Product models and system features
FRUs and compatibility matrixes
180 W AC power module (LSVM1AC800)
Management Ethernet port status LED
Product models and system features
Product models
The H3C S6850-56HF-IM immersion-cooled switch is a high-density intelligent 25G access switch developed by H3C for cloud data centers and cloud computing networks. It provides robust hardware forwarding capabilities and a wide range of data center features.
The S6850 series include the following models:
Product series |
Product model |
Product code |
S6850 series |
S6850-56HF-IM |
LS-6850-56HF-IM |
|
NOTE: · For product selection information, see the switch data sheet: https://www.h3c.com/cn/Products_And_Solution/InterConnect/Products/Switches/. To view the switch product lifecycle management announcement, access https://www.h3c.com/cn/Service/Policy_Trends/Product_Periods/Termination_Notice/Switches_Series/ · To view the product and software compatibility, see the release notes. |
System features
Table 1 Product specifications
Item |
S6850-56HF-IM |
Technical specifications |
|
Dimensions (excluding tank-mount adapter) (H × W × D) |
88 × 487.2 × 800 mm (3.46 × 19.18 × 31.50 in) |
Dimensions (including tank-mount adapter) (H × W × D) |
88 × 538 × 800 mm (3.46 × 21.18 × 31.50 in) |
Dimensions (including packaging) (H × W × D) |
393×685×1150 |
Weight (fully equipped with power modules, excluding transceiver modules/cables) |
≤ 40 kg (88.18 lb) |
Technical specifications |
|
Processor |
Quad-core, 2.2 GHz |
DRAM Memory |
8 GB |
NOR Flash |
2 × 32 MB (32 MB primary and 32 MB backup) |
NAND Flash |
EMMC 4G |
Interface type and quantity |
|
Console ports |
Serial console port: 1 |
Management Ethernet ports |
100M/1000M Base-T copper port: 1 |
USB port |
1 |
SFP28 ports |
48 |
QSFP28 ports |
8 |
IRF physical ports |
QSFP28 ports on the device panel |
Number of power module slots |
|
Power module slots |
2 |
Power module specifications |
|
Power input type |
AC input, 240 V high-voltage DC input |
Power module specifications |
|
Overall power consumption |
|
Typical power consumption Collection standard: Fully-equipped with cables, 50% load |
· Single AC input: 147 W · Dual AC inputs: 152 W |
Power consumption (at full load) Collection standard: Full-equipped with transceiver modules, 100% load |
· Single AC input: 208 W · Dual AC inputs: 213 W |
Overall thermal consumption |
|
Thermal consumption (typical) |
· Single AC input: 501.58 BTU/hour · Dual AC inputs: 518.64 BTU/hour |
Thermal consumption (max) |
· Single AC input: 709.72 BTU/hour · Dual AC inputs: 726.78 BTU/hour |
Heat dissipation |
|
Cooling method |
Single-phase immersion liquid cooling |
Coolant type |
3M: FC-40 fluorinated liquid Noah: 3000A fluoride liquid |
Coolant inlet temperature |
≤ 45°C (113°F) |
Reliability and availability |
|
Power redundancy |
1+1 redundancy |
Hot swapping |
Power module supports hot swapping |
Mean Time Between Failures (MTBF) (years) |
56.7 |
Mean Time To Repair (MTTR) (hours) |
1.5 |
Availability |
99.999698% |
Environment specifications |
|
Altitude |
–60 to +5000 m (–196.85 to 16404.20 ft) |
Operating temperature |
0ºC to 45ºC (32ºF to 113ºF) NOTE: The allowed maximum temperature decreases by 0.33°C (32.59°F) as the altitude increases by 100 m (328.08 ft) from 0 m (0 ft). |
Storage temperature |
–40ºC to +70ºC (–40°F to +158°F) |
Relative humidity (non-condensing) |
5% to 95% |
Certification |
|
Certification |
· Compliant safety standards · Compliant EMC standards · Compliant environmental and eco-friendly standards |
Chassis views
S6850-56HF-IM switch
Figure 1 S6850-56HF-IM front panel
(1) Mounting bracket |
(2) Tank-mount adapter |
(3) USB port |
(4) Management Ethernet copper port |
(5) Serial console port |
(6) SFP28 Ethernet fiber port |
(7) SFP28 port status LED |
(8) QSFP28 port status LED |
(9) QSFP28 Ethernet fiber port |
(10) Serial label pull tab |
(11) Power module status LED |
(12) Power module 1 |
(13) Management Ethernet copper port LED (LINK/ACT) |
(14) Power module 2 |
(15) Power status LED |
(16) System status LED |
Figure 2 S6850-56HF-IM rear panel
Figure 3 S6850-56HF-IM side panel
(1) Mounting bracket |
(2) Chassis rail |
(3) Embedded handle |
|
NOTE: The S6850-56HF-IM immersion-cooled switch provides two power module slots on the front panel, and comes with the one LSVM1AC800 AC power module installed in each slot. |
FRUs and compatibility matrixes
The S6850-56HF-IM immersion-cooled Ethernet switch features a modular design. See Table 2 for details.
