chassis Intrusion |
Variable fields |
N/A |
Severity level |
Minor |
Example |
General Chassis Intrusion |
Impact |
No negative impact. |
Cause |
The chassis access panel is removed. |
Recommended action |
1. Check if the access panel was removed manually. 2. Check if the access panel is installed properly. If necessary, open the access panel and then close it to see if the error log is cleared. 3. Check if the connection between the access-open alarm module and the chassis ear is normal. 4. If the issue persists, contact Technical Support. |
LAN Leash Lost
Event code |
0x054000de |
Message text |
LAN Leash Lost |
Variable fields |
N/A |
Severity level |
Info |
Example |
LAN Leash Lost |
Impact |
No negative impact. |
Cause |
BMC's NCSI channel detects a physical disconnection in the network. |
Recommended action |
1. Check if the network adapter is disabled in the operating system. If it is disabled, no action is required. 2. If the system reports this log during the power on/off phase, it can be ignored. 3. Check if the shared network port cable is properly connected. 4. If the shared network port is not needed, disable it. 5. If the issue persists, contact Technical Support. |
Processor
IERR
Event code |
0x070000de |
Message text |
$1 IERR err---Socket $2 |
Variable fields |
$1: Signal type. Options include MSMI and CATERR. $2: Faulty CPU. |
Severity level |
Critical |
Example |
CATERR IERR err---Socket 1 |
Impact |
It can cause system crash. Then, the system will automatically restart by default. |
Cause |
A CPU internal error was detected. For example, if the Package Control Unit (PCU) encounters an unrecoverable error, this alarm will be triggered. |
Recommended action |
1. Upgrade the BIOS and HDM firmware to the up-to-date version. 2. Process it in conjunction with the specific component event logs reported at the same time as this log. 3. If the issue persists, contact Technical Support. |
MCERR
Event code |
0x070010de |
Message text |
$1 MCERR err---Socket $2 |
Variable fields |
$1: Signal type. Options include MSMI and CATERR. $2: Faulty CPU number. |
Severity level |
Critical |
Example |
CATERR MCERR err---Socket 1 |
Impact |
It can cause system crash. |
Cause |
A CPU internal error was detected. For example, if an uncorrectable error occurs on the memory, this alarm will be triggered. |
Recommended action |
1. Upgrade the BIOS and HDM firmware to the up-to-date version. 2. CPU detects internal error and generates this log. Further check hardware information and sensor pages for errors or disabled components based on the description information. 3. Check for memory, PCIe, and UPI failures using the contextual logs, and perform troubleshooting steps based on the corresponding recommended actions. |
Thermal Trip
Event code |
0x071000de |
Message text |
Thermal Trip |
Variable fields |
N/A |
Severity level |
Critical |
Example |
Thermal Trip |
Impact |
It can cause host power-off. |
Cause |
When the CPU overheats, this event is triggered, which may result in shutdown and poweroff. |
Recommended action |
1. Log in to HDM, and verify that the fan is in normal state. 2. Re-install or replace the fan module with a speed alarm. 3. Identify whether the ambient temperature is too high. Keep the server operating within its normal temperature range. 4. Check for any blockages at the air inlet/outlet and remove any obstructions. 5. Power off the server, check for poor contact of the CPU heatsink, reapply the thermal grease, reinstall the heatsink, and power on the server again. 6. For a liquid-cooled server model, identify whether liquid-cooled component-related alarms have occurred. 7. If the issue persists, contact Technical Support. |
FRB1/BIST failure
Event code |
0x072000de |
Message text |
FRB1/BIST failure. |
Variable fields |
N/A |
Severity level |
Minor |
Example |
FRB1/BIST failure |
Impact |
The operating system might fail to start up and hardware downsizing applies. |
Cause |
This alarm is generated when the CPU self-check detects an error during system startup. |
Recommended action |
1. Power cycle the device. 2. If the issue persists, replace the CPU. 3. If the issue persists, contact Technical Support. |
FRB2/Hang in POST failure
Event code |
0x073000de |
Message text |
FRB2/Hang in POST failure |
Variable fields |
N/A |
Severity level |
Major |
Example |
FRB2/Hang in POST failure |
Impact |
The operating system might fail to start up. |
Cause |
The BIOS startup timed out. |
Recommended action |
1. Upgrade the BIOS. 2. If the issue persists, contact Technical Support. |
FRB3/Processor Startup/Initialization failure
Event code |
0x074000de |
Message text |
FRB3/Processor Startup/Initialization failure |
Variable fields |
N/A |
Severity level |
Minor |
Example |
FRB3/Processor Startup/Initialization failure |
Impact |
The operating system might fail to start up. |
Cause |
The BIOS startup timed out. |
Recommended action |
1. Upgrade the BIOS. 2. If the issue persists, contact Technical Support. |
Configuration Error
Event code |
0x075000de |
Message text |
Configuration Error---$1, ErrorType: $2,Severity: $3, Component: $4, IIO Stack: $5, Location: Socket: $6 or Configuration Error--- ErrorType: $2,Severity: $3, Failed Core: $7, Location: Socket: $6 |
Variable fields |
$1: Time at which the error occurred. It can beCurrent Boot Error or Last Boot Error. $2: Fault type. It can be IIO Internal Error or Spare core Error. $3: Fault severity. $4: Faulty component. $5: I/O number. $6: CPU number. $7: core number. |
Severity level |
Minor |
Example |
Configuration Error---Current Boot Error, ErrorType: IIO Internal Error,Severity:Correctable, Component:VTD, IIO Stack: 1, Location: Socket: 1 |
Impact |
The operating system might fail to start up. |
Cause |
The main system CPU detected internal correctable error information during operation. |
Recommended action |
This log is generated when correctable internal errors are detected during server operation, such as IIO internal errors or CPU core errors. No action is required for correctable internal errors. |
Processor Presence detected
Event code |
0x077000df |
Message text |
Processor Presence detected |
Variable fields |
N/A |
Severity level |
Info/Critical |
Example |
Processor Presence detected |
Impact |
If the primary CPU is not in place, it may result in system startup failure. |
Cause |
This event log is triggered when the primary CPU is not in place or installed incorrectly. |
Recommended action |
1. Verify that the primary CPU is installed correctly. 2. If the primary CPU fails, replace the CPU. 3. If the issue persists, contact Technical Support. |
Processor Automatically Throttled
Event code |
0x07a000de |
Message text |
Processor Automatically Throttled---due to fan error |
Variable fields |
N/A |
Severity level |
Minor |
Example |
Processor Automatically Throttled---due to fan error |
Impact |
System performance decreases due to CPU throttling. |
Cause |
The CPU throttles due to fan failure. |
Recommended action |
1. Log in to HDM, and verify that the fans are running correctly. 2. Verify that the air conditioner in the equipment room is running correctly. |
Processor Automatically Throttled
Event code |
0x07a010de |
Message text |
Processor Automatically Throttled---prochot |
Variable fields |
N/A |
Severity level |
Minor |
Example |
Processor Automatically Throttled---prochot |
Impact |
System performance decreases due to CPU throttling. |
Cause |
CPU throttling might occur due to CPU overheating. |
Recommended action |
1. Log in to HDM, and verify that the fan is in normal state. 2. Re-install or replace the fan module with a speed alarm. 3. Identify whether the ambient temperature is too high. Keep the server operating within its normal temperature range. 4. Check for any blockages at the air inlet/outlet and remove any obstructions. 5. Power off the server, check for poor contact of the CPU heatsink, reapply the thermal grease, reinstall the heatsink, and power on the server again. 6. For a liquid-cooled server model, identify whether liquid-cooled component-related alarms have occurred. 7. If the issue persists, contact Technical Support. |
Processor Automatically Throttled
Event code |
0x07a020de |
Message text |
Processor Automatically Throttled---memhot |
Variable fields |
N/A |
Severity level |
Minor |
Example |
Processor Automatically Throttled---memhot |
Impact |
System performance decreases due to CPU throttling. |
Cause |
CPU throttling may occur due to memory overheating. |
Recommended action |
1. Log in to HDM, and verify that the fan is in normal state. 2. Re-install or replace the fan module with a speed alarm. 3. Identify whether the ambient temperature is too high. Keep the server operating within its normal temperature range. 4. Check for any blockages at the air inlet/outlet and remove any obstructions. 5. For a liquid-cooled server model, identify whether liquid-cooled component-related alarms have occurred. 6. If the issue persists, contact Technical Support. |
Machine Check Exception
Event code |
0x07b000de |
Message text |
Machine Check Exception---$1---$2---Location: Socket:$3 |
Variable fields |
$1: Fault type. $2: Specifies if the error occurred during the current boot or the previous boot. $3: Faulty CPU. |
Severity level |
Critical |
Example |
Machine Check Exception---PIE---Last Boot Error---Location: Socket:1 |
Impact |
The system might stop responding. |
Cause |
Only in AMD models, when the CPU generates an uncorrectable error, this event will be triggered. |
Recommended action |
1. Check if any corresponding faults exist in the operating system. 2. Check the CPU microcode to identify whether to upgrade the microcode. 3. Upgrade the BIOS and BMC to the latest versions. 4. If the issue persists, contact Technical Support. |
Triggered a uncorrectable error
Event code |
0x07b201de |
Message text |
CPU $1 triggered a uncorrectable error. |
Variable fields |
$1: CPU number. |
Severity level |
Critical |
Example |
CPU 1 triggered a uncorrectable error. |
Impact |
The system might stop responding. |
Cause |
Triggering IERR or MCERR errors, the diagnosis result of HDM is CPU uncorrectable error. |
Recommended action |
1. Upgrade the BIOS and HDM firmware to the up-to-date version. 2. Safely power off the server and replace the CPU to identify whether the alarm disappears. 3. If the issue persists, contact Technical Support. |
Machine Check Exception
Event code |
0x07b100de |
Message text |
Machine Check Exception---HBM error---Location: Socket:$1 |
Variable fields |
$1: CPU number. |
Severity level |
Critical |
Example |
Machine Check Exception---HBM error---Location: Socket:1 |
Impact |
The system might stop responding. |
Cause |
HBM failed. |
Recommended action |
1. Check if there are any corresponding faults in the operating system. 2. Check the CPU microcode and upgrade the BIOS and BMC to the latest versions. 3. Safely power off the server and replace the CPU to identify whether the alarm disappears. 4. If the issue persists, contact Technical Support. |
Triggered a correctable error
Event code |
0x07c201de |
Message text |
CPU $1 triggered a correctable error. |
Variable fields |
$1: CPU number. |
Severity level |
Minor |
Example |
CPU 1 triggered a correctable error. |
Impact |
No negative impact. |
Cause |
Triggering IERR or MCERR errors, the diagnosis result of HDM is CPU correctable error. |
Recommended action |
No action is required. |
Correctable Machine Check Error
Event code |
0x07c000de |
Message text |
Correctable Machine Check Error---$1---$2---Location: Socket:$3 |
Variable fields |
$1: Fault type. $2: Specifies if the error occurred during the current boot or the previous boot. $3: Faulty CPU. |
Severity level |
Minor |
Example |
Correctable Machine Check Error---PIE---Current Boot Error---Location: Socket:1 |
Impact |
No negative impact. |
Cause |
This alarm is generated only in AMD models when correctable errors such as TWIX, WAFL, or SMU occur. |
Recommended action |
No action is required. |
Correctable Machine Check Error
Event code |
0x07c100de |
Message text |
Correctable Machine Check Error---HBM error---Location: Socket:$1 |
Variable fields |
$1: CPU number. |
Severity level |
Minor |
Example |
Correctable Machine Check Error---HBM error---Location: Socket:1 |
Impact |
No negative impact. |
Cause |
An correctable error was detected on HBM. |
Recommended action |
No action is required. |
Machine Check Exception
Event code |
0x07b001de |
Message text |
Machine Check Exception---$1, Bank: $2,Severity:$3, Error Info:$4, Location: Socket: $5 |
Variable fields |
$1: Specifies if the error occurred during the current boot or the previous boot. $2: Fault bank. $3: Fault severity. $4: Fault information. $5: CPU number. |
Severity level |
Critical |
Example |
Machine Check Exception---Current Boot Error, Bank: IFU,Severity:FATAL, Error Info:Cache, Location: Socket: 1 |
Impact |
The system might stop responding. |
Cause |
This event occurs when there is an internal fault in the CPU. |
Recommended action |
1. Check if there are any corresponding faults present in the operating system. 2. Check the CPU microcode and upgrade the BIOS and HDM to the latest versions. 3. If the issue persists, preliminarily determine the range of the fault based on the bank location and check if any other warning logs have been generated. 4. Power off the server safely and replace the CPU or peripheral with a known working one to see if the warning disappears. 5. Replace the system board. |
Correctable Machine Check Error
Event code |
0x07c001de |
Message text |
Correctable Machine Check Error---$1, Bank: $2,Severity:$3, Error Info:$4, Location: Socket: $5 |
Variable fields |
$1: Specifies if the error occurred during the current boot or the previous boot. $2: Fault bank. $3: Fault severity. $4: Fault information. $5: CPU number. |
Severity level |
Minor |
Example |
Correctable Machine Check Error---Current Boot Error, Bank: IFU,Severity:Corrected, Error Info:Cache, Location: Socket: 1 |
Impact |
No negative impact. |
Cause |
An internal correctable error occurred in the CPU. |
Recommended action |
No action is required. |
Power Supply
Presence detected
Event code |
0x080000de |
Message text |
Presence detected |
Variable fields |
N/A |
Severity level |
Info |
Example |
Presence detected |
Impact |
No negative impact. |
Cause |
When the power supply is detected as being inserted, this event is triggered, indicating a transition from the power supply not being in place to being in place. When the power supply is detected as being removed, this event is cleared, indicating a transition from the power supply being in place to not being in place. |
Recommended action |
If the power supply is removed, install the power supply again. |
Power Supply Failure detected
Event code |
0x081000de |
Message text |
Power Supply Failure detected |
Variable fields |
N/A |
Severity level |
Major |
Example |
Power Supply Failure detected |
Impact |
It affects system power supply and may result in abnormal system power-off. |
Cause |
A power supply fault was detected. |
Recommended action |
1. Re-install the power supply. 2. If the issue persists, replace the power supply. 3. If the issue persists, contact Technical Support. |
Power Supply Predictive Failure
Event code |
0x082000de |
Message text |
Power Supply Predictive Failure |
Variable fields |
N/A |
Severity level |
Minor |
Example |
Power Supply Predictive Failure |
Impact |
The power supply may have malfunctions that affect system power supply. |
Cause |
A power supply fault was detected. |
Recommended action |
1. Identify whether any foreign objects have obstructed and stop the power supply fan. If yes, remove the foreign objects. 2. If the issue persists, re-install the power supply. 3. If the issue persists, replace the power supply. 4. If the issue persists, contact Technical Support. |
Power Supply input lost (AC/DC)
Event code |
0x083000de |
Message text |
Power Supply input lost (AC/DC) |
Variable fields |
N/A |
Severity level |
Major |
Example |
Power Supply input lost (AC/DC) |
Impact |
It may cause the server to power off abnormally. |
Cause |
The AC power cable of the power supply is unplugged or there is an abnormal AC input. |
Recommended action |
1. Verify that the power input is normal. 2. Verify that all power cables are undamaged and properly connected. 3. Verify that all power supplies are correctly installed. 4. If the issue persists, contact Technical Support. |
Power Supply input lost or out-of-range
Event code |
0x084000de |
Message text |
Power Supply input lost or out-of-range |
Variable fields |
N/A |
Severity level |
Major |
Example |
Power Supply input lost or out-of-range |
Impact |
This may cause the server to power off abnormally. |
Cause |
The input voltage of the power supply exceeded the rated range. |
Recommended action |
1. Verify that the power input is normal. 2. Verify that all power cables are undamaged and properly connected. 3. Verify that all power supplies are correctly installed. 4. If the issue persists, contact Technical Support. |
Power Supply input out-of-range - but present
Event code |
0x085000de |
Message text |
Power Supply input out-of-range - but present |
Variable fields |
N/A |
Severity level |
Major |
Example |
Power Supply input out-of-range - but present |
Impact |
Abnormal power input beyond the supported range may cause the server to power off. |
Cause |
The input voltage of the power supply is too high. |
Recommended action |
1. Check if the input voltage of the power supply is normal. 2. Verify that the power cables and power supplies are installed correctly. 3. Unplug and re-plug the power supply to ensure a good power connection. 4. Check if the fans of the power supply are spinning. 5. If the issue persists, contact Technical Support. |
Configuration error ---Vendor mismatch
Event code |
0x086000de |
Message text |
Configuration error ---Vendor mismatch |
Variable fields |
N/A |
Severity level |
Minor |
Example |
Configuration error ---Vendor mismatch |
Impact |
An unknown risk exists due to non-original certified components. |
Cause |
Non-original certified power supplies are installed. |
Recommended action |
Install original certified power supplies. |
Configuration error---Power Supply rating mismatch
Event code |
0x086030de |
Message text |
Configuration error --- Power Supply rating mismatch |
Variable fields |
N/A |
Severity level |
Minor |
Example |
Configuration error --- Power Supply rating mismatch |
Impact |
This may result in unstable power supply and abnormal system shutdown. |
Cause |
Original certified power supplies are installed, but the models of the two power supplies do not match. |
Recommended action |
1. Make sure all the power supplies are of the same model. 2. If the issue persists, contact Technical Support. |
Configuration error---Power supply rating mismatch
Event code |
0x086200de |
Message text |
Configuration error---Power supply rating mismatch:PSU$1,POUT:$2W |
Variable fields |
$1: PSU ID, which can be 1 or 2. $2: Output power of the power supply. |
Severity level |
Minor |
Example |
Configuration error---Power supply rating mismatch:PSU1,POUT:2000W |
Impact |
This may result in unstable power supply and abnormal system shutdown. |
Cause |
The rated power of the installed power supplies may be inconsistent. |
Recommended action |
1. Make sure all the power supplies are of the same model. 2. If the issue persists, contact Technical Support. |
Power Supply Inactive/standby state
Event code |
0x087000de |
Message text |
Power Supply Inactive/standby state |
Variable fields |
N/A |
Severity level |
Info |
Example |
Power Supply Inactive/standby state |
Impact |
No negative impact. |
Cause |
The power supply exits cold standby mode. When the function of standby power supply is enabled, if the current device is running at a high power, the standby power supply will automatically exit cold backup mode and provide power to the device. |
Recommended action |
No action is required. |
PSU failure detected by CPLD
Event code |
0x088000de |
Message text |
PSU failure detected by CPLD |
Variable fields |
N/A |
Severity level |
Critical |
Example |
PSU failure detected by CPLD |
Impact |
This may result in unstable power supply and abnormal system shutdown. |
Cause |
The server has experienced an AC power failure. |
Recommended action |
1. Check for environmental issues such as high temperature or abnormal power supply fan. 2. Replug the power supply and check if the alarm disappears. 3. If the issue persists, replace the power supply. |
Redundancy Lost
Event code |
0x08100016 |
Message text |
Redundancy Lost |
Variable fields |
N/A |
Severity level |
Major |
Example |
Redundancy Lost |
Impact |
Power redundancy failure reduces the reliability of device power supply. |
Cause |
Power redundancy got lost. |
Recommended action |
1. Check if the power supply environment is normal. 2. Check if any power supply has been removed. 3. Check for poor contact between power supplies and power cables. 4. Check for power-related fault alarm logs to determine if it is a power failure. 5. If the issue persists, contact Technical Support. |
Power Unit
Power limit is exceeded over correction time limit
Event code |
0x095010de |
Message text |
Power limit is exceeded over correction time limit---$1 Current Power: $2W. |
Variable fields |
$1: GPU/Not available for chassis power consumption $2: Current power value. |
Severity level |
Minor |
Example |
GPU: Power limit is exceeded over correction time limit---GPU Current Power: 2000W Chassis: Power limit is exceeded over correction time limit---Current Power: 2000W |
Impact |
Power capping failed and the corresponding policy will be executed. |
Cause |
Power capping triggers this alarm after a certain amount of time elapsed when the power output exceeds the limit. |
Recommended action |
1. Adjust the power capping threshold or adjust the GPU workload. 2. If the issue persists, contact Technical Support. |
Cooling Device
Transition to OK
Event code |
0x0a00000e |
Message text |
Transition to OK |
Variable fields |
N/A |
Severity level |
Info |
Example |
Transition to OK |
Impact |
No negative impact. |
Cause |
The liquid-cooled module is in place and free of faults. |
Recommended action |
No action is required. |
Transition to Non-recoverable---Liquid leakage occurred
Event code |
0x0a60000e |
Message text |
Transition to Non-recoverable---Liquid leakage occurred |
Variable fields |
N/A |
Severity level |
Critical |
Example |
Transition to Non-recoverable---Liquid leakage occurred |
Impact |
For the server model that supports only processor liquid-cooled module, processor heal dissipation is affected. For the server model that supports processor liquid-cooled module and GPU liquid-cooled module, processor or GPU heat dissipation is affected. |
Cause |
This message is generated when liquid leakage occurs. |
Recommended action |
1. Check if the liquid cooling device is functioning properly or if there is any liquid leakage. 2. Replace the liquid-cooled module. |
Transition to Non-recoverable from less severe
Event code |
0x0a30000e |
Message text |
Transition to Non-recoverable from less severe--- Liquid Cooler not present |
Variable fields |
N/A |
Severity level |
Minor |
Example |
Transition to Non-recoverable from less severe--- Liquid Cooler not present |
Impact |
Heat dissipation of the components in the liquid-cooled device on which the alarm is present is affected. |
Cause |
In a server that supports multiple liquid-cooled devices, one liquid-cooled device is not present (or the corresponding liquid leakage detection cable is not plugged in). |
Recommended action |
1. Examine if the liquid leakage detection cable of the liquid-cooled device is loose. If it is loose, remove the AC power and reconnect the liquid leakage detection cable. 2. If the issue persists, contact Technical Support. |
Transition to Non-Critical from OK--- Liquid leakage detection cable is disconnected
Event code |
0x0a10000e |
Message text |
Transition to Non-Critical from OK--- Liquid leakage detection cable is disconnected |
Variable fields |
N/A |
Severity level |
Major |
Example |
Transition to Non-Critical from OK--- Liquid leakage detection cable is disconnected |
Impact |
Unable to detect coolant leakage. |
Cause |
Liquid leakage sensor cannot be detected. |
Recommended action |
1. Check if the liquid cooling device is present. 2. Check if the liquid leakage sensor is installed correctly. 3. Replace the liquid-cooled module. |
Other Units-based Sensor
Exceeded the upper minor threshold
Event code |
0x0b700002 |
Message text |
Exceeded the upper minor threshold---Current reading:$1---Threshold reading:$2 |
Variable fields |
$1: Current power value. $2: Threshold for triggering a minor power notification. |
Severity level |
Minor |
Example |
Exceeded the upper minor threshold---Current reading:20---Threshold reading:18 |
Impact |
Exceeding the maximum power limit will cause the system to shut down. |
Cause |
The power exceeds the limit. |
Recommended action |
1. Log in to HDM, and verify that the threshold value is appropriate. 2. Check if the total power consumption of the server is too high through the HDM web page. 3. Check if the total power consumption of the power supply meets the service requirements. 4. If the issue persists, contact Technical Support. |
Memory
Correctable ECC or other correctable memory error
Event code |
0x0c0000de |
Message text |
Correctable ECC or other correctable memory error--$1-Location:CPU:$2 CH:$3 DIMM:$4 $5 |
Variable fields |
$1: Time at which the error occurred, Current Boot Error or Last Boot Error. $2: CPU number. $3: Channel number. $4: DIMM number. $5: DIMM mark. |
Severity level |
Minor |
Example |
Correctable ECC or other correctable memory error---Current Boot Error-Location:CPU:1 CH:1 DIMM:0 A1 |
Impact |
No negative impact. |
Cause |
Correctable memory errors. |
Recommended action |
No action is required. |
Correctable ECC or other correctable memory error
Event code |
0x0c0020de |
Message text |
Correctable ECC or other correctable memory error---$1---Location:CPU:$2 CH:$3 DIMM:$4 |
Variable fields |
$1: Fault type, which can be ECC, Parity, CRC, or Other $2: CPU number. $3: Channel number. $4: DIMM number. |
Severity level |
Minor |
Example |
Correctable ECC or other correctable memory error---CRC---Location:CPU:1 CH:1 DIMM:0 |
Impact |
No negative impact. |
Cause |
A correctable error occurred on the memory. |
Recommended action |
No action is required. |
Correctable ECC or other correctable memory error
Event code |
0x0c0600de |
Message text |
Correctable ECC or other correctable memory error---$1---$2---Location:CPU$2 CH:$3 DIMM:$4 |
Variable fields |
$1: Fault type, which can be ECC, Parity, or CRC. $2: Specifies if the error occurred during the current boot or the previous boot. It can be Current Boot Error or Last Boot Error. $3: CPU number. $4: Channel number. $5: DIMM number. |
Severity level |
Minor |
Example |
Correctable ECC or other correctable memory error---ECC---Current Boot Error---Location:CPU1 CH:8 DIMM:0 |
Impact |
No negative impact. |
Cause |
A correctable error occurred on the memory. |
Recommended action |
No action is required. |
CPU triggered a correctable error
Event code |
0x0c0500de |
Message text |
CPU $1 $2 triggered a correctable error |
Variable fields |
$1: CPU number. $2: DIMM mark. |
Severity level |
Minor |
Example |
CPU 1 A0 triggered a correctable error |
Impact |
No negative impact. |
Cause |
Triggering IERR or MCERR errors, the HDM diagnostic result shows correctable errors in memory. |
Recommended action |
No action is required. |
Uncorrectable ECC or other uncorrectable memory error
Event code |
0x0c1000de |
Message text |
Uncorrectable ECC or other uncorrectable memory error--$1-Location:CPU:$2 CH:$3 DIMM:$4 $5 |
Variable fields |
$1: Specifies if the error occurred during the current boot or the previous boot. It can be Current Boot Error or Last Boot Error. $2: CPU number. $3: Channel number. $4: DIMM number. $5: DIMM mark. |
Severity level |
Major |
Example |
Uncorrectable ECC or other uncorrectable memory error---Current Boot Error-Location:CPU:1 MEM CTRL:1 CH:1 DIMM:0 A1 |
Impact |
It can cause the system to stop sending responses, unless the memory is in certain RAS modes, such as mirror or MCA recovery. |
Cause |
A non-correctable (multiple bit flip) ECC error has occurred. |
Recommended action |
1. Verify that the temperature and humidity are appropriate. 2. Clean the memory slots and memory contacts, ensuring that there are no foreign objects in the memory slots and the contacts are not contaminated. Then, reinstall the corresponding DIMM. 3. Replace the DIMM. 4. If the issue persists, contact Technical Support. |
Uncorrectable ECC or other uncorrectable memory error
Event code |
0x0c1020de |
Message text |
Uncorrectable ECC or other uncorrectable memory error--$1-Location:CPU:$2 CH:$3 DIMM:$4 |
Variable fields |
$1: Specifies if the error occurred during the current boot or the previous boot. It can be Current Boot Error or Last Boot Error. $2: CPU number. $3: Channel number. $4: DIMM number. |
Severity level |
Major |
Example |
Uncorrectable ECC or other uncorrectable memory error---Current Boot Error-Location:CPU:1 MEM CTRL:1 CH:1 DIMM:0 A1 |
Impact |
It can cause the system to stop sending responses. |
Cause |
An uncorrectable (multiple bit flip) ECC error has occurred. |
Recommended action |
1. Verify that the temperature and humidity are appropriate. 2. Clean the memory slots and memory contacts, ensuring that there are no foreign objects in the memory slots and the contacts are not contaminated. Then, reinstall the corresponding DIMM. 3. Replace the DIMM. 4. If the issue persists, contact Technical Support. |
Triggered an uncorrectable error
Event code |
0x0c1500de |
Message text |
CPU$1 $2 triggered an uncorrectable error |
Variable fields |
$1: CPU number. $2: DIMM mark. |
Severity level |
Major |
Example |
CPU1 A0 triggered an uncorrectable error |
Impact |
The system might restart or stop responding. |
Cause |
Triggering IERR or MCERR errors, the BMC diagnostic result shows uncorrectable errors in memory. |
Recommended action |
1. Verify that the temperature and humidity are appropriate. 2. Clean the memory slots and memory contacts, ensuring that there are no foreign objects in the memory slots and the contacts are not contaminated. Then, reinstall the corresponding DIMM. 3. If the issue persists, replace the DIMM. 4. If the issue persists, contact Technical Support. |
Uncorrectable ECC or other uncorrectable memory error
Event code |
0x0c1600de |
Message text |
Uncorrectable ECC or other uncorrectable memory error---$1---$2---Location:CPU$3 CH:$4 DIMM:$5 |
Variable fields |
$1: Fault type, which can be ECC, Parity, or CRC. $2: Startup time upon error occurrence. It can be Current Boot Error or Last Boot Error. $3: CPU number. $4: Channel number. $5: DIMM number. |
Severity level |
Major |
Example |
Uncorrectable ECC or other uncorrectable memory error---ECC---Last Boot Error---Location:CPU1 CH:8 DIMM:0 |
Impact |
The system might restart or stop responding. |
Cause |
Uncorrectable ECC or other uncorrectable errors occur. |
Recommended action |
1. Verify that the temperature and humidity are appropriate. 2. Clean the memory slots and memory contacts, ensuring that there are no foreign objects in the memory slots and the contacts are not contaminated. Then, reinstall the corresponding DIMM. 3. If the issue persists, replace the DIMM. 4. If the issue persists, contact Technical Support. |
Parity
Event code |
0x0c2000de |
Message text |
Parity ---$1---Location: Location:CPU:$2 CH:$3 DIMM:$4 $5 |
Variable fields |
$1: Specifies if the error occurred during the current boot or the previous boot. It can be Current Boot Error or Last Boot Error. $2: CPU number. $3: Channel number. $4: DIMM number. $5: DIMM mark. |
Severity level |
Minor |
Example |
Parity---Current Boot Error-Location:CPU:1 CH:1 DIMM:0 A0 |
Impact |
No negative impact. |
Cause |
This error message is generated when there is a failure in data parity on the command/address lines while reading the memory cell data, resulting in abnormal data access to the memory. |
Recommended action |
No action is required. |
Parity
Event code |
0x0c2020de |
Message text |
Parity---Location:CPU:$1 CH:$2 DIMM:$3 |
Variable fields |
$1: CPU number. $2: Channel number. $3: DIMM number. |
Severity level |
Minor |
Example |
Parity---Location:CPU:1 CH:1 DIMM:0 |
Impact |
No negative impact. |
Cause |
This message is generated when there is a failure in data parity on the command/address lines while reading the memory cell data, resulting in abnormal data access to the memory. The SEL records the command/address parity error and logs the accessed DIMM. |
Recommended action |
No action is required. |
Parity---An uncorrectable error occurs during the memory test phase
Event code |
0x0c20b1c4 |
Message text |
Parity---An uncorrectable error occurs during the memory test phase---Location:CPU:$1 CH:$2 DIMM:$3 Rank:$4 |
Variable fields |
$1: CPU number. $2: Channel number. $3: DIMM mark. $4: Rank number. |
Severity level |
Minor |
Example |
Parity---An uncorrectable error occurs during the memory test phase---Location:CPU:1 CH:1 DIMM:A1 Rank:0 |
Impact |
System performance degradation might occur. |
Cause |
An UCE occurred in the memtest phase. |
Recommended action |
1. Verify that the temperature and humidity are appropriate. 2. Clean the memory slots and memory contacts, ensuring that there are no foreign objects in the memory slots and the contacts are not contaminated. Then, reinstall the corresponding DIMM. 3. If the issue persists, replace the DIMM. 4. If the issue persists, contact Technical Support. |
Parity---The memory interleaving configuration cannot meet the requirements of the server
Event code |
0x0c20e014 |
Message text |
Parity---The memory interleaving configuration cannot meet the requirements of the server---Location:CPU:$1 CH:$2 DIMM:$3 Rank:$4 |
Variable fields |
$1: CPU number. $2: Channel number. $3: DIMM mark. $4: Rank number. |
Severity level |
Minor |
Example |
Parity---The memory interleaving configuration cannot meet the requirements of the server---Location:CPU:1 CH:1 DIMM:A1 Rank:0 |
Impact |
System performance degradation might occur. |
Cause |
Configuration error. Memory interleave configuration does not meet the requirements of the server. |
Recommended action |
Contact Technical Support. |
Parity---The memory interleaving configuration cannot meet the requirements of the server
Event code |
0x0c20e024 |
Message text |
Parity---The memory interleaving configuration cannot meet the requirements of the server---Location:CPU:$1 CH:$2 DIMM:$3 Rank:$4 |
Variable fields |
$1: CPU number. $2: Channel number. $3: DIMM mark. $4: Rank number. |
Severity level |
Minor |
Example |
Parity---The memory interleaving configuration cannot meet the requirements of the server---Location:CPU:1 CH:1 DIMM:A1 Rank:0 |
Impact |
System performance degradation might occur. |
Cause |
Configuration error. Memory interleave configuration does not meet the requirements of the server. |
Recommended action |
Contact Technical Support. |
Parity---The memory interleaving configuration cannot meet the requirements of the server
Event code |
0x0c20e0e4 |
Message text |
Parity---The memory interleaving configuration cannot meet the requirements of the server---Location:CPU:$1 CH:$2 DIMM:$3 Rank:$4 |
Variable fields |
$1: CPU number. $2: Channel number. $3: DIMM mark. $4: Rank number. |
Severity level |
Minor |
Example |
Parity---The memory interleaving configuration cannot meet the requirements of the server---Location:CPU:1 CH:1 DIMM:A1 Rank:0 |
Impact |
System performance degradation or system startup failure might occur. |
Cause |
Configuration error. Memory interleave configuration does not meet the requirements of the server. |
Recommended action |
Contact Technical Support. |
Parity---CMD eye width is too small
Event code |
0x0c226014 |
Message text |
Parity---CMD eye width is too small---Location:CPU:$1 CH:$2 DIMM:$3 Rank:$4 |
Variable fields |
$1: CPU number. $2: Channel number. $3: DIMM mark. $4: Rank number. |
Severity level |
Minor |
Example |
Parity---CMD eye width is too small---Location:CPU:1 CH:2 DIMM:A0 Rank:0 |
Impact |
System performance degradation or system startup failure might occur. |
Cause |
Memory parity error. CMD eye width is too small. |
Recommended action |
1. Confirm the memory slot according to the alarm information. 2. Check if there are foreign objects on the memory gold finger and memory slot and clean them. 3. If the issue persists, replace the DIMM. 4. If the issue persists, contact Technical Support. |
Parity---CmdPiGroup: No Eye width
Event code |
0x0c226024 |
Message text |
Parity---CmdPiGroup: No Eye width---Location:CPU:$1 CH:$2 DIMM:$3 Rank:$4 |
Variable fields |
$1: CPU number. $2: Channel number. $3: DIMM mark. $4: Rank number. |
Severity level |
Minor |
Example |
Parity---CmdPiGroup: No Eye width---Location:CPU:1 CH:2 DIMM:A0 Rank:0 |
Impact |
System performance degradation might occur. |
Cause |
CMD eye width does not exist. |
Recommended action |