Table 2 FRUs and compatibility matrix for the S6850-56HF-IM
Removable component model |
Component code |
S6850-56HF-IM |
Removable power modules |
||
LSVM1AC800 |
9803A074 |
Yes |
|
NOTE: One power module can meet the power requirement of the switch. You can install two power modules on the switch for 1+1 redundancy. |
Removable power modules
The S6850-56HF-IM immersion-cooled Ethernet switch features a modular design. Select the appropriate power modules according to the actual needs.
WARNING! The S6850 & S9850 switch series supports the replacement of redundant backup power modules without powering off the device. To avoid device damage or even bodily injury, before removing or installing a power module, make sure the power module has no power input. |
180 W AC power module (LSVM1AC800)
Appearance
Figure 4 LSVM1AC650 power module
(1) Handle |
(2) Power module status LED |
(3) Power input receptacle |
(4) Power module latch |
For more information about LED description, see "Power module status LED."
Functions
The LSVM1AC800 is an AC input and DC output power module. It provides a maximum output of 800 W. The main features are as shown in Table 3.
Table 3 LSVM1AC800 power module features
Feature |
Description |
For liquid cooling only |
Can be used in coolant. |
Protection function |
The power module provides protection against input overcurrent, input undervoltage, output overvoltage, output shortcircuit, and overtemperature conditions. |
Support for redundancy |
Two power modules can be connected in parallel to achieve 1+1 redundancy and load balancing. |
Support for hot swapping |
You can remove one of the power modules in 1+1 redundancy when the switch is operating. |
Technical specifications
Table 4 LSVM1AC800 specifications
Item |
Specifications |
Dimensions (H × W × D, including the handle) |
40 × 40.6 × 400 mm (1.57 × 1.60 × 15.75 in) |
Weight |
1.03 kg (2.27 lb) |
Rated input voltage range |
100 to 240 VAC @ 50 or 60 Hz |
Max input voltage range |
90 to 264 VAC @ 47 to 63 Hz |
High voltage DC rated input voltage range |
240 VDC |
High voltage DC maximum input voltage range |
180 to 310 VDC |
Rated input current |
5A |
Rated output current |
66.7A |
Rated output voltage |
12V |
Rated output power |
800W |
Fuse rated current |
10A/250V |
Ports
|
NOTE: · As a best practice, use H3C liquid-cooling modules and cables on the switch. · The H3C liquid-cooling modules and cables are subject to change over time. For the most recent list of H3C liquid-cooling modules and cables, contact your H3C Support or marketing staff. · For the specifications of H3C transceiver modules and cables, see H3C Transceiver Modules User Guide. |
Console ports
The S6850-56HF-IM provides a console port. For specifications about the console port, see Table 5.
Table 5 Console port specifications
Item |
Description |
Connector type |
RJ-45 |
Compliant standard |
EIA/TIA-232 |
Operating mode |
Duplex Universal Asynchronous Receiver/Transmitter (UART) |
Transmission baud rate |
9600 bps (default) to 115200 bps |
Support services |
· Provides connection to an ASCII terminal. · Provides connection to the serial port of a local terminal (for example, a PC) running a terminal emulation program |
Management Ethernet ports
The S6850-56HF-IM provides a management Ethernet copper port. You can connect the port to a local PC for software loading and debugging or to a remote management station for remote management.
Table 6 Management Ethernet port specifications
Item |
Description |
Connector type |
RJ-45 |
Compliant standard |
IEEE802.3ab |
Port transmission rate |
Management 100/1000BASE-T port: · 100M full duplex/half duplex · 1000M full duplex · MDI/MDI-X autosensing |
Interface cable media and maximum transmission distance |
Management 100/1000BASE-T interface: Copper ports with Category 5 unshielded twisted pair (UTP), supporting a transmission distance of 100 meters. |
Functions and services |
For device software update and network management |
USB port
The S6850-56HF-IM provides a USB 2.0 port that complies with the OHCI standard and supports a 480Mbps uploading and downloading rate. Through this interface, users can interact with the Flash file system on the switch, for example, uploading or downloading application files or configuration files.