1. Confirm the memory slot according to the alarm information. 2. Check if there are foreign objects on the memory gold finger and memory slot and clean them. 3. If the issue persists, replace the DIMM. 4. If the issue persists, contact Technical Support. |
Parity---The command is not in the FNv table
Event code |
0x0c228004 |
Message text |
Parity---The command is not in the FNv table---Location:CPU:$1 CH:$2 DIMM:$3 Rank:$4 |
Variable fields |
$1: CPU number. $2: Channel number. $3: DIMM mark. $4: Rank number. |
Severity level |
Minor |
Example |
Parity---The command is not in the FNv table---Location:CPU:1 CH:2 DIMM:A0 Rank:0 |
Impact |
System performance degradation might occur. |
Cause |
The command sent is not in the FNv table. |
Recommended action |
Contact Technical Support. |
Parity---Memory read DqDqs training failed
Event code |
0x0c231134 |
Message text |
Parity---Memory read DqDqs training failed---Location:CPU:$1 CH:$2 DIMM:$3 Rank:$4 |
Variable fields |
$1: CPU number. $2: Channel number. $3: DIMM mark. $4: Rank number. |
Severity level |
Minor |
Example |
Parity---Memory read DqDqs training failed---Location:CPU:1 CH:2 DIMM:A0 Rank:0 |
Impact |
System performance degradation might occur. |
Cause |
Memory read Dq or Dqs training failed. |
Recommended action |
1. Replace the DIMM. 2. If the issue persists, contact Technical Support. |
Parity---Memory Receive Enable Training Error
Event code |
0x0c231144 |
Message text |
Parity---Memory Receive Enable Training Error---Location:CPU:$1 CH:$2 DIMM:$3 Rank:$4 |
Variable fields |
$1: CPU number. $2: Channel number. $3: DIMM mark. $4: Rank number. |
Severity level |
Minor |
Example |
Parity---Memory Receive Enable Training Error---Location:CPU:1 CH:1 DIMM:A1 Rank:0 |
Impact |
System performance degradation might occur. |
Cause |
Memory Faulty Parts Tracking failure. The Receive Enable signal of the memory fails to train to the corresponding timing. |
Recommended action |
1. Replace the DIMM. 2. If the issue persists, contact Technical Support. |
Parity---Memory write DqDqs training failed
Event code |
0x0c231164 |
Message text |
Parity---Memory write DqDqs training failed---Location:CPU:$1 CH:$2 DIMM:$3 Rank:$4 |
Variable fields |
$1: CPU number. $2: Channel number. $3: DIMM mark. $4: Rank number. |
Severity level |
Minor |
Example |
Parity---Memory write DqDqs training failed---Location:CPU:1 CH:2 DIMM:A0 Rank:0 |
Impact |
System performance degradation might occur. |
Cause |
Memory read Dq or Dqs training failed. |
Recommended action |
1. Replace the DIMM. 2. If the issue persists, contact Technical Support. |
Parity---An error occurs during memory test, and the rank is disabled
Event code |
0x0c2311c4 |
Message text |
Parity---An error occurs during memory test, and the rank is disabled---Location:CPU:$1 CH:$2 DIMM:$3 Rank:$4 |
Variable fields |
$1: CPU number. $2: Channel number. $3: DIMM mark. $4: Rank number. |
Severity level |
Minor |
Example |
Parity---An error occurs during memory test, and the rank is disabled---Location:CPU:1 CH:1 DIMM:A1 Rank:0 |
Impact |
System performance degradation might occur. |
Cause |
An error occurred during memory testing, and that rank has been disabled. |
Recommended action |
1. Replace the DIMM. 2. If the issue persists, contact Technical Support. |
Parity---LRDIMM RCVEN training failed
Event code |
0x0c231264 |
Message text |
Parity---LRDIMM RCVEN training failed---Location:CPU:$1 CH:$2 DIMM:$3 Rank:$4 |
Variable fields |
$1: CPU number. $2: Channel number. $3: DIMM mark. $4: Rank number. |
Severity level |
Minor |
Example |
Parity---LRDIMM RCVEN training failed---Location:CPU:1 CH:2 DIMM:A0 Rank:0 |
Impact |
System performance degradation might occur. |
Cause |
LRDIMM RCVEN training failed. |
Recommended action |
1. Replace the DIMM. 2. If the issue persists, contact Technical Support. |
Parity---Read delay training failed
Event code |
0x0c231284 |
Message text |
Parity---Read delay training failed---Location:CPU:$1 CH:$2 DIMM:$3 Rank:$4 |
Variable fields |
$1: CPU number. $2: Channel number. $3: DIMM mark. $4: Rank number. |
Severity level |
Minor |
Example |
Parity---Read delay training failed---Location:CPU:1 CH:2 DIMM:A0 Rank:0 |
Impact |
System performance degradation might occur. |
Cause |
Read delay training has failed. |
Recommended action |
1. Replace the DIMM. 2. If the issue persists, contact Technical Support. |
Parity---Write delay training failed
Event code |
0x0c2312b4 |
Message text |
Parity---Write delay training failed---Location:CPU:$1 CH:$2 DIMM:$3 Rank:$4 |
Variable fields |
$1: CPU number. $2: Channel number. $3: DIMM mark. $4: Rank number. |
Severity level |
Minor |
Example |
Parity---Write delay training failed---Location:CPU:1 CH:2 DIMM:A0 Rank:0 |
Impact |
System performance degradation might occur. |
Cause |
Write delay training failed. |
Recommended action |
1. Replace the DIMM. 2. If the issue persists, contact Technical Support. |
Parity---Mapped out because failed critical mask test at cold boot
Event code |
0x0c28c024 |
Message text |
Parity---Mapped out because failed critical mask test at cold boot---Location:CPU:$1 CH:$2 DIMM:$3 Rank:$4 |
Variable fields |
$1: CPU number. $2: Channel number. $3: DIMM mark. $4: Rank number. |
Severity level |
Minor |
Example |
Parity---Mapped out because failed critical mask test at cold boot---Location:CPU:1 CH:2 DIMM:A0 Rank:0 |
Impact |
System performance degradation or system startup failure might occur. |
Cause |
The DIMM failed in key mask test and mapped out as a failed area during cold boot. |
Recommended action |
1. Replace the DIMM. 2. If the issue persists, contact Technical Support. |
Parity---Invalid SPD contents
Event code |
0x0c2ed094 |
Message text |
Parity---Invalid SPD contents---Location:CPU:$1 CH:$2 DIMM:$3 Rank:$4 |
Variable fields |
$1: CPU number. $2: Channel number. $3: DIMM mark. $4: Rank number. |
Severity level |
Minor |
Example |
Parity---Invalid SPD contents---Location:CPU:1 CH:2 DIMM:A0 Rank:0 |
Impact |
System performance degradation might occur. |
Cause |
Invalid SPD content. |
Recommended action |
1. Replace the DIMM. 2. If the issue persists, contact Technical Support. |
Parity---The DCPMM memory modules of the unexpected model are installed
Event code |
0x0c2ed0c4 |
Message text |
Parity---The DCPMM memory modules of the unexpected model are installed---Location:CPU:$1 CH:$2 DIMM:$3 Rank:$4 |
Variable fields |
$1: CPU number. $2: Channel number. $3: DIMM mark. $4: Rank number. |
Severity level |
Minor |
Example |
Parity---The DCPMM memory modules of the unexpected model are installed---Location:CPU:1 CH:2 DIMM:A0 Rank:0 |
Impact |
System performance degradation might occur. |
Cause |
Unsupported CDPMMs are inserted. |
Recommended action |
1. Based on the alarm type, confirm the specifications of the DCPMM and replace the DCPMM memory. 2. If the issue persists, contact Technical Support. |
Parity---Failed to set the VDD voltage of the DIMM
Event code |
0x0c2f0014 |
Message text |
Parity---Failed to set the VDD voltage of the DIMM---Location:CPU:$1 CH:$2 DIMM:$3 Rank:$4 |
Variable fields |
$1: CPU number. $2: Channel number. $3: DIMM mark. $4: Rank number. |
Severity level |
Minor |
Example |
Parity---Failed to set the VDD voltage of the DIMM---Location:CPU:1 CH:2 DIMM:A0 Rank:0 |
Impact |
System performance degradation might occur. |
Cause |
Software data structure abnormality. |
Recommended action |
1. Replace the DIMM. 2. If the issue persists, replace the system board. 3. If the issue persists, contact Technical Support. |
Parity---Delay exceeded
Event code |
0x0c214024 |
Message text |
Parity---Delay exceeded---Location:CPU:$1 CH:$2 DIMM:$3 Rank:$4 |
Variable fields |
$1: CPU number. $2: Channel number. $3: DIMM mark. $4: Rank number. |
Severity level |
Minor |
Example |
Parity---Delay exceeded---Location:CPU:1 CH:1 DIMM:A1 Rank:0 |
Impact |
System performance degradation might occur. |
Cause |
The program execution timed out. |
Recommended action |
1. Replace the DIMM. 2. If the issue persists, contact Technical Support. |
Parity---Timing error occurred during signal line adjustment for memory write leveling training
Event code |
0x0c215014 |
Message text |
Parity---Timing error occurred during signal line adjustment for memory write leveling training---Location:CPU:$1 CH:$2 DIMM:$3 Rank:$4 |
Variable fields |
$1: CPU number. $2: Channel number. $3: DIMM mark. $4: Rank number. |
Severity level |
Minor |
Example |
Parity---Timing error occurred during signal line adjustment for memory write leveling training---Location:CPU:1 CH:1 DIMM:A1 Rank:0 |
Impact |
System performance degradation might occur. |
Cause |
Timing abnormality occurs to write leveling adjustment signal line. |
Recommended action |
1. Replace the DIMM. 2. If the issue persists, contact Technical Support. |
Parity---CS is not consistent with clock in timing, and the channel is isolated
Event code |
0x0c229044 |
Message text |
Parity---CS is not consistent with clock in timing, and the channel is isolated---Location:CPU:$1 CH:$2 DIMM:$3 Rank:$4 |
Variable fields |
$1: CPU number. $2: Channel number. $3: DIMM mark. $4: Rank number. |
Severity level |
Minor |
Example |
Parity---CS is not consistent with clock in timing, and the channel is isolated---Location:CPU:1 CH:2 DIMM:A0 Rank:0 |
Impact |
System performance degradation might occur. |
Cause |
A timing mismatch occurred between CS and clock. |
Recommended action |
1. Replace the DIMM. 2. If the issue persists, contact Technical Support. |
Parity---CA is not consistent with clock in timing, and the channel is isolated
Event code |
0x0c229054 |
Message text |
Parity---CA is not consistent with clock in timing, and the channel is isolated---Location:CPU:$1 CH:$2 DIMM:$3 Rank:$4 |
Variable fields |
$1: CPU number. $2: Channel number. $3: DIMM mark. $4: Rank number. |
Severity level |
Minor |
Example |
Parity---CA is not consistent with clock in timing, and the channel is isolated---Location:CPU:1 CH:2 DIMM:A0 Rank:0 |
Impact |
System performance degradation might occur. |
Cause |
A timing mismatch might occur between CA and clock. |
Recommended action |
1. Replace the DIMM. 2. If the issue persists, contact Technical Support. |
Parity---LRDIMM external coarse training failed
Event code |
0x0c231204 |
Message text |
Parity---LRDIMM external coarse training failed---Location:CPU:$1 CH:$2 DIMM:$3 Rank:$4 |
Variable fields |
$1: CPU number. $2: Channel number. $3: DIMM mark. $4: Rank number. |
Severity level |
Minor |
Example |
Parity---LRDIMM external coarse training failed---Location:CPU:1 CH:2 DIMM:A0 Rank:0 |
Impact |
System performance degradation might occur. |
Cause |
LRDIMM external fine training failed. |
Recommended action |
1. Replace the DIMM. 2. If the issue persists, contact Technical Support. |
Parity---LRDIMM external fine training failed
Event code |
0x0c231214 |
Message text |
Parity---LRDIMM external fine training failed---Location:CPU:$1 CH:$2 DIMM:$3 Rank:$4 |
Variable fields |
$1: CPU number. $2: Channel number. $3: DIMM mark. $4: Rank number. |
Severity level |
Minor |
Example |
Parity---LRDIMM external fine training failed---Location:CPU:1 CH:2 DIMM:A0 Rank:0 |
Impact |
System performance degradation might occur. |
Cause |
LRDIMM external fine training failed. |
Recommended action |
1. Replace the DIMM. 2. If the issue persists, contact Technical Support. |
Parity---LRDIMM internal coarse training failed
Event code |
0x0c231224 |
Message text |
Parity---LRDIMM internal coarse training failed---Location:CPU:$1 CH:$2 DIMM:$3 Rank:$4 |
Variable fields |
$1: CPU number. $2: Channel number. $3: DIMM mark. $4: Rank number. |
Severity level |
Minor |
Example |
Parity---LRDIMM internal coarse training failed---Location:CPU:1 CH:2 DIMM:A0 Rank:0 |
Impact |
System performance degradation might occur. |
Cause |
LRDIMM internal coarse training failed. |
Recommended action |
1. Replace the DIMM. 2. If the issue persists, contact Technical Support. |
Parity---LRDIMM internal fine training failed
Event code |
0x0c231234 |
Message text |
Parity---LRDIMM internal fine training failed---Location:CPU:$1 CH:$2 DIMM:$3 Rank:$4 |
Variable fields |
$1: CPU number. $2: Channel number. $3: DIMM number. $4: DIMM mark. |
Severity level |
Minor |
Example |
Parity---LRDIMM internal fine training failed---Location:CPU:1 CH:2 DIMM:A0 Rank:0 |
Impact |
System performance degradation or system startup failure might occur. |
Cause |
LRDIMM internal fine training failed. |
Recommended action |
1. Replace the DIMM. 2. If the issue persists, contact Technical Support. |
Memory Device Disabled---The Rank is disabled
Event code |
0x0c40a034 |
Message text |
Memory Device Disabled---The rank is disabled---Location:CPU:$1 CH:$2 DIMM:$3 Rank:$4 |
Variable fields |
$1: CPU number. $2: Channel number. $3: DIMM number. $4: DIMM mark. |
Severity level |
Minor |
Example |
Memory Device Disabled---The rank is disabled---Location:CPU:2 CH:1 DIMM:B1 Rank:1 |
Impact |
System performance degradation might occur. This does not affect normal use of the system. |
Cause |
One rank of the memory is disabled, but it does not affect the use of the remaining ranks. |
Recommended action |
1. Replace the DIMM. 2. If the issue persists, contact Technical Support. |
Memory Device Disabled---The DIMM is disabled
Event code |
0x0c40a044 |
Message text |
Memory Device Disabled---The DIMM is disabled---Location:CPU:$1 CH:$2 DIMM:$3 Rank:$4 |
Variable fields |
$1: CPU number. $2: Channel number. $3: DIMM number. $4: DIMM mark. |
Severity level |
Minor |
Example |
Memory Device Disabled---The DIMM is disabled---Location:CPU:1 CH:1 DIMM:0 Rank:0 |
Impact |
System performance degradation might occur. |
Cause |
The DIMM is disabled. |
Recommended action |
1. Replace the DIMM. 2. If the issue persists, contact Technical Support. |
Memory Device Disabled
Event code |
0x0c4000de |
Message text |
Memory Device Disabled--$1---Location:CPU:$2 CH:$3 DIMM:$4 $5 |
Variable fields |
$1: Specifies if the error occurred during the current boot or the previous boot. It can be Current Boot Error or Last Boot Error. $2: CPU number. $3: Channel number. $4: DIMM number. $5: DIMM mark. |
Severity level |
Major |
Example |
Memory Device Disabled---Current Boot Error---Location:CPU:1 CH:1 DIMM:0 A1 |
Impact |
The DIMM is disabled. System performance degradation might occur. |
Cause |
A memory fault is detected during the system startup process. |
Recommended action |
1. Replace the DIMM. 2. If the issue persists, contact Technical Support. |
Memory Device Disabled
Event code |
0x0c4020de |
Message text |
Memory Device Disabled---Location:CPU:$2 CH:$3 DIMM:$4 |
Variable fields |
$1: CPU number. $2: Channel number. $3: DIMM number. |
Severity level |
Major |
Example |
Memory Device Disabled ---Location:CPU:1 CH:1 DIMM:0 |
Impact |
The DIMM is disabled. System performance degradation might occur. |
Cause |
A memory fault is detected during the system startup process. |
Recommended action |
1. Replace the DIMM. 2. If the issue persists, contact Technical Support. |
Correctable ECC or other memory error limit reached
Event code |
0x0c5000de |
Message text |
Correctable ECC or other memory error limit reached--$1---Location:CPU:$2 CH:$3 DIMM:$4 $5 |
Variable fields |
$1: Specifies if the error occurred during the current boot or the previous boot. It can be Current Boot Error or Last Boot Error. $2: CPU number. $3: Channel number. $4: DIMM number. $5: DIMM mark. |
Severity level |
Minor |
Example |
Correctable ECC or other memory error limit reached---Current Boot Error---Location:CPU:1 CH:1 DIMM:0 A1 |
Impact |
The system might restart or stop responding. |
Cause |
The memory may not be installed correctly or there could be an internal memory failure. The correctable errors in the memory have reached the set threshold, and when the corresponding Memory RAS mode is enabled, the corresponding RAS features will be executed without causing a system crash. Even in the memory repair mode, the errors still exceed the threshold. |
Recommended action |
1. Reinstall the corresponding DIMM to ensure correct installation, clean the gold fingers, make sure no foreign objects exist in the memory slot, and that the temperature and humidity in the environment are normal. 2. Check the memory funnel threshold in the BIOS. If it is too low, adjust the funnel threshold value in the BIOS. 3. If the issue persists, contact Technical Support. |
Correctable ECC or other memory error limit reached
Event code |
0x0c5020de |
Message text |
Correctable ECC or other correctable memory error logging limit reached---$1 $2:$3---Location:CPU:$4 CH:$5 DIMM:$6 |
Variable fields |
$1: MCA/UMC(Available in case of CE Count Overflow) $2: CE Count Overflow/Memory CE Storm Threshold/Memory CE Accumulation Threshold $3: Threshold. $4: CPU number. $5: Channel number. $6: DIMM number. |
Severity level |
Minor |
Example |
Correctable ECC or other correctable memory error logging limit reached---MCA CE Count Overflow:8769---Location:CPU:1 CH:5 DIMM:0 |
Impact |
The system might restart or stop responding. |
Cause |
The memory may not be installed correctly or there could be an internal memory failure. The correctable errors in the memory have reached the set threshold and will not cause a system crash. Even in the memory repair mode, the errors still exceed the threshold. |
Recommended action |
1. Reinstall the corresponding DIMM. Make sure it is installed correctly, the gold contacts are not contaminated, no foreign objects exist in the memory slot, and the environmental temperature and humidity are normal. 2. Check whether the memory funnel threshold in the BIOS is too low. If so, adjust the funnel threshold value in the BIOS. 3. If the issue persists, contact Technical Support. |
Presence detected
Event code |
0x0c6000de |
Message text |
Presence detected |
Variable fields |
N/A |
Severity level |
Info |
Example |
Presence detected |
Impact |
No negative impact. |
Cause |
A DIMM is detected present. |
Recommended action |
No action is required. |
Memory patrol scrub CE occurred
Event code |
0x0c3010de |
Message text |
Memory patrol scrub CE occurred---$1---Location: Location:CPU:$2 CH:$3 DIMM:$4 $5 |
Variable fields |
$1: Specifies if the error occurred during the current boot or the previous boot. It can be Current Boot Error or Last Boot Error. $2: CPU number. $3: Channel number. $4: DIMM number. $5: DIMM mark. |
Severity level |
Minor |
Example |
Memory patrol scrub CE occurred---Current Boot Error---Location:CPU:1 CH:1 DIMM:0 A0 |
Impact |
Check failed for reading memory data. No negative impact. |
Cause |
CE Inspection. This error message indicates that there was a data parity error during the read operation of a memory cell. The error occurred on the command/address lines, resulting in abnormal data retrieval from the memory. The error is recorded in the SEL, along with the DIMM that was accessed during the error. |
Recommended action |
No action is required. |
Memory patrol scrub UCE occurred and degraded to CE
Event code |
0x0c3020de |
Message text |
Memory patrol scrub UCE occurred and degraded to CE---$1---Location: Location:CPU:$2 CH:$3 DIMM:$4 $5 |
Variable fields |
$1: Specifies if the error occurred during the current boot or the previous boot. It can be Current Boot Error or Last Boot Error. $2: CPU number. $3: Channel number. $4: DIMM number. $5: DIMM mark. |
Severity level |
Minor |
Example |
Memory patrol scrub UCE occurred and degraded to CE---Current Boot Error---Location:CPU:1 CH:1 DIMM:0 A0 |
Impact |
Check failed for reading memory data. No negative impact. |
Cause |
UCE Inspection: Degraded CE. This error message indicates that there was a data parity error during the read operation of a memory cell. The error occurred on the command/address lines, resulting in abnormal data retrieval from the memory. The error is recorded in the SEL, along with the DIMM that was accessed during the error. |
Recommended action |
No action is required. |
Configuration error---RDIMMs are installed on the server that supports only UDIMMs
Event code |
0x0c701014 |
Message text |
Configuration error---RDIMMs are installed on the server that supports only UDIMMs---Location:CPU:$1 CH:$2 DIMM:$3 Rank:$4 |
Variable fields |
$1: CPU number. $2: Channel number. $3: DIMM mark. $4: Rank number. |
Severity level |
Minor |
Example |
Configuration error---RDIMMs are installed on the server that supports only UDIMMs-Location:CPU:1 CH:1 DIMM:A1 Rank:0 |
Impact |
The system might restart or stop responding. |
Cause |
An RDIMM was inserted into a CPU platform that only supports UDIMM. |
Recommended action |
1. Replace the DIMM. 2. If the issue persists, contact Technical Support. |
Configuration error---UDIMMs are installed on the server that supports only RDIMMs
Event code |
0x0c702014 |
Message text |
Configuration error---UDIMMs are installed on the server that supports only RDIMMs---Location:CPU:$1 CH:$2 DIMM:$3 Rank:$4 |
Variable fields |
$1: CPU number. $2: Channel number. $3: DIMM mark. $4: Rank number. |
Severity level |
Minor |
Example |
Configuration error---UDIMMs are installed on the server that supports only RDIMMs---Location:CPU:1 CH:1 DIMM:A1 Rank:0 |
Impact |
The system might restart or stop responding. |
Cause |
An UDIMM was inserted into a CPU platform that only supports RDIMM. |
Recommended action |
1. Replace the DIMM. 2. If the issue persists, contact Technical Support. |
Configuration error---SODIMMs are installed on the server that supports only RDIMMs
Event code |
0x0c703014 |
Message text |
Configuration error---SODIMMs are installed on the server that supports only RDIMMs-Location:CPU:$1 CH:$2 DIMM:$3 Rank:$4 |
Variable fields |
$1: CPU number. $2: Channel number. $3: DIMM mark. $4: Rank number. |
Severity level |
Minor |
Example |
Configuration error---SODIMMs are installed on the server that supports only RDIMMs-Location:CPU:1 CH:1 DIMM:A1 Rank:0 |
Impact |
The system might restart or stop responding. |
Cause |
An SODIMM was inserted into a platform that only supports RDIMM. |
Recommended action |
1. Replace the DIMM. 2. If the issue persists, contact Technical Support. |
Configuration error---The number of ranks per channel can be only 1, 2, or 4
Event code |
0x0c707024 |
Message text |
Configuration error---The number of ranks per channel can be only 1, 2, or 4---Location:CPU:$1 CH:$2 DIMM:$3 Rank:$4 |
Variable fields |
$1: CPU number. $2: Channel number. $3: DIMM mark. $4: Rank number. |
Severity level |
Minor |
Example |
Configuration error---The number of ranks per channel can be only 1, 2, or 4---Location:CPU:1 CH:1 DIMM:A1 Rank:0 |
Impact |
The system might restart or stop responding. |
Cause |
The number of ranks in the memory does not meet the requirements of the CPU platform. The current CPU platform supports a maximum of 4 ranks of memory. |
Recommended action |
1. Replace the DIMM. 2. If the issue persists, contact Technical Support. |
Configuration error---Columns, rows, or banks of the DIMM cannot meet the JEDEC standards, and LRDIMMs are not supported
Event code |
0x0c707044 |
Message text |
Configuration error---Columns, rows, or banks of the DIMM cannot meet the JEDEC standards, and LRDIMMs are not supported---Location:CPU:$1 CH:$2 DIMM:$3 Rank:$4 |
Variable fields |
$1: CPU number. $2: Channel number. $3: DIMM mark. $4: Rank number. |
Severity level |
Minor |
Example |
Configuration error---Columns, rows, or banks of the DIMM cannot meet the JEDEC standards, and LRDIMMs are not supported---Location:CPU:1 CH:1 DIMM:A1 Rank:0 |
Impact |
The system might restart or stop responding. |
Cause |
Unsupported memory type: · The memory design (COL, Row, Bank) does not comply with JEDEC standard design. · The LRDIMM is not on the server's supported list. |
Recommended action |
1. Replace the DIMM. 2. If the issue persists, contact Technical Support. |
Configuration error---The number of ranks in the channel exceeds 8
Event code |
0x0c707054 |
Message text |
Configuration error---The number of ranks in the channel exceeds 8---Location:CPU:$1 CH:$2 DIMM:$3 Rank:$4 |
Variable fields |
$1: CPU number. $2: Channel number. $3: DIMM mark. $4: Rank number. |
Severity level |
Minor |
Example |
Configuration error---The number of ranks in the channel exceeds 8---Location:CPU:1 CH:1 DIMM:A1 Rank:0 |
Impact |
The system might restart or stop responding. |
Cause |
The total number of ranks of all memory in the channel exceeds the maximum supported number of ranks (8). |
Recommended action |
1. Replace the DIMM. 2. If the issue persists, contact Technical Support. |
Configuration error---Support for ECC on the DIMMs is not consistent with support for ECC on the server
Event code |
0x0c707094 |
Message text |
Configuration error---Support for ECC on the DIMMs is not consistent with support for ECC on the server---Location:CPU:$1 CH:$2 DIMM:$3 Rank:$4 |
Variable fields |
$1: CPU number. $2: Channel number. $3: DIMM mark. $4: Rank number. |
Severity level |
Minor |
Example |
Configuration error---Support for ECC on the DIMMs is not consistent with support for ECC on the server---Location:CPU:1 CH:1 DIMM:A1 Rank:0 |
Impact |
The system might restart or stop responding. |
Cause |
The ECC support for the server's memory is inconsistent. |
Recommended action |
1. Replace the DIMM. 2. If the issue persists, contact Technical Support. |
Configuration error---The voltage for a DDR4 DIMM must be 12V, and the voltage for a DDR5 DIMM must be 11V
Event code |
0x0c7070a4 |
Message text |
Configuration error---The voltage for a DDR4 DIMM must be 12V, and the voltage for a DDR5 DIMM must be 11V---Location:CPU:$1 CH:$2 DIMM:$3 Rank:$4 |
Variable fields |
$1: CPU number. $2: Channel number. $3: DIMM mark. $4: Rank number. |
Severity level |
Minor |
Example |
Configuration error---The voltage for a DDR4 DIMM must be 12V, and the voltage for a DDR5 DIMM must be 11V---Location:CPU:1 CH:1 DIMM:A1 Rank:0 |
Impact |
The system might restart or stop responding. |
Cause |
The current voltage does not meet the supported voltage of the memory. · DDR4 memory supports a voltage of 12V. · DDR5 memory supports a voltage of 11V. |
Recommended action |
1. Replace the DIMM. 2. If the issue persists, contact Technical Support. |
Configuration error---The CPU is not compatible with 3DS DIMMs
Event code |
0x0c707104 |
Message text |
Configuration error---The CPU is not compatible with 3DS DIMMs---Location:CPU:$1 CH:$2 DIMM:$3 Rank:$4 |
Variable fields |
$1: CPU number. $2: Channel number. $3: DIMM mark. $4: Rank number. |
Severity level |
Minor |
Example |
Configuration error---The CPU is not compatible with 3DS DIMMs-Location:CPU:1 CH:1 DIMM:A1 Rank:0 |
Impact |
The system might restart or stop responding. |
Cause |
The current CPU does not support memory with 3DS packaging. |
Recommended action |
1. Replace the DIMM. 2. If the issue persists, contact Technical Support. |
Configuration error---NVDIMMs with stepping lower than 0x10 are not supported
Event code |
0x0c707114 |
Message text |
Configuration error---NVDIMMs with stepping lower than 0x10 are not supported---Location:CPU:$1 CH:$2 DIMM:$3 Rank:$4 |
Variable fields |
$1: CPU number. $2: Channel number. $3: DIMM mark. $4: Rank number. |
Severity level |
Minor |
Example |
Configuration error---NVDIMMs with stepping lower than 0x10 are not supported---Location:CPU:1 CH:1 DIMM:A1 Rank:0 |
Impact |
The system might restart or stop responding. |
Cause |
Configuration error. NVDIMMs with a step value lower than 16 are not supported. |
Recommended action |
1. Replace the DIMM. 2. If the issue persists, contact Technical Support. |
Configuration error---The CPU is not compatible with the DIMMs
Event code |
0x0c707144 |
Message text |
Configuration error---The CPU is not compatible with the DIMMs---Location:CPU:$1 CH:$2 DIMM:$3 Rank:$4 |
Variable fields |
$1: CPU number. $2: Channel number. $3: DIMM mark. $4: Rank number. |
Severity level |
Minor |
Example |
Configuration error---The CPU is not compatible with the DIMMs---Location:CPU:1 CH:1 DIMM:A1 Rank:0 |
Impact |
The system might restart or stop responding. |
Cause |
Configuration error: CPU and DIMM are not compatible. |
Recommended action |
Contact Technical Support. |
Configuration error---The frequency of the DIMM is not supported on the server
Event code |
0x0c707154 |
Message text |
Configuration error---The frequency of the DIMM is not supported on the server---Location:CPU:$1 CH:$2 DIMM:$3 Rank:$4 |
Variable fields |
$1: CPU number. $2: Channel number. $3: DIMM mark. $4: Rank number. |
Severity level |
Minor |
Example |
Configuration error---The frequency of the DIMM is not supported on the server---Location:CPU:1 CH:1 DIMM:A1 Rank:0 |
Impact |
The system might restart or stop responding. |
Cause |
The current platform configuration does not support the frequency of the memory module. |
Recommended action |
1. The current configuration does not support the memory frequency settings. Confirm whether the Enforce Population POR/Enforce DDR Memory Frequency POR option in the Setup menu is enabled and whether the supported frequency of the memory module is within the supported range. 2. If the issue persists, contact Technical Support. |
Configuration error---24Gb or higher Capacity DRAMs not supported with this CPU
Event code |
0x0c7071f4 |
Message text |
Configuration error---24Gb or higher Capacity DRAMs not supported with this CPU---Location:CPU:$1 CH:$2 DIMM:$3 Rank:$4 |
Variable fields |
$1: CPU number. $2: Channel number. $3: DIMM mark. $4: Rank number. |
Severity level |
Minor |
Example |
Configuration error---24Gb or higher Capacity DRAMs not supported with this CPU---Location:CPU:1 CH:1 DIMM:A1 Rank:0 |
Impact |
The system might restart or stop responding. |
Cause |
The CPU does not support memory modules with a capacity of 24GB or above. |
Recommended action |
1. The current CPU does not support memory modules with a capacity of 24GB or above. Check the error message for the corresponding DIMM and replace the DIMM with a supported capacity. 2. If the issue persists, contact Technical Support. |
Configuration error---The CPU is not compatible with LRDIMMs
Event code |
0x0c707214 |
Message text |
Configuration error---The CPU is not compatible with LRDIMMs---Location:CPU:$1 CH:$2 DIMM:$3 Rank:$4 |
Variable fields |
$1: CPU number. $2: Channel number. $3: DIMM mark. $4: Rank number. |
Severity level |
Minor |
Example |
Configuration error---The CPU is not compatible with LRDIMMs---Location:CPU:1 CH:1 DIMM:A1 Rank:0 |
Impact |
The system might restart or stop responding. |
Cause |
The CPU does not support LRDIMMs. |
Recommended action |
1. Replace the DIMM. 2. If the issue persists, contact Technical Support. |
Configuration error--- DCPMM + HBM config is not supported. Disable DCPMM populated channel
Event code |
0x0c707224 |
Message text |
Configuration error--- DCPMM + HBM config is not supported. Disable DCPMM populated channel---Location:CPU:$1 CH:$2 DIMM:$3 Rank:$4 |
Variable fields |
$1: CPU number. $2: Channel number. $3: DIMM mark. $4: Rank number. |
Severity level |
Minor |
Example |
Configuration error--- DCPMM + HBM config is not supported. Disable DCPMM populated channel---Location:CPU:1 CH:1 DIMM:A1 Rank:0 |
Impact |
The system might restart or stop responding. |
Cause |
DCPMM and HBM cannot coexist. The channel for DCPMM detected by memory installation check must be disabled. |
Recommended action |
1. Remove the DCPMM. 2. If the issue persists, contact Technical Support. |
Configuration error--- Failed to enable the lockstep mode The memory RAS mode has degraded to independent
Event code |
0x0c709014 |
Message text |
Configuration error--- Failed to enable the lockstep mode The memory RAS mode has degraded to independent ---Location:CPU:$1 CH:$2 DIMM:$3 Rank:$4 |
Variable fields |
$1: CPU number. $2: Channel number. $3: DIMM mark. $4: Rank number. |
Severity level |
Minor |
Example |
Configuration error---Failed to enable the lockstep mode The memory RAS mode has degraded to independent---Location:CPU:1 CH:1 DIMM:A1 Rank:0 |
Impact |
The system might restart or stop responding. |
Cause |
The memory configuration cannot enable Lockstep mode. It will be downgraded to independent mode. |
Recommended action |
1. Lockstep configuration has been downgraded. Check if the memory installation satisfies Lockstep mode. 2. If the issue persists, contact Technical Support. |
Configuration error---Failed to enable the full mirror mode
Event code |
0x0c70c014 |
Message text |
Configuration error---Failed to enable the full mirror mode---Location:CPU:$1 CH:$2 DIMM:$3 Rank:$4 |
Variable fields |
$1: CPU number. $2: Channel number. $3: DIMM mark. $4: Rank number. |
Severity level |
Minor |
Example |
Configuration error---Failed to enable the full mirror mode---Location:CPU:1 CH:1 DIMM:A1 Rank:0 |
Impact |
The system might restart or stop responding. |
Cause |
Enabling Full Mirror RAS mode for memory has failed. The Mirror configuration will be downgraded. |
Recommended action |
1. Mirror configuration has been downgraded. Check if the memory installation satisfies mirror mode. 2. If the issue persists, contact Technical Support. |
Configuration error---Failed to enable the partial mirror mode The memory RAS mode degraded to independent
Event code |
0x0c70d014 |
Message text |
Configuration error--- Failed to enable the partial mirror mode The memory RAS mode degraded to independent---Location:CPU:$1 CH:$2 DIMM:$3 Rank:$4 |
Variable fields |
$1: CPU number. $2: Channel number. $3: DIMM mark. $4: Rank number. |
Severity level |
Minor |
Example |
Configuration error--- Failed to enable the partial mirror mode The memory RAS mode degraded to independent---Location:CPU:1 CH:1 DIMM:A1 Rank:0 |
Impact |
The system might restart or stop responding. |
Cause |
Unable to start partial mirror mode. The system is switched to Independent channel mode. |
Recommended action |
1. Partial mirror configuration has been downgraded. Check if the memory installation satisfies Partial mirror mode. 2. If the issue persists, contact Technical Support. |
Configuration error---The memory interleaving configuration cannot meet the requirements of the server
Event code |
0x0c70e034 |
Message text |
Configuration error---The memory interleaving configuration cannot meet the requirements of the server---Location:CPU:$1 CH:$2 DIMM:$3 Rank:$4 |
Variable fields |
$1: CPU number. $2: Channel number. $3: DIMM mark. $4: Rank number. |
Severity level |
Minor |
Example |
Configuration error---The memory interleaving configuration cannot meet the requirements of the server---Location:CPU:1 CH:1 DIMM:A1 Rank:0 |
Impact |
The system might restart or stop responding. |
Cause |
Memory configuration error. The memory interleaving configuration does not meet the requirements of the server. |
Recommended action |
1. Check the memory interleaving configuration in the setup (NUMA and interleaving). 2. If the issue persists, contact Technical Support. |
Configuration error---Failed to enable the rank sparing mode The memory RAS mode has degraded to independent
Event code |
0x0c710014 |
Message text |
Configuration error---Failed to enable the rank sparing mode The memory RAS mode has degraded to independent---Location:CPU:$1 CH:$2 DIMM:$3 Rank:$4 |
Variable fields |
$1: CPU number. $2: Channel number. $3: DIMM mark. $4: Rank number. |
Severity level |
Minor |
Example |
Configuration error---Failed to enable the rank sparing mode The memory RAS mode has degraded to independent---Location:CPU:1 CH:1 DIMM:A1 Rank:0 |
Impact |
The system might restart or stop responding. |
Cause |
Rank Sparing mode cannot be enabled. The memory RAS mode has been downgraded to independent mode. |
Recommended action |
1. The Sparing configuration has been downgraded. Check if the memory installation satisfies the Sparing mode. 2. If the issue persists, contact Technical Support. |
Configuration error---Failed to enable patrol scrubbing
Event code |
0x0c711004 |
Message text |
Configuration error---Failed to enable patrol scrubbing---Location:CPU:$1 CH:$2 DIMM:$3 Rank:$4 |
Variable fields |
$1: CPU number. $2: Channel number. $3: DIMM mark. $4: Rank number. |
Severity level |
Minor |
Example |
Configuration error---Failed to enable patrol scrubbing---Location:CPU:1 CH:1 DIMM:A1 Rank:0 |
Impact |
The system might restart or stop responding. |
Cause |
Memory patrol/scrubbing cannot be enabled. |
Recommended action |
1. Enabling patrol scrub has failed. Check the RAS (Reliability, Availability, Serviceability) features supported by the CPU specifications. 2. If the issue persists, contact Technical Support. |
Configuration error---The number of ranks in the black slot is greater than that in the white slot, or the DIMM is installed in the black slot with the white slot empty
Event code |
0x0c717014 |
Message text |
Configuration error---The number of ranks in the black slot is greater than that in the white slot, or the DIMM is installed in the black slot with the white slot empty---Location:CPU:$1 CH:$2 DIMM:$3 Rank:$4 |
Variable fields |
$1: CPU number. $2: Channel number. $3: DIMM mark. $4: Rank number. |
Severity level |
Minor |
Example |
Configuration error---The number of ranks in the black slot is greater than that in the white slot, or the DIMM is installed in the black slot with the white slot empty---Location:CPU:1 CH:1 DIMM:A1 Rank:0 |
Impact |
The system might restart or stop responding. |
Cause |