IMPORTANT: · Due to compatibility and driver differences among USB devices of different manufacturers, H3C does not guarantee that USB devices from all manufacturers will function normally on this series of switches. If a USB device is not functioning properly, it is not due to a switch fault. Try using a USB device from a different manufacturer. · The USB port on the switch is designed to output current strictly in accordance with the USB 2.0 standard. Use USB storage devices that fully comply with USB 2.0 standards. If the USB storage device you use does not fully comply with the USB 2.0 standard, the USB port of this switch might fail to recognize the USB device. |
QSFP28 ports
Table 7 QSFP28 port description
Item |
Description |
Port name |
100GE QSFP28 fiber port |
Product support status |
The front panel provides eight QSFP28 ports |
Connector type |
MPO |
Description |
The 100GE QSFP28 Ethernet fiber ports are mainly used for transmitting and receiving 100GE fiber port services. |
Compliant standard |
IEEE802.3ba |
Fiber port properties |
Depends on the transceiver modules installed |
Operating mode |
Full Duplex |
Available transceiver modules and cables |
100G QSFP28 liquid-cooling module as shown in Table 8 |
Table 8 QSFP28 SFP liquid-cooling modules
Transceiver module/cable type |
Transceiver module/cable name |
Central wavelength |
Connector |
Cable specifications |
Mode bandwidth (MHz*km) |
Max transmission distance |
QSFP28 module |
QSFP-100G-SR4-MM850-Y5 |
850 nm |
MPO (PC end, 12 cores) |
50/125 µm MMF |
4700 MHz*km |
100 m (328.08 ft) |
SFP28 ports
Table 9 SFP28 port description
Item |
Description |
Port name |
25GE SFP28 Ethernet fiber port |
Product support status |
The front panel provides 48 SFP28 ports. |
Connector type |
LC |
Description |
The 25GE SFP28 Ethernet fiber ports are mainly used for transmitting and receiving 25GE fiber port services. |
Compliant standard |
IEEE802.3by |
Fiber port properties |
Depends on the cables installed |
Operating mode |
Full Duplex |
Available transceiver modules and cables |
25G SFP28 liquid-cooling cables as shown in Table 10 |
Table 10 SFP28 liquid-cooling cables
Cable type |
Transceiver module/cable name |
Max transmission distance |
SFP28 cable |
SFP-25G-D-CAB-3M-Y |
3 m (9.84 ft) |
SFP-25G-D-CAB-5M-Y |
5 m (16.40 ft) |
LEDs
System status LED
Through the system status LED, you can preliminarily determine the working state of the switch. For more information, see Table 11.
Table 11 Description of the system status LED
LED |
Status |
Description |
SYS |
Steady green |
The switch has been normally started |
Flashing green |
The switch is performing power-on self test (POST). |
|
Steady yellow |
The system has experienced a general fault. |
|
Steady red |
The system has experienced a severe fault. |
|
Off |
The switch is powered off or has not started up correctly |
QSFP28 port status LED
Table 12 Description of the QSFP28 port status LED
Status |
Description |
Steady green |
A module has been installed. The port operates with the highest rate, and the port link is up. |
Flashing green |
The port operates with the highest rate, and is receiving or sending data. |
Steady yellow |
A module has been installed. The port operates with the highest rate, and the port link is up. |
Flashing yellow (3 Hz) |
The port operates with the highest rate, and is receiving or sending data. |
Off |
No module has been installed or no link is present on the port. |
SFP28 port status LED
Table 13 Description of the SFP28 port status LED
Status |
Description |
Steady green |
A module has been installed. The port operates with the highest rate, and the port link is up. |
Flashing green |
The port operates with the highest rate, and is receiving or sending data. |
Steady yellow |
A module has been installed. The port operates with the highest rate, and the port link is up. |
Flashing yellow (3 Hz) |
The port operates with the highest rate, and is receiving or sending data. |
Off |
No module has been installed or no link is present on the port. |
Management Ethernet port status LED
Table 14 Management Ethernet port LED description
LED |
Status |
Description |
LINK/ACT |
Off |
The management Ethernet fiber port does not have a connection. |
Steady green |
The management Ethernet fiber port is operating at 1000 Mbps. |
|
Flashing green |
The management Ethernet fiber port is in sending or receiving data. |
|
Steady yellow |
The management Ethernet fiber port is operating at 100 Mbps. |
|
Flashing yellow |
The management Ethernet fiber port is in sending or receiving data. |
Power status LED
Table 15 Power status LED description
LED |
Status |
Description |
PSU |
Steady green |
The power modules are running normally. |
Steady yellow |
A power module is faulty or absent. |
|
Steady red |
All power modules are faulty or absent. |
Power module status LED
The LSVM1AC800 provides a power LED at the panel to show the input and output state of the power module. For more information about the status of the LED, see Table 16.
Table 16 Description of the power module status LED
Status |
Description |
Steady green |
The power module is operating correctly and is in primary state. |
Flashing green |
The power module is operating correctly and is in standby state. |
Steady yellow |
The power module is faulty or has entered a protection state. |
Flashing yellow |
One of the following power module conditions are present but the power module has not entered a protection state: Output overvoltage, output undervoltage, output overcurrent, power overload, or overtemperature. |
Off |
The current power module does not have power input. If a device has two power modules, one of which has power input but the other does not, the LED on the power module without power input is off. |
Cooling system
The S6850-56HF-IM immersion-cooled switch adopts single-phase immersion liquid cooling technology. The switch is fully immersed in the water for the flow of the liquid to remove the heat. For more information about the liquid cooling system, see H3C Immersion Cooling System User Guide.