1. The principle of having larger rank memory in front (white slot) is not met under the channel configuration. 2. The principle of white slot preferred with memory is not met. |
Recommended action |
1. The memory installation is incorrect. Refer to the Intel PDG for DDR5/DCPMM and other relevant resources for proper memory installation guidelines. 2. If the issue persists, contact Technical Support. |
Configuration error---DIMM population error Two DDR-T memory modules cannot be installed in a channel
Event code |
0x0c717034 |
Message text |
Configuration error---DIMM population error Two DDR-T memory modules cannot be installed in a channel---Location:CPU:$1 CH:$2 DIMM:$3 Rank:$4 |
Variable fields |
$1: CPU number. $2: Channel number. $3: DIMM mark. $4: Rank number. |
Severity level |
Minor |
Example |
Configuration error---DIMM population error Two DDR-T memory modules cannot be installed in a channel---Location:CPU:1 CH:1 DIMM:A1 Rank:0 |
Impact |
The system might restart or stop responding. |
Cause |
Two DCPMMs are installed in a channel, which does not meet DIMM installation requirements. |
Recommended action |
1. The DIMMs are installed incorrectly. For more information, see DDR5/DCPMM related information from Intel PDG. 2. If the issue persists, contact Technical Support. |
Configuration error---The DDR-T memory module is installed in the white slot
Event code |
0x0c717054 |
Message text |
Configuration error---The DDR-T memory module is installed in the white slot---Location:CPU:$1 CH:$2 DIMM:$3 Rank:$4 |
Variable fields |
$1: CPU number. $2: Channel number. $3: DIMM mark. $4: Rank number. |
Severity level |
Minor |
Example |
Configuration error---The DDR-T memory module is installed in the white slot---Location:CPU:1 CH:1 DIMM:A1 Rank:0 |
Impact |
The system might restart or stop responding. |
Cause |
The DCPMM is installed in a white slot, which does not meet DIMM installation requirements. |
Recommended action |
1. The DIMMs are installed incorrectly. For more information, see DDR5/DCPMM related information from Intel PDG. 2. If the issue persists, contact Technical Support. |
Configuration error---ODT configuration errorThe channel is isolated
Event code |
0x0c729034 |
Message text |
Configuration error---ODT configuration error The channel is isolated---Location:CPU:$1 CH:$2 DIMM:$3 Rank:$4 |
Variable fields |
$1: CPU number. $2: Channel number. $3: DIMM mark. $4: Rank number. |
Severity level |
Minor |
Example |
Configuration error---ODT configuration errorThe channel is isolated---Location:CPU:1 CH:2 DIMM:A0 Rank:0 |
Impact |
The system might restart or stop responding. |
Cause |
Memory ODT is configured incorrectly, and the channel is isolated. |
Recommended action |
1. Replace the DIMM. 2. If the issue persists, contact Technical Support. |
Configuration error---REQ is not consistent with clock in timing
Event code |
0x0c729064 |
Message text |
Configuration error---REQ is not consistent with clock in timing---Location:CPU:$1 CH:$2 DIMM:$3 Rank:$4 |
Variable fields |
$1: CPU number. $2: Channel number. $3: DIMM mark. $4: Rank number. |
Severity level |
Minor |
Example |
Configuration error---REQ is not consistent with clock in timing---Location:CPU:1 CH:2 DIMM:A0 Rank:0 |
Impact |
The system might restart or stop responding. |
Cause |
REQ and the clock input have inconsistent timing. |
Recommended action |
1. Replace the DIMM. 2. If the issue persists, contact Technical Support. |
Configuration error---Failed to enable ADDDC
Event code |
0x0c73a014 |
Message text |
Configuration error---Failed to enable ADDDC---Location:CPU:$1 CH:$2 DIMM:$3 Rank:$4 |
Variable fields |
$1: CPU number. $2: Channel number. $3: DIMM mark. $4: Rank number. |
Severity level |
Minor |
Example |
Configuration error---Failed to enable ADDDC---Location:CPU:1 CH:2 DIMM:A0 Rank:0 |
Impact |
The system might restart or stop responding. |
Cause |
Failed to enable ADDDC due to incorrect memory configuration. |
Recommended action |
1. Verify that the memory configuration meets the ADDDC requirements. 2. If the issue persists, contact Technical Support. |
Configuration error---NVMCTRL_MEDIA_NOTREADY
Event code |
0x0c784024 |
Message text |
Configuration error---NVMCTRL_MEDIA_NOTREADY---Location:CPU:$1 CH:$2 DIMM:$3 Rank:$4 |
Variable fields |
$1: CPU number. $2: Channel number. $3: DIMM mark. $4: Rank number. |
Severity level |
Minor |
Example |
Configuration error---NVMCTRL_MEDIA_NOTREADY---Location:CPU:1 CH:2 DIMM:A0 Rank:0 |
Impact |
The system might restart or stop responding. |
Cause |
The DCPMM firmware medium is not ready. |
Recommended action |
1. Access the BIOS setup utility to identify the DCPMM status and update the DCPMM firmware. 2. Replace the DIMM. 3. If the issue persists, contact Technical Support. |
Drive Slot
Drive Presence
Event code |
0x0d0000de |
Message text |
Drive Presence |
Variable fields |
N/A |
Severity level |
Info |
Example |
Drive Presence |
Impact |
The drive presence changed. |
Cause |
The drive presence changed. |
Recommended action |
No action is required. |
Drive Fault
Event code |
0x0d1000de |
Message text |
Drive Fault HDDBay upper drive: Drive Fault --- Bay Slot: $1, HDD Slot: $2 |
Variable fields |
$1: Bay slot number. $2: HDD slot number. |
Severity level |
Major |
Example |
Drive Fault HDDBay upper drive: Drive Fault --- Bay Slot: 1, HDD Slot: 2 |
Impact |
The drive is faulty, which might cause data loss. |
Cause |
The drive is faulty. |
Recommended action |
1. Verify that the status of the drive is Unconfigured Good. 2. Verify that drive LEDs are normal, and the drive can be identified and is accessible in the OS. If a drive LED is orange, the drive is faulty. Replace the faulty components, if any. 3. Verify that the storage controller is in normal state. 4. If the issue persists, contact Technical Support. |
Drive Fault---The disk is missing
Event code |
0x0d1520de |
Message text |
Drive Fault---The disk is missing---Bay slot:$1---HDD slot:$2 |
Variable fields |
$1: Bay slot number. $2: HDD slot number. |
Severity level |
Major |
Example |
Drive Fault---The disk is missing---Bay slot:14---HDD slot:37 |
Impact |
The drive is removed or not installed correctly, which impacts the storage system stability of the system. |
Cause |
The drive cannot be identified by the storage controller or drive cables are connected incorrectly. |
Recommended action |
1. Log in to HDM, and verify that the drive can be identified successfully. 2. Re-install the drive. 3. Replace the drive. 4. If the issue persists, contact Technical Support. |
Predictive Failure
Event code |
0x0d2000de |
Message text |
Predictive Failure |
Variable fields |
N/A |
Severity level |
Minor |
Example |
Predictive Failure |
Impact |
The drive reliability decreases, which might impact the OS storage performance and service operation. |
Cause |
The RAID controller or NVMe SSD reports a predictive failure, which can be a storage medium reserved block alarm, drive lifetime alarm, Prefail alarm, or bad sector alarm. |
Recommended action |
1. Replace the drive. 2. If the issue persists, contact Technical Support. |
In Critical Array
Event code |
0x0d5000de |
Message text |
In Critical Array---PCIe slot:$1---LDDevno:$2 |
Variable fields |
$1: PCIe slot where the logical drive resides. $2: Logical drive number. |
Severity level |
Major |
Example |
In Critical Array---PCIe slot:1---LDDevno:1 |
Impact |
The logical drive degraded, which might impact data reliability. |
Cause |
A drive in a logical drive was removed or failed and the logical drive degraded. |
Recommended action |
1. Verify that no drive is removed. If a drive is removed, re-install the drive and recreate the RAID array. 2. Log in to HDM, view drive information from the storage page, and verify that all drives in the logical drive are identified correctly. If a drive cannot be identified, re-install the drive. If the drive cannot be identified after re-installation, replace the drive. 3. Log in to HDM, view drive information, and verify that the status of the drive is Unconfigured Good. 4. After the drive is identified correctly, recreate the RAID array. 5. If the issue persists, contact Technical Support. |
In Failed Array
Event code |
0x0d6000de |
Message text |
In Failed Array---PCIe slot:$1---LDDevno:$2 |
Variable fields |
$1: PCIe slot where the logical drive resides. $2: Logical drive number. |
Severity level |
Major |
Example |
In Failed Array---PCIe slot:1---LDDevno:1 |
Impact |
The RAID array becomes invalid, causing data loss offline. |
Cause |
A drive in a logical drive was removed or failed and the logical drive was totally corrupted. |
Recommended action |
1. Verify that no drive is removed. If a drive is removed, re-install the drive. 2. If the drive is installed correctly, log in to HDM. View drive information from the storage page, and verify that the drive can be identified correctly. If the drive cannot be identified, re-install the drive. If the drive cannot be identified after re-installation, replace the drive. 3. If the drive is installed correctly, log in to HDM, view drive information from the storage page, and verify that the status of the drive is Unconfigured Good. 4. After the drive is identified correctly, verify that the RAID array is normal. If the RAID array is faulty, recreate the RAID array. 5. If the issue persists, contact Technical Support. |
Rebuild/Remap in progress
Event code |
0x0d7000de |
Message text |
Rebuild/Remap in progress |
Variable fields |
N/A |
Severity level |
Info |
Example |
Rebuild/Remap in progress |
Impact |
No negative impact. |
Cause |
This message is generated during RAID rebuilding after a drive is installed. |
Recommended action |
No action is required. |
The disk triggered an media error
Event code |
0x0da000de |
Message text |
The disk triggered an media error--$1 |
Variable fields |
$1: Drive location. |
Severity level |
Info |
Example |
The disk triggered an media error--Front 1 |
Impact |
A media error on the storage media might cause data loss. |
Cause |
The number of media errors exceeded the threshold. |
Recommended action |
1. Update the drive firmware. 2. Replace the drive. 3. If the issue persists, contact Technical Support. |
The disk triggered an uncorrectable error
Event code |
0x0db000de |
Message text |
The disk triggered an uncorrectable error--$1 |
Variable fields |
$1: Drive location. |
Severity level |
Minor |
Example |
The disk triggered an uncorrectable error--Front 1 |
Impact |
An uncorrectable error on the storage media might cause data loss. |
Cause |
The number of uncorrectable errors exceeded the threshold. |
Recommended action |
1. Update the drive firmware. 2. Replace the drive. 3. If the issue persists, contact Technical Support. |
The disk is missing
Event code |
0x0dc000de |
Message text |
The disk is missing |
Variable fields |
N/A |
Severity level |
Major |
Example |
The disk is missing |
Impact |
The drive is removed or not installed correctly, which impacts the storage system stability of the system. |
Cause |
The drive cannot be identified by the storage controller or drive cables are connected incorrectly. |
Recommended action |
1. Log in to HDM, and verify that the drive can be identified successfully. 2. Verify that the drive data cables, power cords, and signal cables are connected correctly. 3. Re-install the drive. 4. Replace the drive. 5. If the issue persists, contact Technical Support. |
System Firmware Progress
System Firmware Error (POST Error)---Run sense AMP HW FSM failed
Event code |
0x0f0fe044 |
Message text |
System Firmware Error (POST Error)---Run sense AMP HW FSM failed |
Variable fields |
N/A |
Severity level |
Major |
Example |
System Firmware Error (POST Error)---Run sense AMP HW FSM failed |
Impact |
System startup failure might occur. |
Cause |
A memory configuration error occurred. |
Recommended action |
1. Update the BIOS firmware. 2. Verify that the CPUs and DIMMs are installed correctly. 3. Reduce interleaving configuration (memory interleaving and NUMA). |
System Firmware Error (POST Error)--- Memory population enforcement mismatch, Please check the DIMM symmetry on the socket
Event code |
0x0f017134 |
Message text |
System Firmware Error (POST Error)--- Memory population enforcement mismatch, Please check the DIMM population rules--- Location: cpu $1 |
Variable fields |
$1: CPU number. |
Severity level |
Major |
Example |
System Firmware Error (POST Error)--- Memory population enforcement mismatch, Please check the DIMM population rules--- Location: cpu 1 |
Impact |
System performance degradation might occur. |
Cause |
The DIMM population is incorrect. |
Recommended action |
See the DIMM population schemes in the user guide for the corresponding product. |
System Firmware Error (POST Error)---No Dimm on socket$1
Event code |
0x0f017184 |
Message text |
System Firmware Error (POST Error)---No Dimm on socket$1 |
Variable fields |
$1: CPU number. |
Severity level |
Major |
Example |
System Firmware Error (POST Error)---No Dimm on socket1 |
Impact |
If no DIMMs are installed for CPU 1, the system cannot start up. If no DIMMs are not installed for other CPUs, system performance degradation might occur. |
Cause |
No DIMMs are installed for the CPU. |
Recommended action |
1. Verify that the DIMMs are installed correctly as required in the user guide for the server. Re-install all DIMMs if needed. 2. Re-install the DIMM. Verify that the gold contacts on the DIMM are not contaminated and the DIMM slot does not contain any foreign objects. 3. Replace the DIMM, and then power on the server. 4. If the issue persists, contact Technical Support. |
System Firmware Error (POST Error)---No memory found
Event code |
0x0f0e8014 |
Message text |
System Firmware Error (POST Error)---No memory found |
Variable fields |
N/A |
Severity level |
Major |
Example |
System Firmware Error (POST Error)---No memory found |
Impact |
The system cannot start up correctly. |
Cause |
No DIMMs are available. |
Recommended action |
Verify that the DIMMs are available in the system. |
System Firmware Error (POST Error)---No DIMM is available for memory-mapping operation
Event code |
0x0f0e8024 |
Message text |
System Firmware Error (POST Error)---No DIMM is available for memory-mapping operation |
Variable fields |
N/A |
Severity level |
Major |
Example |
System Firmware Error (POST Error)---No DIMM is available for memory-mapping operation |
Impact |
System performance degradation might occur. |
Cause |
No DIMMs is available for memory mapping. |
Recommended action |
1. Log in to HDM, access the memory page, and verify that available DIMMs exist. 2. If the issue persists, contact Technical Support. |
System Firmware Error (POST Error)---DIMM population error
Event code |
0x0f0ed024 |
Message text |
System Firmware Error (POST Error)---DIMM population error |
Variable fields |
N/A |
Severity level |
Major |
Example |
System Firmware Error (POST Error)---DIMM population error |
Impact |
System startup failure might occur. |
Cause |
A DIMM compatibility error occurred. |
Recommended action |
See the HDM maintenance guide for the server. |
System Firmware Error (POST Error)---Some CPU links failed to train. UPI topology changed across reset
Event code |
0x0f003ff4 |
Message text |
System Firmware Error (POST Error)---Some CPU links failed to train. UPI topology changed across reset |
Variable fields |
N/A |
Severity level |
Major |
Example |
System Firmware Error (POST Error)---Some CPU links failed to train. UPI topology changed across reset |
Impact |
System startup failure might occur. |
Cause |
A CPU error occurred. |
Recommended action |
Verify that CPUs are installed correctly. |
System Firmware Error (POST Error)---CPU stepping mismatch detected
Event code |
0x0f010ff4 |
Message text |
System Firmware Error (POST Error)---CPU stepping mismatch detected |
Variable fields |
N/A |
Severity level |
Major |
Example |
System Firmware Error (POST Error)---CPU stepping mismatch detected |
Impact |
System startup failure might occur. |
Cause |
The CPUs were installed incorrectly and CPU stepping mismatch occurred. |
Recommended action |
Verify that the CPU stepping is consistent between the installed CPUs. |
System Firmware Error (POST Error)---KTI Topology Change Logged
Event code |
0x0f0ffff4 |
Message text |
System Firmware Error (POST Error)---KTI Topology Change Logged |
Variable fields |
N/A |
Severity level |
Major |
Example |
System Firmware Error (POST Error)---KTI Topology Change Logged |
Impact |
System startup failure might occur. |
Cause |
A CPU error occurred. |
Recommended action |
Verify that the CPUs are installed correctly. |
System Firmware Error (POST Error)---CPU matching failure---CPU stepping is detected
Event code |
0x0f0d00de |
Message text |
System Firmware Error (POST Error)---CPU matching failure---CPU stepping is detected |
Variable fields |
N/A |
Severity level |
Major |
Example |
System Firmware Error (POST Error)---CPU matching failure---CPU stepping is detected |
Impact |
System startup failure occurs. |
Cause |
A CPU stepping mismatch error occurred at POST. |
Recommended action |
1. Verify that the CPU has the same model as the primary CPU. 2. Verify that CPU stepping of the CPU matches the primary CPU. |
System Firmware Error (POST Error)---CPU matching failure---CPU frequency is detected
Event code |
0x0f0d10de |
Message text |
System Firmware Error (POST Error)---CPU matching failure---CPU frequency is detected |
Variable fields |
N/A |
Severity level |
Major |
Example |
System Firmware Error (POST Error)---CPU matching failure---CPU frequency is detected |
Impact |
System startup failure might occur. |
Cause |
A CPU frequency mismatch error occurred at POST. |
Recommended action |
Verify that the CPU has the same model as the primary CPU. |
System Firmware Error (POST Error)---CPU matching failure---CPU Microcode is detected
Event code |
0x0f0d20de |
Message text |
System Firmware Error (POST Error)---CPU matching failure---CPU Microcode is detected |
Variable fields |
N/A |
Severity level |
Major |
Example |
System Firmware Error (POST Error)---CPU matching failure---CPU Microcode is detected |
Impact |
System startup failure might occur. |
Cause |
A CPU microcode mismatch error occurred at POST. |
Recommended action |
Verify that the CPU has the same model as the primary CPU. |
System Firmware Error (POST Error)---CPU matching failure---UPI Topology is detected
Event code |
0x0f0d30de |
Message text |
System Firmware Error (POST Error)---CPU matching failure---UPI Topology is detected |
Variable fields |
N/A |
Severity level |
Major |
Example |
System Firmware Error (POST Error)---CPU matching failure---UPI Topology is detected |
Impact |
System startup failure might occur. |
Cause |
A CPU UPI mismatch error occurred at POST. |
Recommended action |
Verify that the CPU has the same model as the primary CPU. |
System Firmware Error(POST Error)---Unrecoverable video controller failure
Event code |
0x0f0090de |
Message text |
System Firmware Error(POST Error)---Unrecoverable video controller failure |
Variable fields |
N/A |
Severity level |
Minor |
Example |
System Firmware Error(POST Error)---Unrecoverable video controller failure |
Impact |
KVM video display is abnormal. |
Cause |
Two VGA screen captures are the same during the host startup process. |
Recommended action |
1. Replace the BMC card. 2. If the issue persists, contact Technical Support. |
System Firmware Hang
Event code |
0x0f1000de |
Message text |
System Firmware Hang |
Variable fields |
N/A |
Severity level |
Critical |
Example |
System Firmware Hang |
Impact |
System operation failure might occur. |
Cause |
The BIOS hangs during startup. |
Recommended action |
1. Resolve the issue based on other event logs reported simultaneously for the component. 2. If the issue persists, contact Technical Support. |
System software triggered an uncorrectable error
Event code |
0x0f1a00de |
Message text |
System software triggered an uncorrectable error |
Variable fields |
N/A |
Severity level |
Major |
Example |
System software triggered an uncorrectable error |
Impact |
An IERR or MCERR error is triggered, which may cause service unavailability. |
Cause |
An IERR or MCERR error is triggered, and the HDM diagnosis result shows that a system software uncorrectable error occurred. |
Recommended action |
Usually an IERR or MCERR error is triggered by an abnormality in the system or system software. Contact Technical Support. |
System software triggered a correctable error
Event code |
0x0f0a00de |
Message text |
System software triggered a correctable error |
Variable fields |
N/A |
Severity level |
Minor |
Example |
System software triggered a correctable error |
Impact |
An IERR or MCERR error is triggered, which may cause service unavailability. |
Cause |
An IERR or MCERR error is triggered, and the HDM diagnosis result shows that a system software correctable error occurred. |
Recommended action |
Usually an IERR or MCERR error is triggered by an abnormality in the system or system software. Contact Technical Support. |
System Firmware Progress---Video initialization---Detection unsuccessful
Event code |
0x0f2090de |
Message text |
System Firmware Progress---Video initialization---Detection unsuccessful |
Variable fields |
N/A |
Severity level |
Minor |
Example |
System Firmware Progress---Video initialization---Detection unsuccessful |
Impact |
No negative impact. |
Cause |
A video controller check failed. |
Recommended action |
Contact Technical Support. |
System Firmware Progress---Secondary processor(s) initialization---Detection unsuccessful
Event code |
0x0f2030de |
Message text |
System Firmware Progress---Secondary processor(s) initialization---Detection unsuccessful |
Variable fields |
N/A |
Severity level |
Minor |
Example |
System Firmware Progress---Secondary processor(s) initialization---Detection unsuccessful |
Impact |
No negative impact. |
Cause |
The TPM/TCM self-test signal is lost or a device access failure occurs. |
Recommended action |
Contact Technical Support. |
Event Logging Disabled
Log Area Reset/Cleared
Event code |
0x102000de |
Message text |
Log Area Reset/Cleared |
Variable fields |
N/A |
Severity level |
Info |
Example |
Log Area Reset/Cleared |
Impact |
No negative impact. |
Cause |
This message is generated when all event log entries are cleared. |
Recommended action |
No action is required. |
SEL Full
Event code |
0x104000de |
Message text |
SEL Full |
Variable fields |
N/A |
Severity level |
Minor |
Example |
SEL Full |
Impact |
The system stops logging new events. |
Cause |
This message is generated when one of the following occurs: · If the event log reaches its maximum size, the system stops logging new events. · A user disables event logging. |
Recommended action |
Log in to HDM, enter the Event Log page, and clear all event logs. |
SEL Almost Full
Event code |
0x105000de |
Message text |
SEL Almost Full |
Variable fields |
N/A |
Severity level |
Minor |
Example |
SEL Almost Full |
Impact |
No negative impact. |
Cause |
The log file is reaching its maximum size when the logging policy is configured to stop login at full storage. |
Recommended action |
Log in to HDM, enter the Event Log page, and clear all event logs. |
System Event
System Reconfigured---BIOS load default. CMOS cleared
Event code |
0x120000de |
Message text |
System Reconfigured---BIOS load default. CMOS cleared |
Variable fields |
N/A |
Severity level |
Minor |
Example |
System Reconfigured---BIOS load default. CMOS cleared |
Impact |
The BIOS loads the default settings and the user-configured settings get lost. |
Cause |
The system board battery is abnormal. |
Recommended action |
1. Verify that the BIOS boot mode meets the requirements of secure boot. If not, change the boot mode to UEFI. 2. Verify that the BIOS firmware is upgraded successfully. 3. Upgrade the BIOS with the factory defaults (if any) or default settings of the BIOS restored. 4. If the issue persists, contact Technical Support. |
Limit Exceeded---CPU usage exceeds the threshold
Event code |
0x1210100a |
Message text |
Limit Exceeded---CPU usage exceeds the threshold---Current usage $1, Threshold $2 |
Variable fields |
$1: Current CPU usage. $2: CPU usage threshold. |
Severity level |
Info |
Example |
Limit Exceeded---Cpu usage exceeds the threshold---Current usage 82%, Threshold 80% |
Impact |
System performance degradation might occur. |
Cause |
The CPU usage exceeds the threshold. |
Recommended action |
No action is required. |
Limit Exceeded---Mem usage exceeds the threshold
Event code |
0x120200de |
Message text |
Limit Exceeded---Mem usage exceeds the threshold---Current usage $1, Threshold $2 |
Variable fields |
$1: Current memory usage. $2: Memory usage threshold. |
Severity level |
Major |
Example |
Limit Exceeded---Mem usage exceeds the threshold---Current usage 81%, Threshold 80% |
Impact |
System performance degradation might occur. |
Cause |
The memory usage exceeds the threshold. |
Recommended action |
No action is required. |
Limit Exceeded---Network usage exceeds the threshold
Event code |
0x120300de |
Message text |
Limit Exceeded---Network usage exceeds the threshold---Current usage $1, Threshold $2 |
Variable fields |
$1: Current network usage. $2: Network usage threshold. |
Severity level |
Major |
Example |
Limit Exceeded---Network usage exceeds the threshold---Current usage 81%, Threshold 80% |
Impact |
The network might get lost. |
Cause |
The network usage exceeds the threshold. |
Recommended action |
This message is triggered by FIST SMS according to the system resource usage. |
Limit Exceeded---Hard disk usage exceeds the threshold
Event code |
0x120400de |
Message text |
Limit Exceeded---Hard disk usage exceeds the threshold---OS:Linux/Unix,See disk details about Logical disk name,Current usage $1, Threshold $2 |
Variable fields |
$1: Current drive usage. $2: Drive usage threshold. |
Severity level |
Major |
Example |
Limit Exceeded---Hard disk usage exceeds the threshold---OS:Linux/Unix,See disk details about Logical disk name,Current usage 81%, Threshold 80% |
Impact |
The drive reliability decreases, which might impact the storage performance and service operation of the OS. |
Cause |
The drive usage exceeds the threshold. |
Recommended action |
This message is triggered by FIST SMS according to the system resource usage. |
Timestamp clock synch---BMC Time SYNC succeed
Event code |
0x125000de |
Message text |
Timestamp Clock Synch---BMC Time SYNC succeed. |
Variable fields |
N/A |
Severity level |
Info |
Example |
Timestamp Clock Synch---BMC Time SYNC succeed. |
Impact |
No negative impact. |
Cause |
BMC synchronized ME clock successfully. |
Recommended action |
No action is required. |
Timestamp clock synch
Event code |
0x128000de |
Message text |
Timestamp Clock Synch---event is $1 of pair---SEL Timestamp Clock updated |
Variable fields |
$1: In the format of first/second, where first represents the event before time synchronization and second represents the event after time synchronization. |
Severity level |
Info |
Example |
Timestamp Clock Synch---event is first of pair---SEL Timestamp Clock updated |
Impact |
No negative impact. |
Cause |
HDM synchronizes time with the server when the server is powered on. The first event is triggered before time synchronization and the second event is triggered after time synchronization. |
Recommended action |
No action is required. |
Critical Interrupt
PCI PERR
Event code |
0x134000de |
Message text |
PCI PERR ---Slot $1---PCIE Name:$2 |
Variable fields |
$1: Slot number. $2: PCIe name. |
Severity level |
Major |
Example |
PCI PERR ---Slot 3---PCIE Name: RAID-LSI-9361-8i |
Impact |
An error occurred on the PCIe module, which might lead to the system-level failure if the error is severe enough. |
Cause |
An internal parity error occurs on the PCIe module. This message is generated when the PERR signal (parity check) on the PCIe module is abnormal. |
Recommended action |
1. If the message is reported serval times during a period of time, ensure that the riser card is securely connected to the system board. 2. Reboot the server. 3. Locate the PCIe module based on the slot number. 4. If the PCIe module is a removable component, perform the following operations: a. Verify that the PCIe module is installed correctly. b. Verify that the golden plating on the PCIe module is not contaminated. c. Install the PCIe module to another slot to identify whether the error is present on the PCIe module or the slot. d. Update all firmware and drivers, including non-Intel components. e. If the error occurs on the PCIe slot, verify that the slot is normal and the gold plating on the riser card is not contaminated. f. Replace the PCIe module. 5. If the PCIe module is embedded on the system board, perform the following operations: a. Update the BIOS, firmware, and drivers. b. Replace the system board. |
PCI SERR
Event code |
0x13500000 |
Message text |
PCI SERR---Slot $1---PCIE Name:$2 |
Variable fields |
$1: Slot number. $2: PCIe name. |
Severity level |
Major |
Example |
PCI SERR---Slot 3---PCIE Name: RAID-LSI-9361-8i |
Impact |
An error occurred on the PCIe module, which might lead to the system-level failure if the error is severe enough. |
Cause |
An internal system error occurred on the PCIe module. This message is generated when the SERR signal on the PCIe module is abnormal. A system error includes an address parity error, data parity error within a period, and other fatal errors. |
Recommended action |
1. If the message is reported serval times during a period of time, ensure that the riser card is securely connected to the system board. 2. Reboot the server. 3. Locate the PCIe module based on the slot number. 4. If the PCIe module is a removable component, perform the following operations: a. Verify that the PCIe module is installed correctly. b. Verify that the golden plating on the PCIe module is not contaminated. c. Install the PCIe module to another slot to identify whether the error is present on the PCIe module or the slot. d. Update all firmware and drivers, including non-Intel components. e. If the error occurs on the PCIe slot, verify that the slot is normal and the gold plating on the riser card is not contaminated. f. Replace the PCIe module. 5. If the PCIe module is embedded on the system board, perform the following operations: a. Update the BIOS, firmware, and drivers. b. Replace the system board. |
Bus Correctable Error
Event code |
0x137000de |
Message text |
Bus Correctable Error ---Slot $1---PCIE Name:$2 |
Variable fields |
$1: PCIe slot number. $2: PCIe module name. |
Severity level |
Minor |
Example |
Bus Correctable Error---Slot 3---PCIE Name: RAID-LSI-9361-8i |
Impact |
If this message is generated occasionally, no negative impact occurs on the system. If this message is generated frequently, the PCIe module performance might be affected. |
Cause |
An internal correctable error occurred on the PCIe module. |
Recommended action |
1. Ignore this message if it is generated during access to the PCIe module, ignore it. 2. If the same message is generated repeatedly, use the slot number to locate the faulty PCIe module. 3. If the PCIe module is removable, verify that the PCIe module is installed correctly or install the PCIe module to another slot to identify the cause. 4. Replace the PCIe module. |
Bus Correctable Error
Event code |
0x137800de |
Message text |
Bus Correctable Error ---Slot $1---PCIE Name:$2 |
Variable fields |
$1: PCIe slot number. $2: PCIe module name. |
Severity level |
Minor |
Example |
Bus Correctable Error---Slot 3---PCIE Name: RAID-LSI-9361-8i |
Impact |
If this message is generated occasionally, no negative impact occurs on the system. If this message is generated frequently, the PCIe module performance might be affected. |
Cause |
An internal correctable error occurred on the PCIe module on an AMD model. |
Recommended action |
1. Ignore this message if it is generated during access to the PCIe module, ignore it. 2. If the same message is generated repeatedly, use the slot number to locate the faulty PCIe module. 3. If the PCIe module is removable, verify that the PCIe module is installed correctly or install the PCIe module to another slot to identify the cause. 4. Replace the PCIe module. |
Bus Uncorrectable Error
Event code |
0x138000de |
Message text |
Bus Uncorrectable Error ---Slot $1---PCIE Name:$2 |
Variable fields |
$1: PCIe slot number. $2: PCIe module name. |
Severity level |
Major |
Example |
Bus Uncorrectable Error---Slot 3---PCIE Name: RAID-LSI-9361-8i |
Impact |
An error occurred on the PCIe module, which might lead to the system-level failure if the error is severe enough. |
Cause |
An internal uncorrectable error occurred on the PCIe module. |
Recommended action |
1. If the message is reported serval times during a period of time, ensure that the riser card is securely connected to the system board. 2. Reboot the server. 3. Locate the PCIe module based on the slot number. 4. If the PCIe module is a removable component, perform the following operations: a. Verify that the PCIe module is installed correctly. b. Verify that the golden plating on the PCIe module is not contaminated. c. Install the PCIe module to another slot to identify whether the error is present on the PCIe module or the slot. d. If the error occurs on the PCIe module, update all firmware and drivers. e. If the error occurs on the slot, verify that the gold plating on the riser card is not contaminated. f. If the issue persists, replace the PCIe module. 5. If the PCIe module is embedded on the system board, perform the following operations: a. Update the BIOS, firmware, and drivers. b. Replace the system board. 6. If the issue persists, contact Technical Support. |
Bus Uncorrectable Error
Event code |
0x138800de |
Message text |
Bus Uncorrectable Error ---Slot $1---PCIE Name:$2 |
Variable fields |
$1: PCIe slot number. $2: PCIe module name. |
Severity level |
Major |
Example |
Bus Uncorrectable Error---Slot 3---PCIE Name: RAID-LSI-9361-8i |
Impact |
An error occurred on the PCIe module, which might lead to the system-level failure if the error is severe enough. |
Cause |
An internal uncorrectable error identified by SHD occurred on the PCIe module on an AMD model. |
Recommended action |
1. Locate the PCIe module based on the slot number. 2. If the PCIe module is a removable component, perform the following operations: a. Verify that the PCIe module is installed correctly. b. Install the PCIe module is another slot. c. Update the firmware and driver of the PCIe module. 3. If the PCIe module is embedded on the system board, perform the following operations: a. Update the BIOS, firmware, and driver. b. Replace the system board. |
Bus Fatal Error
Event code |
0x13a000de |
Message text |
Bus Fatal Error ------Slot $1---PCIE Name: $2 |
Variable fields |
$1: PCIe slot number. $2: PCIe module name. |
Severity level |
Major |
Example |
Bus Fatal Error---Slot 3---PCIE Name: RAID-LSI-9361-8i |
Impact |
An error occurred on the PCIe module, which might lead to the system-level failure if the error is severe enough. |
Cause |
An internal fatal error occurred on the PCIe module. |
Recommended action |
1. If the message is reported serval times during a period of time, ensure that the riser card is securely connected to the system board. 2. Reboot the server. 3. Locate the PCIe module based on the slot number. 4. If the PCIe module is a removable component, perform the following operations: a. Verify that the PCIe module is installed correctly. b. Verify that the golden plating on the PCIe module is not contaminated. c. Install the PCIe module to another slot to identify whether the error is present on the PCIe module or the slot. d. If the error occurs on the PCIe module, upgrade firmware and drivers of the PCIe module. e. If the error occurs on the slot, verify that the gold plating on the riser card is not contaminated. f. If the issue persists, replace the PCIe module. 5. If the PCIe module is embedded on the system board, perform the following operations: a. Update the BIOS, firmware, and drivers. b. Replace the system board. 6. If the issue persists, contact Technical Support. |
Bus Degraded
Event code |
0x13b000de |
Message text |
Bus Degraded ------Slot $1---PCIE Name: $2 |
Variable fields |
$1: PCIe slot number. $2: PCIe module name. |
Severity level |
Major |
Example |
Bus Degraded ---Slot 3---PCIE Name: RAID-LSI-9361-8i |
Impact |
System performance degradation might occur. |
Cause |
The speed and bandwidth of the PCIe module decreased. |
Recommended action |
1. If the message is reported serval times during a period of time, ensure that the riser card is securely connected to the system board. 2. Reboot the server. 3. Locate the PCIe module based on the slot number. 4. If the PCIe module is a removable component, perform the following operations: a. Verify that the PCIe module is installed correctly. b. Verify that the golden plating on the PCIe module is not contaminated. c. Install the PCIe module to another slot to identify whether the error is present on the PCIe module or the slot. d. Update all firmware and drivers, including non-Intel components. e. If the error occurs on the PCIe slot, verify that the slot is normal and the gold plating on the riser card is not contaminated. f. Replace the PCIe module. 5. If the PCIe module is embedded on the system board, perform the following operations: a. Update the BIOS, firmware, and drivers. b. Replace the system board. |
$1 triggered an uncorrectable error
Event code |
0x138400de |
Message text |
$1 triggered an uncorrectable error |
Variable fields |
$1: PCIe module type. |
Severity level |
Major |
Example |
NIC triggered an uncorrectable error |
Impact |
An error occurred on the PCIe module, which might lead to the system-level failure if the error is severe enough. |
Cause |
An IERR or MCERR error occurred, which is identified as a PCIe uncorrectable error by HDM. |
Recommended action |
1. Locate the PCIe module based on the slot number. 2. If the PCIe module is a removable component, perform the following operations: a. Verify that the PCIe module is installed correctly. b. Install the PCIe module to another slot to identify whether the error is present on the PCIe module or the slot. c. Update all firmware and drivers, including non-Intel components. 3. If the PCIe module is embedded on the system board, perform the following operations: a. Update the BIOS, firmware, and driver. b. Replace the system board. |
$1 triggered a correctable error
Event code |
0x137400de |
Message text |
$1 triggered a correctable error |
Variable fields |
$1: PCIe module type. |
Severity level |
Major |
Example |
NIC triggered a correctable error |
Impact |
An error occurred on the PCIe module, which might lead to the system-level failure if the error is severe enough. |
Cause |
An IERR or MCERR error occurred, which is identified as a PCIe correctable error by HDM. |
Recommended action |
1. Locate the PCIe module based on the slot number. 2. If the PCIe module is a removable component, perform the following operations: a. Verify that the PCIe module is installed correctly. b. Install the PCIe module to another slot to identify whether the error is present on the PCIe module or the slot. c. Update all firmware and drivers, including non-Intel components. 3. If the PCIe module is embedded on the system board, perform the following operations: a. Update the BIOS, firmware, and driver. b. Replace the system board. |
Button / Switch
Power Button pressed---Physical button---Button pressed
Event code |
0x140000de |
Message text |
Power Button pressed---$1---$2 |
Variable fields |
N/A |
Severity level |
$1: Button type, including Physical button and Virtual button. $2: Action, including Power off command, Power on command, and Soft off command. |
Example |
Power Button pressed---Physical button---Power off command |
Impact |
No negative impact. |
Cause |
This message is generated in the following conditions: · The physical power button on the front panel of the server is pressed. · Commands are executed to forcedly power off the server, gracefully power off the server, and power cycle the server. |
Recommended action |
No action is required. |
Reset Button pressed
Event code |
0x142000de |
Message text |
Reset Button pressed---Virtual button---reset command |
Variable fields |
N/A |
Severity level |
Info |
Example |
Reset Button pressed---Virtual button---reset command |
Impact |
No negative impact. |
Cause |
This message is generated when one of the following conditions exists: · The reset command is executed. · An IERR event occurs. |
Recommended action |
No action is required. |
Module / Board
Transition to Non-Critical from OK
Event code |
0x1510000e |
Message text |
Transition to Non-Critical from OK |
Variable fields |
N/A |
Severity level |
Minor |
Example |
Transition to Non-Critical from OK |
Impact |
No negative impact if this message is generated occasionally. |
Cause |
An internal correctable error occurred on the PCIe BUS0 device. |
Recommended action |
1. Verify that the power supply for the system is normal. 2. If the issue persists, contact Technical Support. |
Transition to Critical from less severe
Event code |
0x1520000e |
Message text |
Transition to Critical from less severe |
Variable fields |
N/A |
Severity level |
Major |
Example |
Transition to Critical from less severe |
Impact |
An error occurred on the PCIe BUS0 device, which might lead to the system-level failure if the error is severe enough. |
Cause |
An internal uncorrectable error occurred on the PCIe BUS0 device. |
Recommended action |
1. Verify that the power supply for the system is normal 2. Verify that all components are operating correctly. 3. If the issue persists, contact Technical Support. |
Transition to Non- Recoverable from less severe
Event code |
0x1530000e |
Message text |
Transition to Non- Recoverable from less severe $1($2). |
Variable fields |
$1: Faulty component, such as the system board (---System detected a power supply failure on Motherboard), PDB (---System detected a power supply failure on PDB), compute module (---System detected a power supply failure on CMOD), and riser card (---System detected a power supply failure on Riser). If this alarm is not related to specific components, this field is empty. $2: Specific faulty component, such as P5V, P5V_STBY, CPU1_PVCSA, CPU2_PVCCIO. |
Severity level |
Critical |
Example |
Transition to Non- Recoverable from less severe---System detected a power supply failure on Motherboard(P5V). |
Impact |
System power-off might occur. |
Cause |
Abnormal board voltage. |
Recommended action |
1. Ignore this message if it is triggered by a system power-on or power-off event. 2. Reconnect power cords and identify whether the server can be powered on correctly. ¡ If the server can be powered on, the message might be generated because the detection signals were interfered. No action is required. ¡ If the server cannot be powered on, review the SDS logs to locate the fault and replace the faulty component. 3. If the message is generated again during the operation, replace the faulty component. 4. If the issue persists, contact Technical Support. |
Transition to Non-Critical from OK---System is operating in KTI Link Slow Speed Mode
Event code |
0x15101ff4 |
Message text |
Transition to Non-Critical from OK---System is operating in KTI Link Slow Speed Mode |
Variable fields |
N/A |
Severity level |
Minor |
Example |
Transition to Non-Critical from OK---System is operating in KTI Link Slow Speed Mode |
Impact |
System startup failure might occur. |
Cause |
The system is operating in Keizer Technology Interconnect (KTI) low speed mode. |
Recommended action |
Verify that the signal quality and hardware parameters are correct. |
Transition to Non-Critical from OK---Requested Link Speed is not supported. Defaulting to 18GT
Event code |
0x15102ff4 |
Message text |
Transition to Non-Critical from OK---Requested Link Speed is not supported. Defaulting to 18GT |
Variable fields |
N/A |
Severity level |
Minor |
Example |
Transition to Non-Critical from OK---Requested Link Speed is not supported. Defaulting to 18GT |
Impact |
System startup failure might occur. |
Cause |
The link speed is not supported. |
Recommended action |
Verify that hardware parameters are correct. |
Transition to Non-Critical from OK---One or more per Link option mismatch detected. Forcing to common setting
Event code |
0x15104ff4 |
Message text |
Transition to Non-Critical from OK---One or more per Link option mismatch detected. Forcing to common setting |
Variable fields |
N/A |
Severity level |
Minor |
Example |
Transition to Non-Critical from OK---One or more per Link option mismatch detected. Forcing to common setting |
Impact |
System startup failure might occur. |
Cause |
Some CPU links are faulty. |
Recommended action |
Verify that the UPI configuration is correct on the BIOS setup utility. |
Transition to Non-Critical from OK---Some CPU has more than one link connecting to other CPU. Disable one of the Dual-Link
Event code |
0x15105ff4 |
Message text |
Transition to Non-Critical from OK---Some CPU has more than one link connecting to other CPU. Disable one of the Dual-Link |
Variable fields |
N/A |
Severity level |
Minor |
Example |
Transition to Non-Critical from OK---Some CPU has more than one link connecting to other CPU. Disable one of the Dual-Link |
Impact |
System startup failure might occur. |
Cause |
A UPI link error occurred. |
Recommended action |
Verify that the UPI link is connected as required. |
Transition to Non-Critical from OK---KTI Adaptation is in progress, or High Speed adaptation is failed
Event code |
0x15106ff4 |
Message text |
Transition to Non-Critical from OK---KTI Adaptation is in progress, or High Speed adaptation is failed |
Variable fields |
N/A |
Severity level |
Minor |
Example |
Transition to Non-Critical from OK---KTI Adaptation is in progress, or High Speed adaptation is failed |
Impact |
System startup failure might occur. |
Cause |
KTI adaption is in progress. |
Recommended action |
Verify that the signal quality and hardware parameters are correct. |
System board triggered an uncorrectable error
Event code |
0x1521000e |
Message text |
System board triggered an uncorrectable error |
Variable fields |
N/A |
Severity level |
Major |
Example |
System board triggered an uncorrectable error |
Impact |
An IERR or MCERR error occurred in the system, which causes services to become unavailable. |
Cause |
An IERR or MCERR error was triggered. The error was identified as an uncorrectable error on the system board (including backplanes) by HDM. |
Recommended action |
If the issue persists, contact Technical Support. |
System board triggered a correctable error
Event code |
0x1521000e |
Message text |
System board triggered a correctable error |
Variable fields |
N/A |
Severity level |
Minor |
Example |
System board triggered a correctable error |
Impact |
An IERR or MCERR error occurred in the system, which causes services to become unavailable. |
Cause |
An IERR or MCERR error was triggered. The error was identified as an uncorrectable error on the system board (including backplanes) by HDM. |
Recommended action |
If the issue persists, contact Technical Support. |
Add-in Card
Transition to OK
Event code |
0x1700000e |
Message text |
Transition to OK---PCIe slot: $1---LDDevno:$2 |
Variable fields |
$1: PCIe slot where the logical drive resides. $2: Logical drive number. |
Severity level |
Info |
Example |
Transition to OK---PCIe slot:1---LDDevno:0 |
Impact |
No negative impact. |
Cause |
This message is generated if the logical drive managed by the storage controller changes from abnormal to normal. |
Recommended action |
No action is required. |
Transition to Critical from less severe
Event code |
0x1720000e |
Message text |
Transition to Critical from less severe |
Variable fields |
N/A |
Severity level |
Major |
Example |
Transition to Critical from less severe |
Impact |
System power-off might occur. |
Cause |
The backplane power supply is faulty. |
Recommended action |
1. Ignore this message if it is triggered by a system power-on or power-off event. 2. Reconnect power cords and identify whether the server can be powered on correctly. ¡ If the server can be powered on, the message might be generated because the detection signals were interfered. No action is required. ¡ If the server cannot be powered on, review the SDS logs to locate the fault and replace the faulty component. 3. If the issue persists, replace the faulty component. 4. If the issue persists, contact Technical Support. |
Transition to Critical from less severe
Event code |
0x172a000e |
Event code |
Transition to Critical from less severe---PCIe slot:$1---LDDevno::$2 |
Message text |
The logical drive degraded. |
Variable fields |
Major |
Severity level |
Transition to Critical from less severe---PCIe slot: 1---LDDevno:0 |
Example |
The logical drive degraded, which might impact data reliability. |
Impact |
This message is generated when the logical drive managed by the storage controller is degraded or faulty. |
Cause |
1. Log in to HDM to identify whether the logical drive is degraded or faulty. 2. If the logical drive is degraded, perform the following operations: a. Verify that all member drives in the logical drive are operating correctly. b. Re-install member drives to identify whether the drives can be correctly identified. c. Access the BIOS to identify whether all member drives have been configured correctly. d. Check the error logs for the drives. e. Replace the faulty drive. f. If the issue persists, contact Technical Support. 3. If the logical drive is faulty, perform the following operations: a. Verify that the drive has not been uninstalled. b. Re-install the member drives and rebuild the RAID. c. Replace the faulty drive, and then reboot the server. d. If the issue persists, contact Technical Support. |
Transition to Non-recoverable from less severe
Event code |
0x1730000e |
Message text |
Transition to Non-recoverable from less severe |
Variable fields |
N/A |
Severity level |
Critical |
Example |
Transition to Non-recoverable from less severe |
Impact |
System power-off might occur. |
Cause |
The backplane power supply or the riser power supply is faulty. |
Recommended action |
1. Ignore this message if it is triggered by a system power-on or power-off event. 2. Reconnect power cords and identify whether the server can be powered on correctly. ¡ If the server can be powered on, the message might be generated because the detection signals were interfered. No action is required. ¡ If the server cannot be powered on, review the SDS logs to locate the fault and replace the faulty component. 3. If the issue persists, replace the faulty component. 4. If the issue persists, contact Technical Support. |
ChipSet
Transition to Critical from less severe
Event code |
0x1920000e |
Message text |
Transition to Critical from less severe |
Variable fields |
N/A |
Severity level |
Major |
Example |
Transition to Critical from less severe |
Impact |
System performance degradation might occur. |
Cause |
The PCH status was abnormal. |
Recommended action |
1. If this message is generated during the host restart process, ignore this message. 2. If this message is repeatedly generated during the operation, replace the system board. 3. If the issue persists, contact Technical Support. |
Cable/Interconnect
Configuration Error - Incorrect cable connected / Incorrect interconnection
Event code |
0x1b1000de |
Message text |
Configuration Error - Incorrect cable connected / Incorrect interconnection |
Variable fields |
N/A |
Severity level |
Minor |
Example |
Configuration Error - Incorrect cable connected / Incorrect interconnection |
Impact |
The network is abnormal, which might cause network disconnectivity in the system. |
Cause |
Incorrect cable configuration. |
Recommended action |
1. Verify that the cables are connected to the correct interfaces. 2. Verify that the cables connected properly for power connection. |
Configuration Error - Incorrect cable connected / Incorrect interconnection
Event code |
0x1b1800de |
Message text |
Configuration Error - Incorrect cable connected / Incorrect interconnection---$1 |
Variable fields |
$1: Incorrect cable configuration. |
Severity level |
Minor |
Example |
Configuration Error - Incorrect cable connected / Incorrect interconnection---Incorrect SATA cable connection to the backplane |
Impact |
A communication exception might occur on the backplane. |
Cause |
Incorrect cable configuration. |
Recommended action |
1. Verify that the cables are connected to the correct interfaces. 2. Verify that the cables connected properly for power connection. |
Configuration Error - Incorrect cable connected / Incorrect interconnection
Event code |
0x1b1400de |
Message text |
Configuration Error - Incorrect cable connected / Incorrect interconnection ($1) |
Variable fields |
$1: Cable connection location. |
Severity level |
Minor |
Example |
Configuration Error-Incorrect cable connected / Incorrect interconnection(FrontBackplane1) |
Impact |
A communication exception might occur on the backplane. |
Cause |
Incorrect cable configuration. |
Recommended action |
1. Verify that the cables are connected to the correct interfaces. 2. Verify that the cables connected properly for power connection. |
System Boot / Restart Initiated
Initiated by power up
Event code |
0x1d0000de |
Message text |
Initiated by power up |
Variable fields |
N/A |
Severity level |
Info |
Example |
Initiated by power up |
Impact |
No negative impact. |
Cause |
This event is triggered by a system power-on. |
Recommended action |
No action is required. |
Initiated by hard reset
Event code |
0x1d1000de |
Message text |
Initiated by hard reset |
Variable fields |
N/A |
Severity level |
Info |
Example |
Initiated by hard reset |
Impact |
No negative impact. |
Cause |
This event is triggered by a system restart. |
Recommended action |
No action is required. |
Initiated by warm reset
Event code |
0x1d2000de |
Message text |
Initiated by warm reset |
Variable fields |
N/A |
Severity level |
Info |
Example |
Initiated by warm reset |
Impact |
No negative impact. |
Cause |
This event is triggered by a system warm restart. |
Recommended action |
No action is required. |
System restart
Event code |
0x1d7000de |
Message text |
System Restart---$1:$2 |
Variable fields |
$1: Reboot cause. $2: Power mode. Options include power off, power reset, and power cycle. This option may be empty. |
Severity level |
Info |
Example |
System Restart---due to power button pressed:power off |
Impact |
No negative impact. |
Cause |
The system restarts. |
Recommended action |
No action is required. |
Boot Error
No bootable media
Event code |
0x1e0000de |
Message text |
No bootable media |
Variable fields |
N/A |
Severity level |
Info |
Example |
No bootable media |
Impact |
No negative impact. |
Cause |
Status description to indicate no bootable media, which typically has no negative impact. |
Recommended action |
1. Specify an available boot device. 2. If the issue persists, contact Technical Support. |
OS_BOOT
C: boot completed
Event code |
0x1f1000de |
Message text |
C: boot completed |
Variable fields |
N/A |
Severity level |
Info |
Example |
C: boot completed |
Impact |
No negative impact. |
Cause |
The operating system booted from a hard drive. This event happens for most Windows OSs. |
Recommended action |
No action is required. |
Boot completed - boot device not specified
Event code |
0x1f6000de |
Message text |
Boot completed - boot device not specified |
Variable fields |
N/A |
Severity level |
Info |
Example |
Boot completed - boot device not specified |
Impact |
No negative impact. |
Cause |
This message is generated when the server exits the BIOS boot phase. |
Recommended action |
No action is required. |
OS Stop / Shutdown
Run-time Critical Stop
Event code |
0x201000de |
Message text |
Run-time Critical Stop |
Variable fields |
N/A |
Severity level |
Critical |
Example |
Run-time Critical Stop |
Impact |
The system crashes. |
Cause |
A critical error occurred during operating system operation. |
Recommended action |
1. Verify that the installed system, drivers, firmware, and software do not have bugs and are compatible with the server. 2. Update the versions if bugs or compatibility issues exist. 3. Verify that the installed hardware options are compatible with the server. For more information about component and server compatibility, access the component compatibility query tool at the official website. 4. If the issue persists, contact Technical Support. |
OS Graceful Stop
Event code |
0x202000de |
Message text |
OS Graceful Stop |
Variable fields |
N/A |
Severity level |
Info |
Example |
OS Graceful Stop |
Impact |
The system shut down. |
Cause |
The Windows OS was forcedly stopped. |
Recommended action |
No action is required. |
OS Graceful Shutdown
Event code |
0x203000de |
Message text |
OS Graceful Shutdown |
Variable fields |
N/A |
Severity level |
Info |
Example |
OS Graceful Shutdown |
Impact |
The system shut down. |
Cause |
The Windows OS was shut down gracefully. |
Recommended action |
No action is required. |
Slot / Connector
Device disabled: PCIe module information not obtained
Event code |
0x21000012 |
Message text |
Device disabled: PCIe module information not obtained---Slot $1 |
Variable fields |
$1: PCIe slot number. |
Severity level |
Major |
Example |
Device Disabled: PCIe module information not obtained---Slot 1 |
Impact |
The PCIe module cannot be identified, which decrease the system performance. |
Cause |
The PCIe module is faulty. |
Recommended action |
1. Verify that the server starts up with the minimum configuration. For more information, see H3C Servers Troubleshooting Guide. 2. Verify that port is disabled in the BIOS. 3. Verify that the PCIe module is compatible with the server. 4. Verify that the PCIe module is installed correctly. 5. Install the PCIe module into another slot to verify that the PCIe module is not faulty. 6. If the issue persists, contact Technical Support. |
Fault Status asserted
Event code |
0x210000de |
Message text |
Fault Status asserted:---fan error in slot $1 |
Variable fields |
$1: Slot number. |
Severity level |
Major |
Example |
Fault Status asserted:---fan error in slot 15 |
Impact |
The system might crash due to a PCIe module error. |
Cause |
This message is generated when the OCP fan is absent or blocked. |
Recommended action |
1. Re-install the OCP fan. 2. If the issue persists, replace the OCP fan. |
Transition to Non-Critical from OK
Event code |
0x2110000e |
Message text |
Transition to Non-Critical from OK---slot $1----PCIe Name:$2 |
Variable fields |
$1: PCIe slot number. $2: PCIe module name. |
Severity level |
Major |
Example |
Transition to Non-Critical from OK---slot 15----PCIe Name:NIC-620F-B2-25Gb-2P-1-X |
Impact |
The system might crash due to a PCIe module error. |
Cause |
This message is generated when the system fails to obtain information about network adapter connection. |
Recommended action |
1. Verify that the network adapter is no faulty. 2. Verify that the related links are operating correctly, for example, I2C or MCTP. |
System ACPI Power State
S0 / G0 "working"
Event code |
0x220000de |
Message text |
S0 / G0 "working" |
Variable fields |
N/A |
Severity level |
Info |
Example |
S0 / G0 "working" |
Impact |
No negative impact. |
Cause |
S0/G0 indicate that the system is operating correctly, where G(0-2) indicate the global states (G-States) and S(0-5) indicate the sleep states (S-States). G0 operating status: In this state, you can run the applications. S0 sleep state: Normal operating status. |
Recommended action |
No action is required. |
S0 / G0 "working"
Event code |
0x220800de |
Message text |
S0 / G0 "working"---$1 |
Variable fields |
$1: Reason for a power-on operation, including: · due to virtual power button pressed · due to physical power button pressed · due to ipmi cmd · due to redfish cmd · due to AC lost · due to kvm button pressed · due to snmp cmd |
Severity level |
Info |
Example |
S0 / G0 "working"--- due to virtual power button pressed |
Impact |
No negative impact. |
Cause |
The system is powered on. |
Recommended action |
No action is required. |
S5 / G2 "soft-off"
Event code |
0x225000de |
Message text |
S5 / G2 "soft-off" |
Variable fields |
N/A |
Severity level |
Info |
Example |
S5 / G2 "soft-off" |
Impact |
No negative impact. |
Cause |
S5 / G2 indicates the software shutdown state. You cannot run applications or the operating system in this state. Software shutdown shuts down the entire operating system except the main power supply unit. Almost no power is consumed during software shutdown. The waking time will be longer to reboot the system after a soft shutdown. |
Recommended action |
No action is required. |
S5 / G2 "soft-off"
Event code |
0x225000de |
Message text |
S5 / G2 "soft-off"---$1 |
Variable fields |
$1: Reason for a power-off operation, including: · due to virtual power button pressed · due to physical power button pressed · due to ipmi cmd · due to redfish cmd · due to AC lost · due to kvm button pressed · due to snmp cmd |
Severity level |
Info |
Example |
S5 / G2 "soft-off"--- due to virtual power button pressed |
Impact |
No negative impact. |
Cause |
S5 / G2 indicates the software shutdown state. You cannot run applications or the operating system in this state. Software shutdown shuts down the entire operating system except the main power supply unit. Almost no power is consumed during software shutdown. The waking time will be longer to reboot the system after a soft shutdown. |
Recommended action |
No action is required. |
S4 / S5 soft-off, particular S4 / S5 state cannot be determined
Event code |
0x226000de |
Message text |
S4 / S5 soft-off, particular S4 / S5 state cannot be determined |
Variable fields |
N/A |
Severity level |
Info |
Example |
S4 / S5 soft-off, particular S4 / S5 state cannot be determined |
Impact |
No negative impact. |
Cause |
S4/S5 indicates the software shutdown state, but you cannot identify whether the current state is S4 or S5. S(0-5) indicate the sleep states (S-States). S4 state: · All components are closed including ARM. · Only the platform settings are retained, while other settings are saved in a special location on the drive. · After a successful switch to S4, the system will shut down. · Due to the cessation of almost all programs and configurations, the power consumption is less than 3W. · Upon wake-up, the system needs to enter BIOS Boot Sequence again. · No system restart is required. The system will continue with the S5 shutdown state. |
Recommended action |
No action is required. |
LPC Reset occurred
Event code |
0x22d000de |
Message text |
LPC Reset occurred |
Variable fields |
N/A |
Severity level |
Info |
Example |
LPC Reset occurred |
Impact |
No negative impact. |
Cause |
The server was reset. This message is available only for servers that use Intel processors. |
Recommended action |
No action is required. |
Watchdog2
Watchdog overflowAction:Timer expired
Event code |
0x230000de |
Message text |
Watchdog overflow.Action:Timer expired - status only (no action and no interrupt)---interrupt type:$1---timer use at expiration:$2 |
Variable fields |
$1: Interrupt type. Options include none, SMI, NMI, Messaging Interrupt, and unspecified. $2: Watchdog. Options include reserved, BIOS FRB2, BIOS POST, OS Load, SMS OS, OEM, and unspecified. |
Severity level |
Info |
Example |
Watchdog overflow.Action:Timer expired - status only (no action and no interrupt)---interrupt type:none---timer use at expiration:BIOS FRB2 |
Impact |
System startup failure might occur. |
Cause |
This message is generated when the following conditions are met: · The watchdog is enabled in the BIOS. · The watchdog timer expires. · The timeout action is set to no action. |
Recommended action |
1. For a BIOS POST watchdog timeout, review the event logs to identify hardware errors or BIOS startup errors, and troubleshoot the errors as instructed in the logs. 2. For an OS Load watchdog timeout, verify that no error is present in the system startup environment. If no error is present, proceed to step 5. 3. For an OS Running watchdog timeout, review the OS logs to identify whether software exceptions occurred and troubleshoot the exceptions as instructed in the logs. 4. Identify whether data storms have occurred. If yes, troubleshoot network errors. 5. If the issue persists, contact Technical Support. |
Watchdog overflowAction:Hard Reset
Event code |
0x231000de |
Message text |
Watchdog overflow.Action:Hard Reset---interrupt type:$1---timer use at expiration:$2 |
Variable fields |
$1: Interrupt type. Options include none, SMI, NMI, Messaging Interrupt, and unspecified. $2: Watchdog. Options include reserved, BIOS FRB2, BIOS POST, OS Load, SMS OS, OEM, and unspecified. |
Severity level |
Major |
Example |
Watchdog overflow.Action:Hard Reset---interrupt type:none---timer use at expiration:BIOS FRB2 |
Impact |
System startup failure might occur. |
Cause |
This message is generated when the following conditions are met: · The watchdog is enabled in the BIOS. · The watchdog timer expires during the BIOS POST, OS Load, or SMS/OS phase (indicated by the watchdog timer type). · The timeout action is set to hard reset. |
Recommended action |
1. For a BIOS POST watchdog timeout, review the event logs to identify hardware errors or BIOS startup errors, and troubleshoot the errors as instructed in the logs. 2. For an OS Load watchdog timeout, verify that no error is present in the system startup environment. If no error is present, proceed to step 5. 3. For an OS Running watchdog timeout, review the OS logs to identify whether software exceptions occurred and troubleshoot the exceptions as instructed in the logs. 4. Identify whether data storms have occurred. If yes, troubleshoot network errors. 5. If the issue persists, contact Technical Support. |
Watchdog overflowAction:Power Down
Event code |
0x232000de |
Message text |
Watchdog overflow.Action:Power Down---interrupt type:$1---timer use at expiration:$2 |
Variable fields |
$1: Interrupt type. Options include none, SMI, NMI, Messaging Interrupt, and unspecified. $2: Watchdog. Options include reserved, BIOS FRB2, BIOS POST, OS Load, SMS OS, OEM, and unspecified. |
Severity level |
Major |
Example |
Watchdog overflow.Action:Power Down---interrupt type:none---timer use at expiration:BIOS FRB2 |
Impact |
System startup failure might occur. |
Cause |
This message is generated when the following conditions are met: · The watchdog is enabled in the BIOS. · The watchdog timer expires during the BIOS POST, OS Load, or SMS/OS phase (indicated by the watchdog timer type). · The timeout action is set to power down. The watchdog powered off the system forcibly. Services are interrupted and the data that has not been saved will get lost. |
Recommended action |
1. For a BIOS POST watchdog timeout, review the event logs to identify hardware errors or BIOS startup errors, and troubleshoot the errors as instructed in the logs. 2. For an OS Load watchdog timeout, verify that no error is present in the system startup environment. If no error is present, proceed to step 5. 3. For an OS Running watchdog timeout, review the OS logs to identify whether software exceptions occurred and troubleshoot the exceptions as instructed in the logs. 4. Identify whether data storms have occurred. If yes, troubleshoot network errors. 5. If the issue persists, contact Technical Support. |
Watchdog overflowAction:Power Cycle
Event code |
0x233000de |
Message text |
Watchdog overflow.Action:Power Cycle---interrupt type:$1---timer use at expiration:$2 |
Variable fields |
$1: Interrupt type. Options include none, SMI, NMI, Messaging Interrupt, and unspecified. $2: Watchdog. Options include reserved, BIOS FRB2, BIOS POST, OS Load, SMS OS, OEM, and unspecified. |
Severity level |
Major |
Example |
Watchdog overflow.Action:Power Cycle---interrupt type:none---timer use at expiration:BIOS FRB2 |
Impact |
System startup failure might occur. |
Cause |
This message is generated when the following conditions are met: · The watchdog is enabled in the BIOS. · The watchdog timer expires during the BIOS POST, OS Load, or SMS/OS phase (indicated by the watchdog timer type). · The timeout action is set to power cycle. |
Recommended action |
1. For a BIOS POST watchdog timeout, review the event logs to identify hardware errors or BIOS startup errors, and troubleshoot the errors as instructed in the logs. 2. For an OS Load watchdog timeout, verify that no error is present in the system startup environment. If no error is present, proceed to step 5. 3. For an OS Running watchdog timeout, review the OS logs to identify whether software exceptions occurred and troubleshoot the exceptions as instructed in the logs. 4. Identify whether data storms have occurred. If yes, troubleshoot network errors. 5. If the issue persists, contact Technical Support. |
Entity Presence
Entity Present---License is about to expire
Event code |
0x250000de |
Message text |
Entity Present---License is about to expire |
Variable fields |
N/A |
Severity level |
Minor |
Example |
Entity Present---License is about to expire |
Impact |
No negative impact. |
Cause |
This message is generated when the remaining validity period of the license is less than 10 days. |
Recommended action |
The temporary license is about to expire. Please purchase the formal license. |
Entity Disabled---License has expired
Event code |
0x252000de |
Message text |
Entity Disabled---$1 |
Variable fields |
$1: Certificate state: · License has expired. · License is unavailable. |
Severity level |
Minor |
Example |
Entity Disabled---License has expired |
Impact |
No negative impact. |
Cause |
The certificate has expired or is not available. |
Recommended action |
1. If the temporary license has expired, purchase and activate the formal license. 2. If the license is not available, re-install and activate the existing license or contact Technical Support. |
Management Subsystem Health
Controller access degraded or unavailable
Event code |
0x281000de |
Message text |
Controller access degraded or unavailable---$1 |
Variable fields |
$1: Possible options include Failed to access the SD card and SD card partitions are missing. |
Severity level |
Major |
Example |
Controller access degraded or unavailable---Failed to access the SD card. |
Impact |
No negative impact. |
Cause |
SD card reading failed or the SD card was missing. |
Recommended action |
1. Restart HDM. 2. Reset the SD module for BMC. 3. If the issue persists, contact Technical Support. |
Controller access degraded or unavailable
Event code |
0x282000de |
Message text |
Management controller off-line ---$1 |
Variable fields |
$1: BMC reboot cause. |
Severity level |
Info |
Example |
Management controller off-line---BMC reset |
Impact |
No negative impact. |
Cause |
BMC was restarted. |
Recommended action |
No action is required. |
Battery
Battery low (predictive failure)
Event code |
0x290000de |
Message text |
Battery low (predictive failure)---PCIe slot:$1 |
Variable fields |
$1: PCIe slot number of the storage controller. |
Severity level |
Minor |
Example |
Battery low (predictive failure)---PCIe slot:1 |
Impact |
The reliability of the RAID controller will degrade, which might cause system performance degradation. |
Cause |
The supercapacitor of the storage controller has a low charge, overtemperature, overvoltage, or overcurrent condition. |
Recommended action |
1. Power on the server to charge the supercapacitor. Log in to HDM, and verify that the supercapacitor of the RAID controller is in normal state and identify whether the alarm is cleared. 2. Verify that the power fail safeguard module is installed correctly. 3. Replace the corresponding components, including the battery, supercapacitor, or flash card (if any), and then restart the server. 4. If the issue persists, contact Technical Support. |
Battery failed
Event code |
0x291000de |
Message text |
Battery failed---PCIe slot:$1 |
Variable fields |
$1: PCIe slot number of the storage controller. |
Severity level |
Minor |
Example |
Battery failed---PCIe slot:1 |
Impact |
The reliability of the RAID controller will degrade, which might cause system performance degradation. |
Cause |
An internal error occurred on the power fail safeguard module of the storage controller. Possible reasons include: · The supercapacitor is exhausted or has expired. · The power fail safeguard module failed to be initialized. · The power fail safeguard module subsystem failed. · The supercapacitor failed to be charged. · The battery or supercapacitor fails. |
Recommended action |
1. Log in to HDM, and verify that the supercapacitor of the RAID controller is in normal state. 2. Verify that the power fail safeguard module is installed correctly. 3. Replace the corresponding components, including the battery, supercapacitor, or flash card (if any), and then restart the server. 4. If the issue persists, contact Technical Support. |
Battery presence detected
Event code |
0x292000de |
Message text |
Battery presence detected---PCIe slot:$1 |
Variable fields |
$1: PCIe slot number of the storage controller. |
Severity level |
Info |
Example |
Battery presence detected---PCIe slot:1 |
Impact |
The reliability of the RAID controller will degrade, which might cause system performance degradation. |
Cause |
The battery or supercapacitor of the RAID controller is absent. |
Recommended action |
1. Log in to HDM, and verify that the supercapacitor of the RAID controller is in normal state. 2. Verify that the supercapacitor is installed correctly and the supercapacitor cable is connected correctly. 3. Replace the corresponding components, including the battery, supercapacitor, or flash card (if any), and then restart the server. 4. If the issue persists, contact Technical Support. |
Version Change
Hardware incompatibility detected with associated Entity---Memory is not certified
Event code |
0x2b2000de |
Message text |
Hardware incompatibility detected with associated Entity---Memory is not certified---Location:CPU:$1 CH:$2 DIMM:$3 |
Variable fields |
$1: CPU number. $2: Channel number. $3: DIMM number. |
Severity level |
Minor |
Example |
Hardware incompatibility detected with associated Entity---Memory is not certified---Location:CPU:1 CH:1 DIMM:0 |
Impact |
No negative impact. |
Cause |
This message is generated when the DIMM is not certified. |
Recommended action |
1. Install H3C certified DIMMs. 2. If the issue persists, contact Technical Support. |